THOMAS GENERAL CONTRACTORS, INC. | B= | C | 04/09/2019 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 6159634 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 03/21/2019 | All corrections complete. Additional Inspections Required (computer generated): ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 6139822 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 02/11/2019 | need all completed final inspections, mount drinking fountain at correct height, vertical grab bar at restroom not in correct location, to far from back wall, post restroom signage. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 6103262 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 11/16/2018 | with completed required inspections frame okay. Reviewed Accessible Elements / | NATHAN | NATHAN | | BFR | P | 6027985 |
THOMAS GENERAL CONTRACTORS, INC. | BIN | P | 11/05/2018 | exterior walls okay | NATHAN | NATHAN | | BIN | P | 6015768 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | R | 11/05/2018 | need completed splice for frame inspection, | NATHAN | NATHAN | | BFR | R | 6015763 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 10/31/2018 | west exterior wall frame with completed required inspections okay | NATHAN | NATHAN | | BFR | P | 6011814 |
THOMAS GENERAL CONTRACTORS, INC. | BFT | P | 09/13/2018 | Still need to splice plans to show S sheets or may have wrong permit called in, could not find correct permit on line in the field / Interior strip footing installed per Eng design on site / Still need Eng detail for water line in F1 pad on south side, contractor said that will move pad in and lower under water line, at time of inspection this was the case / Still need open hole report | NICK | NICK | | BFT | P | 5963969 |
THOMAS GENERAL CONTRACTORS, INC. | BFN | R | 09/11/2018 | No S sheets on approved uploaded plans / Eng stamped S sheets on site show F1 and F2 pads / F1 pad on south side has water line running through, will need Eng / Still need to inspect interior strip footing / Need to splice plans to show S sheets / Need to attach all MEP's / Need open hole report / Poor all other pads at own risk | NICK | NICK | | BFN | R | 5961663 |
DILLER ELECTRIC LLC | E= | C | 02/04/2019 | | BRIAN | BRIAN | | E= | C | 6096526 |
DILLER ELECTRIC LLC | E= | P | 02/01/2019 | gfci protect drinking fountain / ko plug in light j box back office / no power to roof top gfci / no power to s.east office and rear break room / panel sch / | BRIAN | BRIAN | | E= | P | 6095061 |
DILLER ELECTRIC LLC | ES | C | 12/03/2018 | Commercial Service: 200 amp 4-w ---ok for contractor to sch switch over with csu---ok to set meter--------------------------NOTE------need to add 2 ground rods and intersystem bond by final | BRIAN | BRIAN | | ES | C | 6041077 |
DILLER ELECTRIC LLC | ER | P | 11/28/2018 | entry soffit at bottom of stairs--ok | BRIAN | BRIAN | | ER | P | 6036202 |
DILLER ELECTRIC LLC | ER | P | 11/07/2018 | rest of the walls and hard lids---ok | BRIAN | BRIAN | | ER | P | 6018414 |
DILLER ELECTRIC LLC | ER | P | 10/31/2018 | walls and hard lids on 2nd floor ---except the panel room---- | BRIAN | BRIAN | | ER | P | 6011419 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | C | 04/09/2019 | ALL OK | JERRYF | JERRYF | | H= | C | 6159633 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 03/29/2019 | PARTIAL PENDING PICTURES OF RTU | JERRYF | JERRYF | | H= | P | 6148492 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 03/22/2019 | TAB REPORT SHOWS 18 SA GRILLES / PLAN SHOWS 21 SA GRILLES | JERRYF | JERRYF | | H= | P | 6140633 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 03/21/2019 | PARTIAL PENDING THE FOLLOWING - TAB REPORT AND LEVEL RTU PER PREVIOUS NOTES NOTES: PLAN SPLICE IS COMPLETE | JERRYF | JERRYF | | H= | P | 6139505 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 03/11/2019 | PARTIAL PENDING THE FOLLOWING - TAB REPORT - PLAN REVISIONS SHOWING NORTH END AS FUTURE TENANT FINISH - DELETING 1 TRANSFER FAN - LEVEL RTU #4 AND INSTALL DRAIN | JERRYF | JERRYF | | H= | P | 6129994 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 02/08/2019 | NEED THE FOLLOWING - DELETE 2 TRANSFER FANS FROM PERMIT - REVISE PLAN TO MATCH INSTALLED - CO2 SENSOR - ROOF INSPECTION TO VERIFY UNITS AND SAFETY RAILINGS - ACCESS LADDER AT PARAPET TAB REPORT - NEED ALL TRANSFER GRILLES - WHAT IS BEING DONE WITH NORTH END OFFICES AND CORRIDOR ROOMS 219 - 222 - 223 - 224 - 225 AND CORRIDOR | JERRYF | JERRYF | | H= | P | 6101829 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | C | 01/31/2019 | ALL FINAL CONNECTIONS / REGULATORS AND VENTS OK NOTES: 2# LETTER RECEIVED | JERRYF | JERRYF | | H= | C | 6093390 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HC | C | 01/31/2019 | RELEASE METER | JERRYF | JERRYF | | HC | C | 6093388 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | C | 01/31/2019 | PRESSURE TEST OK AND PIPING PER PLAN | JERRYF | JERRYF | | HI | C | 6093387 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | P | 01/31/2019 | 2# LETTER RECEIVED | JERRYF | JERRYF | | HI | P | 6093149 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 11/06/2018 | ABOVE HARD LID SA / EXHAUST OK - NEED PLAN REVISED FOR ALL OTHER HVAC FOR NEXT INSPECTION | JERRYF | JERRYF | | HD | P | 6017197 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | C | 03/19/2019 | corrections made | JOSEPHD | JOSEPHD | | P= | C | 6137588 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 02/07/2019 | need approval for single drinking fountain and bottle filler, need trap guards in both floor drains in mens and womens bathrooms, sink by water heater not complete | JOSEPHD | JOSEPHD | | P= | P | 6100888 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | C | 11/01/2018 | Need revisions for drinking fountain delete ( not roughed-in ), rest OK | SHANEN | SHANEN | | PTO | C | 6012626 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 10/17/2018 | Under floor DWV test OK | SHANEN | SHANEN | | PTO | P | 5997089 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PB | C | 10/17/2018 | Tie-in OK | SHANEN | SHANEN | | PB | C | 5997085 |
PRESTIGE MECHANICAL CONTRACTORS,INC | XPS | P | 03/12/2019 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Plumbing splice 3/12/19: Accessible drinking fountain with bottle filler | SHANEN | SHANEN | | XPS | P | 6131285 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | XMS | P | 03/11/2019 | PLAN SPLICE FEE: $0 by: TCRIPPEN for Mechanical: mechanical splice 3-11-19 New splice See As Built Notes on plan pages. | TCRIPPEN | TCRIPPEN | | XMS | P | 6130104 |
THOMAS GENERAL CONTRACTORS, INC. | XBS | T | 03/11/2019 | PAID (REC#1582002) PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Revised drinking fountain | LBENNETT | LBENNETT | | XBS | T | 6130047 |
THOMAS GENERAL CONTRACTORS, INC. | XBS | T | 12/11/2018 | PAID (REC#1562649) PLAN SPLICE FEE: $50 by: DANM for Construction: Revised Roof Ledger Detail (7/S1.3) | DANM | DANM | | XBS | T | 6048630 |
THOMAS GENERAL CONTRACTORS, INC. | XBS | T | 11/27/2018 | PAID (REC#1558851) PLAN SPLICE FEE: $50 by: DANM for Construction: Added urinal to Men's Restroom | DANM | DANM | | XBS | T | 6034632 |
PRESTIGE MECHANICAL CONTRACTORS,INC | XPS | P | 11/27/2018 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Plumbing: plumbing splice 11-27-18 | TCRIPPEN | TCRIPPEN | | XPS | P | 6034627 |
THOMAS GENERAL CONTRACTORS, INC. | XBS | T | 11/14/2018 | PAID (REC#1556234) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Minor changes add structural | MICHAELA | MICHAELA | | XBS | T | 6024881 |
DILLER ELECTRIC LLC | XES | P | 11/14/2018 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised power and lighting for background change. | BERTHA | BERTHA | | XES | P | 6024869 |