JOHNSON CONSTRUCTORS LLC | B= | C | 12/02/2019 | eng letter for drywall installation of rated wall assembly on file | BOBF | BOBF | | B= | C | 6412295 |
JOHNSON CONSTRUCTORS LLC | B= | R | 11/22/2019 | eng letter received for acceptance of revised hardware connections / need letter approving and accepting GA WP 3510 wall due to no record of drywall install. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | BOBF | BOBF | | B= | R | 6408476 |
JOHNSON CONSTRUCTORS LLC | BE | L | 10/25/2019 | Renewed for No Fee at 10/25/2019 10:26:27 AM | TERRI | TERRI | | BE | L | 6380290 |
JOHNSON CONSTRUCTORS LLC | BFR | P | 02/12/2019 | Need to attach Mechanical to Permit / hardware installed not per plans in several locations - Contractor states engineering will capture these changes / framing OK pending Mechanical and Engineering / reviewed GA WP-3510 onsite | RICHB | RICHB | | BFR | P | 6104377 |
JOHNSON CONSTRUCTORS LLC | BSP | T | 02/07/2019 | PAID (REC#1574909) ADDITIONAL PLAN REVIEW TIME: $50 From: DALEH added mechanical scope | DALEH | DALEH | | BSP | T | 6100957 |
JOHNSON CONSTRUCTORS LLC | BFR | P | 01/31/2019 | Framing for fire resistance rated wall on East side OK per GA file WP 3510 - verify fasteners & spacing / discussed framing changes needing engineering at West wall / still need ll other framing inspected | RICHB | RICHB | | BFR | P | 6093356 |
JOHNSON CONSTRUCTORS LLC | BFI | C | 11/28/2018 | Horizontal slab insulation OK per COMcheck / discussed inspections that are required for fire-resistance rated walls | RICHB | RICHB | | BFI | C | 6037180 |
JOHNSON CONSTRUCTORS LLC | BFT | C | 10/26/2018 | (11) piers OK per plans | RICHB | RICHB | | BFT | C | 6006870 |
JOHNSON CONSTRUCTORS LLC | BBB | P | 10/04/2018 | Block & reinforcement for bond beam at top-of-wall OK per plans and UL U907 | RICHB | RICHB | | BBB | P | 5985529 |
JOHNSON CONSTRUCTORS LLC | BBB | P | 10/01/2018 | 8' above grade Bond beam inspection- Reinforcement per plans okay / Verified block installment to UL U907 / Training with Rich | SHAUN | SHAUN | | BBB | P | 5981216 |
JOHNSON CONSTRUCTORS LLC | BBB | P | 09/14/2018 | Block, verts & horizontal reinforcement for bond beam at 4'-0" above top of footing OK / verified material and construction with UL U907 | RICHB | RICHB | | BBB | P | 5966276 |
JOHNSON CONSTRUCTORS LLC | BFT | P | 09/11/2018 | Open Hole received - 1500 PSF, no drain required / footing formwork & reinforcement for CMU wall at South end OK (see Wall Detail on S-1) | RICHB | RICHB | | BFT | P | 5960872 |
NICKS ELECTRICAL SERVICES | E= | C | 05/13/2019 | corrections made | CHIPO | CHIPO | | E= | C | 6196508 |
NICKS ELECTRICAL SERVICES | E= | R | 05/09/2019 | 210.8 (B) (8) says ALL single phase, 150 volt or less, 50 amps or less, receptacles in a garage need GFCI protection. You will need a GFCI breaker for ceiling heater receptacles.------Wall receptacles okay. | CHIPO | CHIPO | | E= | R | 6193558 |
NICKS ELECTRICAL SERVICES | E= | R | 05/08/2019 | Receptacles in garage require GFCI protection-----all else okay. | CHIPO | CHIPO | | E= | R | 6192016 |
NICKS ELECTRICAL SERVICES | ES | C | 03/21/2019 | Commercial Service: 200-amp 3-wire new commercial service / okay to set meter | CHIPO | CHIPO | | ES | C | 6139364 |
NICKS ELECTRICAL SERVICES | ER | C | 03/21/2019 | All surface mount / all ceiling and back wall opposite garage doors okay, anything else installed will need to have boxes open at final to check wiring | CHIPO | CHIPO | | ER | C | 6139363 |
NICKS ELECTRICAL SERVICES | ES | R | 02/25/2019 | Commercial Service: approved prints show 200 amp 40 circuit panel and 100 amp 30 circuit panel to be installed in line after meter---actually installed is 200 amp disconnect and 200 amp panel------need correct equipment or splice on plans to complete inspection | CHIPO | CHIPO | | ES | R | 6116019 |
HANDS ON AIR & HOME SERVICES INC | H= | C | 11/22/2019 | SEE IMAGES FOR GAS CONNECTIONS | JERRYF | JERRYF | | H= | C | 6407827 |
HANDS ON AIR & HOME SERVICES INC | H= | P | 10/23/2019 | NEED PICTURES OF GAS CONNECTIONS INSTALLED PER INSTALL MANUAL CIRCLED ON SECTION 1.6 - ENGINEER LETTER FOR EQUIPMENT CHANGE AND PICTURES OF VENTS RECEIVED - PLAN REVISION IS COMPLETE | JERRYF | JERRYF | | H= | P | 6377641 |
HANDS ON AIR & HOME SERVICES INC | HC | C | 10/23/2019 | RELEASE METER | JERRYF | JERRYF | | HC | C | 6377640 |
HANDS ON AIR & HOME SERVICES INC | HI | C | 10/23/2019 | PRESSURE TEST OK AND PIPING PER REVISED PLAN | JERRYF | JERRYF | | HI | C | 6377639 |
HANDS ON AIR & HOME SERVICES INC | H= | P | 09/04/2019 | SEE ALL NOTES FROM HI AND HV INSPECTION | JERRYF | JERRYF | | H= | P | 6323311 |
HANDS ON AIR & HOME SERVICES INC | HI | R | 09/04/2019 | NEED 10# ON 30# GAUGE CURRENTLY SHOWING 20 POUNDS - INSTALL DOES NOT MATCH INSTALL - NOTICED 2 MEDIUM PRESSURE REGULATORS ON FLOOR IF THIS SYSTEM IS BEING CHANGED TO MEDIUM PRESSURE WILL NEED LABELS - REGULATORS / PLAN REVISION AND 2# APPROVAL LETTER FROM CSU - PLAN SHOWS 11/2" GAS HEADER AT METER LOCATION - AT THIS TIME 1" FROM METER IS ONLY GOOD FOR 220000 TOTAL BTU'S????? - RE INSPECT ALL | JERRYF | JERRYF | | HI | R | 6323295 |
HANDS ON AIR & HOME SERVICES INC | HV | P | 09/04/2019 | NEED PICTURES OF VENT CAPS AND INSULATION SHIELDS IN ATTIC AT 2 FLUES - NEED INSTALL MANUAL FOR TUBE HEATERS TO VERIFY INSTALL - TUBE HEATERS INSTALLED DO NOT MATCH EQUIPMENT SCHEDULE WILL NEED STAMPED LETTER FROM ENGINEER APPROVING EQUIPMENT CHANGE - STOPPED INSPECTION - RE INSPECT ALL | JERRYF | JERRYF | | HV | P | 6323280 |
HANDS ON AIR & HOME SERVICES INC | XMS | T | 10/11/2019 | PAID (REC#1636737) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: revised gas piping | DALEH | DALEH | | XMS | T | 6365818 |
NICKS ELECTRICAL SERVICES | XES | T | 03/20/2019 | PAID (REC#1583768) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revise panel schedule | SHELBY | SHELBY | | XES | T | 6138823 |
JOHNSON CONSTRUCTORS LLC | XES | T | 02/12/2019 | PAID (REC#1575929) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added electrical scope. | BERTHA | BERTHA | | XES | T | 6105359 |