BRYAN CONSTRUCTION, INC. | B= | C | 08/09/2018 | Items corrected | DAKOTAB | DAKOTAB | | B= | C | 5928644 |
BRYAN CONSTRUCTION, INC. | BSP | P | 08/08/2018 | State electrical certificate on file | DAKOTAB | DAKOTAB | | BSP | P | 5927085 |
BRYAN CONSTRUCTION, INC. | BSP | P | 08/07/2018 | State plumbing inspection certificate on file | DAKOTAB | DAKOTAB | | BSP | P | 5925684 |
BRYAN CONSTRUCTION, INC. | B= | P | 08/03/2018 | Interior remodel in kitchen building final OK pending mechanical final, state electric certificate -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet, COLORADO COMMERCIAL REFRIG. Mechanical Final Inspection is not Completed yet, COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | P | 5923891 |
BRYAN CONSTRUCTION, INC. | BFR | P | 05/31/2018 | New interior light gauge framed wall OK -- need to complete HRR -- Will need certificate from state electrical and plumbing inspections | DAKOTAB | DAKOTAB | | BFR | P | 5860830 |
COLORADO SHEET METAL CO., INC. | H= | C | 08/08/2018 | INTERLOCKS CONFIRMED, MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 5927514 |
COLORADO SHEET METAL CO., INC. | H= | P | 08/07/2018 | COULD NOT GET THE SYSTEM TO WORK PROPERLY TO TEST THE INTERLOCKS. PLEASE RESCHEDULE WHEN READY. | DUSTINS | DUSTINS | | H= | P | 5926307 |
COLORADO SHEET METAL CO., INC. | HSP | P | 08/07/2018 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. | DUSTINS | DUSTINS | | HSP | P | 5925779 |
COLORADO COMMERCIAL REFRIGERATION, INC | H= | C | 08/06/2018 | REFRIGERATION FINAL OK. | DUSTINS | DUSTINS | | H= | C | 5925127 |
COLORADO SHEET METAL CO., INC. | H= | P | 07/30/2018 | FLEX AND DIFFUSERS OK. GREASE WRAP OK. STILL NEED TO SEE INTERLOCKS. PROVIDE TEST AND BALANCE REPORT FOR FINAL. NOTE: SEE M-701 (BDA 16) FOR INTERLOCKS. | DUSTINS | DUSTINS | | H= | P | 5917755 |
COLORADO COMMERCIAL REFRIGERATION, INC | HRP | C | 07/12/2018 | TWO 325 LB TEST OK. NOTE: SEE M-701 FOR REFRIGERATION CALCS, NO REFRIGERATION LEAKAGE ALARM REQUIRED. | DUSTINS | DUSTINS | | HRP | C | 5900645 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/09/2018 | BUTT CONNECTIONS TO HOOD OK AND GREASE WRAP INSTALLED OK, OK TO FINISH GREASE WRAP TO HOOD. DRYER VENT OK. NEED TO SEE INTERLOCKS AND FLEX AND DIFFUSERS. PROVIDE TEST AND BALANCE REPORT FOR FINAL. | DUSTINS | DUSTINS | | HD | P | 5896817 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/22/2018 | PROVIDE INSTALLATION INSTRUCTIONS FOR GREASE WRAP AND HAVE ON SITE FOR NEXT INSPECTION. MAKE UP AIR DUCTS ABOVE CEILING OK. OK TO WRAP. | DUSTINS | DUSTINS | | HD | P | 5882833 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/08/2018 | GREASE DUCT LIGHT TEST - LIGHT TEST COMPLETE FOR BUTT/COUPLINGS JOINT BETWEEN PIECES TESTED AT SHOP PREVIOUSLY. THREE COUPLINGS TOTAL. HOOD NOT HUNG AT THIS TIME. OK TO WRAP GREASE DUCT FROM CURB TO DUCT COMPLETED.
HOOD WALL INSPECTION - EXISTING WALL IS FREE OF COMBUSTIBLE MATERIALS
STILL NEED - Butt joints on couplings to hood outlets. | MARKB | MARKB | | HD | P | 5869532 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/31/2018 | LIGHT TEST PERFORMED AT CSM SHOP OK ON ALL FITTINGS DUCT AND JOINTS MARKED WITH PAINT | JERRYF | JERRYF | | HD | P | 5860068 |
COLORADO SHEET METAL CO., INC. | XMS | T | 06/15/2018 | PAID (REC#1507709) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised for new layout in kitchen HVAC | JUSTINC | JUSTINC | | XMS | T | 5875640 |