PEAK PROFESSIONAL CONTRS INC | B= | C | 12/20/2018 | | BERTW | BERTW | | B= | C | 6059856 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 12/06/2018 | Temp CO: extension ( Expires: 1/5/2019 12:00:00 AM) | GITA | GITA | | B= | P | 6044719 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 11/12/2018 | Need core/shell completed, towel dispenser corrected -- Schedule a new Building Final when above items are complete. | NATHAN | NATHAN | | B= | P | 6023038 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 10/26/2018 | Temp CO: all trades partialed or done ( Expires: 11/25/2018 12:00:00 AM) | GITA | GITA | | B= | P | 6007701 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 10/16/2018 | need soap dispensers to activate no more than 48" in height, need core/shell completed, complete all final inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Mechanical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet, MAUI MECHANICAL, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5995954 |
PEAK PROFESSIONAL CONTRS INC | BSP | R | 08/31/2018 | NEED MECHANICAL PERMIT AND INSPECTION FOR HOOD WALL BEFORE COVER. | NATHAN | NATHAN | | BSP | R | 5952668 |
PEAK PROFESSIONAL CONTRS INC | BFR | R | 08/21/2018 | inspection was not needed canceled at the curb | NATHAN | NATHAN | | BFR | R | 5940874 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 08/07/2018 | need attached mechanical permit and inspection / backing installed / partial frame okay with completed required inspections Reviewed Accessible Elements / | NATHAN | NATHAN | | BFR | P | 5926338 |
EL PASO ELECTRIC, LLC. | E= | C | 10/30/2018 | corrections made / | MIGUEL | MIGUEL | | E= | C | 6010620 |
EL PASO ELECTRIC, LLC. | E= | P | 10/19/2018 | replace circuit 24 GFCIs located above 6' 6" in kitchen to standard receptacles and protect w/ blank face at panel / | MIGUEL | MIGUEL | | E= | P | 6000344 |
EL PASO ELECTRIC, LLC. | E= | P | 10/18/2018 | replace GFCI at drive thru soda dispenser to standard receptacle--can not have gfci behind equipment above counter on wall behind pos---receptacles up high on wall not gfci protected / | MIGUEL | MIGUEL | | E= | P | 5999495 |
EL PASO ELECTRIC, LLC. | E= | P | 10/16/2018 | receptacles on wall behind POS station not GFCI protected, 1 blank face GFCI not testing, maybe same circuit ----replace GFCI receptacle at soda dispenser / | MIGUEL | MIGUEL | | E= | P | 5996660 |
EL PASO ELECTRIC, LLC. | E= | P | 10/15/2018 | CAN NOT HAVE GFCI DEVICE BEHIND SODA DISP OR EQUIPMENT----NO DEVICES ABOVE 6'6' WITH RESET BUTTONS----NEED PANEL SCH--- | BRIAN | BRIAN | | E= | P | 5994541 |
EL PASO ELECTRIC, LLC. | ER | P | 10/03/2018 | above ceiling in kitchen area ok / | MIGUEL | MIGUEL | | ER | P | 5984946 |
EL PASO ELECTRIC, LLC. | ES | P | 10/02/2018 | Commercial Service: 400 amp,4w, new commercial, ok to set meter in unit 100,--------fuses are 200K, check branch circuits later, | JOHNN | JOHNN | | ES | P | 5982354 |
EL PASO ELECTRIC, LLC. | ES | R | 09/28/2018 | 400 amp,4w, need 400 amp fuses rated for the available fault current, existing fuses are 20K, ok to upload pics,----------------------------check branch circuits in panel later, | JOHNN | JOHNN | | ES | R | 5979752 |
EL PASO ELECTRIC, LLC. | ES | R | 09/19/2018 | Commercial Service: need access to suite and panel open / | MIGUEL | MIGUEL | | ES | R | 5970586 |
EL PASO ELECTRIC, LLC. | ER | P | 08/16/2018 | WALLS AND HARD LIDS--OK | BRIAN | BRIAN | | ER | P | 5936282 |
MAUI MECHANICAL, INC. | H= | C | 11/05/2018 | GREASE FAN EXTENSION IS COMPLETE | JERRYF | JERRYF | | H= | C | 6015619 |
MAUI MECHANICAL, INC. | H= | P | 10/23/2018 | NEW TAB REPORT RECEIVED - STILL NEED GREASE FAN EXTENSION | JERRYF | JERRYF | | H= | P | 6002704 |
MAUI MECHANICAL, INC. | H= | C | 10/23/2018 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6002658 |
MAUI MECHANICAL, INC. | H= | P | 10/23/2018 | TAB REPORT MUST HAVE APPROVED STAMP | JERRYF | JERRYF | | H= | P | 6002540 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 10/18/2018 | | JERRYF | JERRYF | | H= | C | 5998354 |
LANDMARK PLUMBING AND HEATING, INC. | H= | P | 10/16/2018 | NEED TIE DOWN AT PATTY PRESS ATTACH PICTURE TO NEXT INSPECTION REQUEST | JERRYF | JERRYF | | H= | P | 5995555 |
MAUI MECHANICAL, INC. | H= | P | 10/15/2018 | PENDING TAB REPORT AND GREASE FAN EXTENSION ATTACH PICTURE OF FAN EXTENSION TO TAB REPORT NOTES: INTERLOCKS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5994525 |
LANDMARK PLUMBING AND HEATING, INC. | H= | P | 10/12/2018 | NEED THE FOLLOWING - ALL PREVIOUS NOTES FROM LAST HI INSPECTION - CHANGE WATER HEATER ON PERMIT FROM MOBILE HOME WATER HEATER - SUPPORT WATER HEATER FLUES PER INSTALL MANUAL STOPPED INSPECTION | JERRYF | JERRYF | | H= | P | 5993580 |
LANDMARK PLUMBING AND HEATING, INC. | H= | P | 10/11/2018 | NEED THE FOLLOWING - COMPLETE WATER HEATER VENTS - T&P DRAIN AT WATER HEATER - PICTURE OF TIE DOWN AT PATTY PRESS - VERIFY BALL BEARINGS HAVE BEEN REMOVED AT ALL EXTERIOR GAS REGULATORS VENTS | JERRYF | JERRYF | | H= | P | 5991955 |
MAUI MECHANICAL, INC. | HD | P | 10/08/2018 | ALL ABOVE CEILING FINAL CONNECTIONS ARE COMPLETE AT ALL SA / RA AND EXHAUST GRILLES - STILL NEED INTERLOCKS - SEAL ALL METAL SURFACES ABOVE HOOD AT WALL - GREASE FAN EXTENSION - CONTROLS - CONDENSATE DRAINS AT WALK IN | JERRYF | JERRYF | | HD | P | 5988380 |
MAUI MECHANICAL, INC. | HD | P | 10/03/2018 | NEED GREASE DUCT INSTALL MANUAL FOR INSPECTION - NEED GREASE FAN EXTENDED ABOVE ROOF TO 40" NOTES: DINING AREA SA / RA MAINS AND RUN OUTS OK | JERRYF | JERRYF | | HD | P | 5984217 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 10/03/2018 | RELEASE METER FOR 2# SYSTEM | JERRYF | JERRYF | | HC | C | 5984164 |
LANDMARK PLUMBING AND HEATING, INC. | HI | C | 10/03/2018 | LABELS INSTALLED - AT FUTURE INSPECTION VERIFY ALL REGS AND FINAL CONNECTIONS | JERRYF | JERRYF | | HI | C | 5984154 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 10/02/2018 | UNABLE TO VIEW PLANS IN COMPUTER - NEED TO REVIEW PLANS TO VERIFY MEDIUM PRESSURE NOTES: PRESSURE TEST OK - PIPING PER PLAN - NEED LINE TAGGED AT EXTERIOR BEFORE METER RELEASE ATTACH PICTURE TO NEXT INSPECTION REQUEST | JERRYF | JERRYF | | HI | P | 5983538 |
MAUI MECHANICAL, INC. | HRP | C | 09/26/2018 | WALK IN COOLER OK NO DRAINS REQUIRED - WILL VERIFY IF ALARMS ARE REQUIRED AT FUTURE INSPECTION | JERRYF | JERRYF | | HRP | C | 5976930 |
MAUI MECHANICAL, INC. | HSP | P | 09/26/2018 | WILL DOING COOLER INSPECTION NOTICED LARGE GAPS AT STAINLESS SURFACE BEHIND AND ABOVE HOOD NEED PICTURES OF ALL JOINTS SEALED BEFORE HOOD IS HUNG | JERRYF | JERRYF | | HSP | P | 5976920 |
MAUI MECHANICAL, INC. | HD | P | 09/05/2018 | HOOD WALL OK | JERRYF | JERRYF | | HD | P | 5955684 |
MAUI MECHANICAL, INC. | HD | P | 09/04/2018 | NEED INSPECTION FOR WALL AFTER PLYWOOD HAS BEEN REMOVED BEHIND METAL LINER - REST OF HOOD WALL OK | JERRYF | JERRYF | | HD | P | 5954246 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 10/19/2018 | Corrections made | SHANEN | SHANEN | | P= | C | 5999805 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 10/16/2018 | Leak under front area hand sink, adjust air-gap at prep sink drain, rest OK | SHANEN | SHANEN | | P= | P | 5995837 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 10/12/2018 | In ceiling vents and water distribution OK | SHANEN | SHANEN | | PTO | C | 5993119 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 10/12/2018 | No hot water re-inspect all, need air gaps at all indirect wastes, need to connect vent to in-wall vents | SHANEN | SHANEN | | P= | P | 5993114 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 08/14/2018 | In -wall DWV and water distribution test OK | SHANEN | SHANEN | | PTO | P | 5933056 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 07/16/2018 | Grease waste and sanitary sewer - test OK | SHANEN | SHANEN | | PB | C | 5903106 |