HOMEOWNER | B= | C | 02/26/2019 | | LONNYS | LONNYS | | B= | C | 6117393 |
HOMEOWNER | B= | P | 02/22/2019 | Rear downspout missing tipout - Other item corrected -- Schedule a new Building Final when above items are complete. | TIMOTHYS | TIMOTHYS | | B= | P | 6115186 |
HOMEOWNER | B= | P | 02/11/2019 | need to move address to street side of home / missing gutters and down spouts / slab - no decks -- Schedule a new Building Final when above items are complete. | LONNYS | LONNYS | | B= | P | 6103276 |
HOMEOWNER | BIN | C | 11/30/2018 | | LONNYS | LONNYS | | BIN | C | 6038852 |
HOMEOWNER | BFR | C | 11/30/2018 | H2.5s OK at front porch per plan splice | LONNYS | LONNYS | | BFR | C | 6038851 |
HOMEOWNER | BIN | P | 11/28/2018 | complete bfr | DALE | DALE | | BIN | P | 6036646 |
HOMEOWNER | BFR | P | 11/21/2018 | Still could not verity (2) H2.5 @ front porch beam bearing / other items corrected | PARKER | PARKER | | BFR | P | 6032512 |
HOMEOWNER | BFR | P | 11/20/2018 | front porch post caps to be installed in pairs / could not verify 2nd H2.5 at front porch beam bearing / missing 3rd king EE slider / foam and fire block incomplete throughout / OK to insulate - follow insulation specs provided by PPRBD IECC standards handout in plans | LONNYS | LONNYS | | BFR | P | 6030672 |
HOMEOWNER | BFN | C | 10/25/2018 | foundation design in master plan (bearing capacity verified) | LONNYS | LONNYS | | BFN | C | 6005349 |
HOMEOWNER | BFT | C | 10/25/2018 | open hole on file 2400PSF - usable - 5% / footing and foundation observations on file - ufer noted | LONNYS | LONNYS | | BFT | C | 6005341 |
HOMEOWNER | BFI | C | 10/01/2018 | need all paperwork to complete bft bfn | DALE | DALE | | BFI | C | 5982110 |
HOMEOWNER | E= | C | 02/04/2019 | no a/c | TOMC | TOMC | | E= | C | 6097232 |
HOMEOWNER | ER | C | 11/19/2018 | ER OK ---CORRECTIONS MADE--- | GREGM | GREGM | | ER | C | 6029335 |
HOMEOWNER | ER | R | 11/15/2018 | ground all metal boxes (o/s light & receptacles , kitchen lights ) 7- locations stationary part of sliding door is considered wall space -- measure 6' from center of slider to first receptacle bath pendant lights need light boxes not single gang nail-ons need fan rated boxes for ceiling fans --- 4sq with mud-ring not rated protect wire within 6' of attic access
| TOMC | TOMC | | ER | R | 6027406 |
HOMEOWNER | EUG | P | 11/12/2018 | 1.5" pvc no wire at this time | TOMC | TOMC | | EUG | P | 6023132 |
HOMEOWNER | ES | C | 11/06/2018 | Residential Underground: 200-amp 3 Wire service, ok to set meter / | TOMC | TOMC | | ES | C | 6017581 |
HOMEOWNER | H= | C | 01/30/2019 | NOTE: DIRECT VENT BOILER, IN-FLOOR HYDRONIC HEAT. | BILLS | BILLS | | H= | C | 6092155 |
HOMEOWNER | HSP | C | 12/05/2018 | CHANGED TO HSP INSPECTION. CONSULT WITH HOMEOWNER ON HYDRONIC PIPING AND HEAT FINAL REQUIREMENTS | BILLS | BILLS | | HSP | C | 6044087 |
HOMEOWNER | HC | C | 11/19/2018 | RELEASE METER | BILLS | BILLS | | HC | C | 6029740 |
HOMEOWNER | HRR | C | 11/19/2018 | NOTE: DIRECT VENT BOILER, IN-FLOOR HYDRONIC HEAT. | BILLS | BILLS | | HRR | C | 6029722 |
HOMEOWNER | HRR | R | 11/15/2018 | NOT READY. INSTALL DRYER VENT, BATH EXHAUST, AND KITCHEN HOOD EXHAUST. IS FIREPLACE GOING TO BE FREE STANDING OR BUILT IN ? | BILLS | BILLS | | HRR | R | 6026657 |
HODGES PLUMBING INC | HI | C | 11/06/2018 | 10 LB TEST OK , 1 1/4 INCH MAIN , 1 BOILER , 1 BBQ , 1 FIRE PLACE , 1 DRYER , 1 RANGE | ANDREWP | ANDREWP | | HI | C | 6017446 |
HOMEOWNER | HWP | P | 10/01/2018 | 60 lb test ok Notes-- ok to cover ground level slab. | JEFFL | JEFFL | | HWP | P | 5982055 |
HODGES PLUMBING INC | P= | C | 02/08/2019 | | TAYLOR | TAYLOR | | P= | C | 6101540 |
HOMEOWNER | P= | L | 02/05/2019 | need gate code. | TAYLOR | TAYLOR | | P= | L | 6097898 |
HOMEOWNER | P= | P | 02/05/2019 | certificate of potable water ok, see images. | TAYLOR | TAYLOR | | P= | P | 6097400 |
HOMEOWNER | PWO | C | 11/12/2018 | note: will need potable water certification by final | JOSEPHD | JOSEPHD | | PWO | C | 6023103 |
HODGES PLUMBING INC | PTO | C | 11/06/2018 | note: check connection from potable water to boiler, check for protection from cement to hot and cold pex below boiler, vtr (1) | JOSEPHD | JOSEPHD | | PTO | C | 6017401 |
HOMEOWNER | PWO | P | 11/05/2018 | need 46" ground cover at foundation, still need to see connection at well, at final will need backflow for yard hydrants, at final will need potable water certification | JOSEPHD | JOSEPHD | | PWO | P | 6015612 |
HODGES PLUMBING INC | PB | P | 09/25/2018 | need to uncover water line at foundation to check depth needs 46" of coverage, rest ok water lines under slab to fixtures | JOSEPHD | JOSEPHD | | PB | P | 5975682 |
HODGES PLUMBING INC | PB | P | 09/17/2018 | 3'' stub in under footer only, looks to be a crawlspace | TED | TED | | PB | P | 5967268 |
HOMEOWNER | PWO | P | 09/17/2018 | water line under footer stub in only, will need to see line run to well and depth of line | TED | TED | | PWO | P | 5967263 |
HOMEOWNER | PWO | R | 09/17/2018 | image no good | TED | TED | | PWO | R | 5966534 |
HOMEOWNER | XBS | P | 11/28/2018 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Revise truss hold down | MICHAELA | MICHAELA | | XBS | P | 6036044 |