THOMAS GENERAL CONTRACTORS, INC. | B= | C | 11/13/2018 | Shell completed, items corrected | NATHAN | NATHAN | | B= | C | 6023528 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 10/11/2018 | Items have been corrected. Need core/shell completed. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5992168 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 09/24/2018 | Temp CO: Pending MEP fianls and final Zoning ( Expires: 10/24/2018 12:00:00 AM) | RITA | RITA | | B= | P | 5974487 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 09/21/2018 | install drain wrap at restroom sinks, and occupancy sign, complete all required inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Mechanical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5972809 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 08/03/2018 | need RTU framing inspected when done / interior frame with completed required inspections okay. | NATHAN | NATHAN | | BFR | P | 5923432 |
DILLER ELECTRIC LLC | E= | C | 09/21/2018 | | BRIAN | BRIAN | | E= | C | 5972403 |
DILLER ELECTRIC LLC | E= | P | 09/20/2018 | need label on main stating series rated replace with type _____ fuses only-----delete sub panel b-1 from plans----add outlet for recert pump on water heater--- | BRIAN | BRIAN | | E= | P | 5970855 |
DILLER ELECTRIC LLC | E= | P | 09/17/2018 | panel schedule shows fully rated at 22k, 10k breakers installed, label panel w/ AIC rating----no panel B-1 at this time, no circuits to patio at this time----need bushings and lockrings on pvc in bottom of panel---install 15A breakers on MUA and Exhaust fan ------WH not hooked up at this time---outlet labeled B-29 needs gfci protection, did not trip breaker---group neutrals in panel w/ ungrounded conductors they serve----existing RTU 60A ok | MIGUEL | MIGUEL | | E= | P | 5967711 |
DILLER ELECTRIC LLC | ER | P | 09/14/2018 | GRID CEILING IN KITCHEN AREA----OK ----NOTE NEED TO REROUTE THE MC AT PANEL THAT IS OVER THE 2.5" EMT IN THE WALL---- | BRIAN | BRIAN | | ER | P | 5965350 |
DILLER ELECTRIC LLC | ER | P | 09/12/2018 | WALL ABOVE THE WALK IN COOLER---OK | BRIAN | BRIAN | | ER | P | 5962559 |
DILLER ELECTRIC LLC | ES | C | 08/30/2018 | Commercial Service: 400 amp., 4-wire service in existing gear, okay for meter set | GARYL | GARYL | | ES | C | 5950827 |
DILLER ELECTRIC LLC | ER | P | 08/23/2018 | all hard lids this area, except cooler | GARYL | GARYL | | ER | P | 5944212 |
DILLER ELECTRIC LLC | ER | P | 08/15/2018 | half wall in dining/kitchen area, ,,,, all walls are complete except back wall with conduit for lighting going up | GARYL | GARYL | | ER | P | 5935377 |
DILLER ELECTRIC LLC | ER | R | 08/09/2018 | not ready | GARYL | GARYL | | ER | R | 5929128 |
DILLER ELECTRIC LLC | ER | P | 07/31/2018 | all walls, EXCEPT taco bar wall with 3/4" pvc out of wall | GARYL | GARYL | | ER | P | 5919137 |
DILLER ELECTRIC LLC | ESL | C | 06/27/2018 | 5- 3/4" pvc in food bar area ok / | MIGUEL | MIGUEL | | ESL | C | 5886745 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | C | 10/17/2018 | | JERRYF | JERRYF | | H= | C | 5997587 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 10/16/2018 | TAB REPORT RECEIVED STILL NEED PREVIOUS NOTES ADDRESSED | JERRYF | JERRYF | | H= | P | 5995478 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | C | 10/05/2018 | SEE IMAGES | JERRYF | JERRYF | | H= | C | 5986613 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 09/21/2018 | INTERLOCKS ARE COMPLETE - STILL NEED PREVIOUS NOTES ADDRESSED | JERRYF | JERRYF | | H= | P | 5972654 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | P | 09/21/2018 | SUPPORT WATER HEATER FLUE ATTACH PICTURES TO NEXT INSPECTION REQUEST NOTES: ALL TIE DOWNS / DISCONNECTS - / REGULATORS AND VENTS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5972647 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 09/19/2018 | NEED THE FOLLOWING TO COMPLETE FINAL - TAB REPORT - REMOVE WATER HEATER FROM PERMIT AND LEAVE WATER HEATER VENT ON PERMIT - VERIFY INTERLOCKS - EXTEND PLUMBING VENT 3' ABOVE ECONOMIZER - PROPERLY SUPPORT WATER HEATER FLUE EVERY 4' PER INSTALL MANUAL AND COMPLETE SAME VENT ON ROOF | JERRYF | JERRYF | | H= | P | 5969513 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 09/13/2018 | ABOVE CEILING SA / RA GRILLES AND FINAL CONNECTIONS OK IN PREP AND WASH AREA LAY IN CEILING | JERRYF | JERRYF | | HD | P | 5964274 |
ALNOR INC. | H= | C | 09/13/2018 | DRAINS ARE COMPLETE - NO ALARMS REQUIRED | JERRYF | JERRYF | | H= | C | 5964270 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HC | C | 09/10/2018 | RELEASE METER FOR 2# SYSTEM | JERRYF | JERRYF | | HC | C | 5959597 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | C | 09/10/2018 | PRESSURE TEST OK AND PIPING PER PLAN - NEED PLAN REVISION APPROVED SHOWING NEW LINE TO FIRE PIT AND 2# LETTER FROM CSU | JERRYF | JERRYF | | HI | C | 5959584 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 08/28/2018 | FACTORY GREASE DUCT FROM HOOD THROUGH ROOF STILL NEED TO VERIFY GASKET AND FAN INSTALLATION | JERRYF | JERRYF | | HD | P | 5948049 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 08/16/2018 | FACTORY GREASE DUCT OK STILL NEED TO VERIFY ALL OUTER BANDS - MUA DUCT OK | JERRYF | JERRYF | | HD | P | 5936587 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 08/14/2018 | ABOVE CEILING SA AND EXHAUST OK IN RESTROOM HARD LID AREA'S | JERRYF | JERRYF | | HD | P | 5933496 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HSP | P | 08/14/2018 | UNDER GROUND GAS LINE AT FIRE PIT NEEDS PROTECTIVE SLEEVE - VERIFY AT FUTURE INSPECTION | JERRYF | JERRYF | | HSP | P | 5933489 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 08/02/2018 | HOOD WALL OK FOR 18" CLEARANCE | JERRYF | JERRYF | | HD | P | 5922538 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HO | P | 07/27/2018 | PRESSURE TEST AND PIPING OK FOR UNDER GROUND TO FIRE PIT OK TO BURY - NEED STAMPED APPROVED PLANS SHOWING FIRE PIT LINE CONTRACTOR PROCEEDING AT OWN RISK (((((NEED MECHANICAL CONTRACTOR ATTACHED TO THIS PERMIT BEFORE NEXT INSPECTION)))) | JERRYF | JERRYF | | HO | P | 5916571 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | C | 10/04/2018 | Corrections made | SHANEN | SHANEN | | P= | C | 5985521 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | C | 09/21/2018 | Corrections made | SHANEN | SHANEN | | PTO | C | 5972295 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 09/21/2018 | Install south sink behind bar, hook up ice makers, install back-flow for yard hydrant, install dome strainers throughout, rest OK | SHANEN | SHANEN | | P= | P | 5972293 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 08/02/2018 | Ok for in wall domestic water and dwv. Note: need approved plans on site and splice per previous inspection notes. | DANR | DANR | | PTO | P | 5921657 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PB+ | P | 07/27/2018 | Need approved plans, need to inspect yard hydrant, cover at own risk, test OK | SHANEN | SHANEN | | PB+ | P | 5915984 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PB | C | 06/22/2018 | Sanitary and grease waste test OK | SHANEN | SHANEN | | PB | C | 5882517 |
DILLER ELECTRIC LLC | XES | P | 09/17/2018 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised scope of work - added patio - added Sub Panel B1. | BERTHA | BERTHA | | XES | P | 5967368 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | XMS | T | 09/10/2018 | PAID (REC#1535606) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: added gas and changed diffuser | DALEH | DALEH | | XMS | T | 5960250 |
THOMAS GENERAL CONTRACTORS, INC. | XBS | T | 08/09/2018 | PAID (REC#1525643) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Finish revisions - patio clarification | MICHAELA | MICHAELA | | XBS | T | 5928953 |