SUN CONSTRUCTION & FACILITY SERVICES, INC. | B= | C | 07/22/2020 | Received engineers observation letter for excavations, concrete fills, steel reinforcement, and structural concrete / Final building inspection complete | TIMOTHYS | TIMOTHYS | | B= | C | 6646293 |
SUN CONSTRUCTION & FACILITY SERVICES, INC. | BE | L | 07/21/2020 | Renewed for No Fee at 7/21/2020 9:07:59 AM | SABRINA | SABRINA | | BE | L | 6643971 |
SUN CONSTRUCTION & FACILITY SERVICES, INC. | BSP | P | 11/08/2018 | Courtesy drywall inspection - not required to be inspected (non-rated non-structural walls) | RICHB | RICHB | | BSP | P | 6020027 |
SUN CONSTRUCTION & FACILITY SERVICES, INC. | BFR | P | 11/05/2018 | Framing for full-height non-rated walls and door openings OK pending other Roughs - see wall type B6W on Sheet A2.01 | RICHB | RICHB | | BFR | P | 6015760 |
DYNALECTRIC COMPANY | E= | C | 12/13/2018 | | GARYL | GARYL | | E= | C | 6052326 |
DYNALECTRIC COMPANY | E= | P | 11/29/2018 | | GARYL | GARYL | | E= | P | 6038084 |
DYNALECTRIC COMPANY | E= | C | 11/29/2018 | FIRE ALARM INSPECTION: | GARYL | GARYL | | E= | C | 6038074 |
DYNALECTRIC COMPANY | E= | C | 11/29/2018 | FIRE ALARM INSPECTION: | GARYL | GARYL | | E= | C | 6038075 |
DYNALECTRIC COMPANY | ER | P | 11/02/2018 | FIRE ALARM INSPECTION: one and only wall with fire alarm | GARYL | GARYL | | ER | P | 6014759 |
DYNALECTRIC COMPANY | ER | P | 11/02/2018 | 1) 3-3" conduits, empty, 2) load on 4-- vfd's, CHWP-- 4 and 5 5& 6, | GARYL | GARYL | | ER | P | 6014728 |
DYNALECTRIC COMPANY | ER | P | 09/13/2018 | pipes run from mdp to md5,md6,ok, vfd's: pipe/wire on line side,ok | JOHNN | JOHNN | | ER | P | 5964487 |
MECHONE, INC. | H= | C | 01/02/2019 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6066262 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 12/28/2018 | | JERRYF | JERRYF | | H= | C | 6064664 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 11/19/2018 | PRESSURE TESTS OK ON 2ND FLOOR CHILLED SUPPLY AND RETURN FROM MAINS TO TIE INS AND HEATING WATER TO AHU-C9- A | JERRYF | JERRYF | | HWP | P | 6030142 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 10/31/2018 | PRESSURE TEST OK ON CONDENSER WATER FROM TOWER / CHILLED SUPPLY PIPING FROM PUMPS TO SECOND FLOOR - TOWER DRAIN LINE FROM TOWER TO FLOOR SINK AND HEAT TAPE OK - STILL NEED SEE TO INSULATION ON SAME | JERRYF | JERRYF | | HWP | P | 6011923 |
MECHONE, INC. | H= | P | 10/22/2018 | PARTIAL FINAL PENDING TAB REPORT | JERRYF | JERRYF | | H= | P | 6001978 |
MECHONE, INC. | HD | C | 10/22/2018 | ABOVE CEILING OUTSIDE AIR AND EXHAUST MAINS AND RUN OUTS OK | JERRYF | JERRYF | | HD | C | 6001963 |
MECHONE, INC. | H= | L | 10/19/2018 | AUTO CALL COMPLETE AT 12:56 - ARRIVED 1:22 - CALLED CONTRACTOR - CONTRACTOR CANCELED | JERRYF | JERRYF | | H= | L | 6000443 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 10/04/2018 | THE FOLLOWING PIPING WAS INSPECTED AND IS OK - ALL OVER HEAD CONDENSER SUPPLY AND RETURN - ALL OVER HEAD CHILLED - OVER HEAD CONDENSER RETURN TO TOWER - OVER HEAD CONDENSER SUPPLY TO PUMPS - CHILLED SUPPLY AND RETURN TO HEAT EXCHANGER - OVER HEAD RETURN TO 2ND FLOOR - (((((STILL NEED FINAL CONNECTIONS AT ALL MACHINES AND CHILLED WATER TO 2ND FLOOR FROM PUMPS AND COMPLETION OF 2ND FLOOR PIPING ))))) | JERRYF | JERRYF | | HWP | P | 5986491 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 12/28/2018 | | TAYLOR | TAYLOR | | P= | C | 6064991 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 10/04/2018 | Check vent tie-in and insulation at final | SHANEN | SHANEN | | PTO | C | 5986378 |
OLSON PLUMBING & HEATING COMPANY | PB | C | 08/10/2018 | Base DWV test OK | SHANEN | SHANEN | | PB | C | 5931028 |