HL CUSTOM HOMES, LLC | B= | C | 04/23/2019 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 6175748 |
HL CUSTOM HOMES, LLC | B= | P | 04/23/2019 | . Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | NICK | NICK | | B= | P | 6175340 |
HL CUSTOM HOMES, LLC | B= | R | 04/19/2019 | Need no more than 4" openings for guard rails at stairs / Need to install graspable hand rail for upper stair section / Need lower stair section to have graspable hand rail from top noising to bottom noising of stair / All other aspects of final OK. Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | NICK | NICK | | B= | R | 6171843 |
HL CUSTOM HOMES, LLC | BFR | C | 02/13/2019 | Frame items completed / Front deck frame OK | NICK | NICK | | BFR | C | 6106196 |
HL CUSTOM HOMES, LLC | BSP | T | 02/12/2019 | PAID (REC#1575930) ADDITIONAL PLAN REVIEW TIME: $50 From: DANM Reconfigure great room openings; add front deck | DANM | DANM | | BSP | T | 6105357 |
HL CUSTOM HOMES, LLC | BFR | P | 01/15/2019 | Need to verify pads under new location of T-post in basement / Provide design for rated walls between house and garage as shown on plot plan / Update plans to show added door on west side of home / Received updated observation showing date that steel beam in basement was observed | SHAUN | SHAUN | | BFR | P | 6078049 |
HL CUSTOM HOMES, LLC | BIN | P | 01/11/2019 | Complete items in frame inspection notes / BIN insulation okay | SHAUN | SHAUN | | BIN | P | 6076550 |
HL CUSTOM HOMES, LLC | BFN | C | 01/11/2019 | Foundation design on file | SHAUN | SHAUN | | BFN | C | 6076549 |
HL CUSTOM HOMES, LLC | BFT | C | 01/11/2019 | Received all updated paperwork // Still need plot plan | SHAUN | SHAUN | | BFT | C | 6076548 |
HL CUSTOM HOMES, LLC | BFR | R | 01/11/2019 | West door not on plans / Provide plot plan / Other items completed / Observation letters on file / UPDATE: Observation for steel beam in basement does not show date of inspection / Location of t post in basement doesn't match foundation design, need to verify pads under posts / Plot plan doesn't match foot print of master plan | SHAUN | SHAUN | | BFR | R | 6076547 |
HL CUSTOM HOMES, LLC | BFR | R | 01/09/2019 | 1. Request items to complete BFT, BFN, BFD prior to any further field inspections / 2. Missing 2nd H2.5 at each T02 truss front bearing wall / 3. Missing 2nd king EE of front bedroom window / 4. Strap top plate at master bath / 5. Missing 2nd trimmer at right side of great room rear window / 6. Door at great room not on approved plans / 7. Missing hangers at basement landing / 8. T post in basement do not match locations on approved plans // Finished basement / Plans reviewed electronically / Unable to verify plot plan - Will need to verify plot plan | JUSTINL | JUSTINL | | BFR | R | 6073739 |
HL CUSTOM HOMES, LLC | BSP | P | 01/09/2019 | Engineer observation for front porch piers received - plans for deck not on file - Request plans for deck - front deck and porch to be inspected at later date as BSP | JUSTINL | JUSTINL | | BSP | P | 6073731 |
HL CUSTOM HOMES, LLC | BFD | P | 01/09/2019 | Engineer observation for drain received - Damp proof noted - Engineer observation missing date of observation - Request observation with date of inspection | JUSTINL | JUSTINL | | BFD | P | 6073726 |
HL CUSTOM HOMES, LLC | BFN | P | 01/09/2019 | Engineer observation for foundation received - Ufer noted / Request foundation design
| JUSTINL | JUSTINL | | BFN | P | 6073725 |
HL CUSTOM HOMES, LLC | BFT | P | 01/09/2019 | Engineer observation for footers received / Soils and open hole received - request clarification of bearing capacity - soils references 14000 PSF - Open hole references 1500 PSF / Request foundation design / Drain to be entire / 10% | JUSTINL | JUSTINL | | BFT | P | 6073723 |
HL CUSTOM HOMES, LLC | BFD | P | 06/12/2018 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFD | P | 5872433 |
HL CUSTOM HOMES, LLC | BFN | P | 06/12/2018 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFN | P | 5872431 |
HL CUSTOM HOMES, LLC | BFT | P | 06/12/2018 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFT | P | 5872432 |
BEE ELECTRIC LLC | E= | C | 04/10/2019 | | JOHNN | JOHNN | | E= | C | 6161148 |
BEE ELECTRIC LLC | E= | R | 03/12/2019 | install arc shields on receptacles at white paneling / strap riser / expose ufer / | MIGUEL | MIGUEL | | E= | R | 6131455 |
BEE ELECTRIC LLC | ES | C | 11/20/2018 | Residential Underground: New 150 amp service, | GARYL | GARYL | | ES | C | 6031242 |
BEE ELECTRIC LLC | ER | C | 11/20/2018 | Finished basement, no cen vac, expose ufer at final, | GARYL | GARYL | | ER | C | 6031241 |
MOUNTAIN VIEW COMFORT | H= | C | 04/18/2019 | | MATTM | MATTM | | H= | C | 6170991 |
MOUNTAIN VIEW COMFORT | H= | P | 04/15/2019 | BOTH BASEMENT BEDROOMS LACK RETURN AIR PATH, PROTECT LOW VOLT WIRES AT FURNACE CABINET, MISSING FURNACE FILTER, COMPLETELY SEAL RETURN DUCT TO FILTER BASE, OK TO ATTACH PICTURES TO NEXT INSPECTION REQUEST NOTES: FINISHED BASEMENT, LOUVER DOOR TO MECHANICAL ROOM, OUTSIDE AIR TO FURNACE RETURN, NO A/C, NO FIREPLACE | MATTM | MATTM | | H= | P | 6166328 |
MOUNTAIN VIEW COMFORT | H= | R | 04/11/2019 | CONFIRMED CALL AHEAD AT 1:55PM, NOBODY ON SITE, DOORS LOCKED, NO LOCK BOX CODE PROVIDED. B-VENT REQUIRED TO TERMINATE AT LEAST 1 FOOT ABOVE ROOF. | MATTM | MATTM | | H= | R | 6163012 |
MOUNTAIN VIEW COMFORT | HC | C | 01/08/2019 | RELEASE METER | PAULO | PAULO | | HC | C | 6072288 |
MOUNTAIN VIEW COMFORT | HI | C | 01/08/2019 | 10# test ok. note: 1" main at 30' to 1- furnace and 1- water heater. | PAULO | PAULO | | HI | C | 6072286 |
MOUNTAIN VIEW COMFORT | HRR | C | 01/04/2019 | note: finished basement, outside air to return, no a/c. | PAULO | PAULO | | HRR | C | 6068089 |
MOUNTAIN VIEW COMFORT | HRR | T | 01/03/2019 | PAID (REC#1567090) not ready. need to pay trip fee and recall inspection under code HRR. note: finished basement, outside air to return, no a/c. | PAULO | PAULO | | HRR | T | 6067901 |
MOUNTAIN VIEW COMFORT | HSP | P | 12/14/2018 | had conversation with Ivan about HRR (rough inspection notes) missing standard option for duct design, mechanical pg. M1 shows extended option. need splice for standard duct design. | PAULO | PAULO | | HSP | P | 6052923 |
MOUNTAIN VIEW COMFORT | HRR | T | 12/13/2018 | PAID (REC#1567090) not ready. still need to address the following-- (splice for duct design without extended option), all S.A. ducts to rec. room undersized, missing S.A. duct to great room. note: finished basement, outside air to return, no a/c. (CALL ME IN THE MORNING FROM 7:30 TO 8:30 A.M. 799-2871. | PAULO | PAULO | | HRR | T | 6052596 |
MOUNTAIN VIEW COMFORT | HRR | P | 12/07/2018 | not ready, waived trip fee. still need to address the following-- (duct design without extended option), all S.A. ducts to rec. room undersized, missing S.A. duct to great room. note: finished basement, outside air to return, no a/c. | PAULO | PAULO | | HRR | P | 6046880 |
MOUNTAIN VIEW COMFORT | HI | P | 12/07/2018 | cannot use thread protector as a coupling (re- test needed). note: 1" main at 30' to 1- furnace and 1- water heater. | PAULO | PAULO | | HI | P | 6046879 |
MOUNTAIN VIEW COMFORT | HRR | P | 12/03/2018 | need to address the following-- correct duct design without extended option (all S.A. ducts to rec. room undersized, missing S.A. duct to great room, extend S.A. duct in bedroom #5, complete all venting to installed appliances, proper support to dryer exhaust duct, nail protection to dryer exhaust duct. RE-INSPECT ALL. note: finished basement, outside air to return, no a/c. | PAULO | PAULO | | HRR | P | 6041493 |
DMB PLUMBING SERVICES INC. | P= | C | 03/21/2019 | Corrections made | MALYNDA | MALYNDA | | P= | C | 6139259 |
DMB PLUMBING SERVICES INC. | P= | P | 03/19/2019 | leak at hall toilet, need trap guard at floor drain in mech, rest ok note: finished basement, no irrigation | JOSEPHD | JOSEPHD | | P= | P | 6137530 |
DMB PLUMBING SERVICES INC. | PTO | C | 11/26/2018 | Finished basement, no irrigation | SHANEN | SHANEN | | PTO | C | 6033660 |
DMB PLUMBING SERVICES INC. | PB | C | 09/20/2018 | Basement fixtures only to lift station | SHANEN | SHANEN | | PB | C | 5971269 |