HOMEOWNER | B= | C | 10/21/2019 | | JUSTINL | JUSTINL | | B= | C | 6374993 |
HOMEOWNER | BIN | C | 10/21/2019 | | JUSTINL | JUSTINL | | BIN | C | 6374981 |
HOMEOWNER | BFR | C | 10/21/2019 | Engineer letter of file addressing item noted in BFR 3-12-19 - Frame complete | JUSTINL | JUSTINL | | BFR | C | 6374975 |
HOMEOWNER | B= | P | 10/18/2019 | Need to complete exterior surfaces and secure deck railings - Rest of building corrections OK. -- Schedule a new Building Final when above items are complete. | CHUCK | CHUCK | | B= | P | 6373182 |
HOMEOWNER | B= | R | 10/15/2019 | Install gutters and extensions away from foundation / Finish weather resistant exterior surfaces, deck fireplace and cover lid / Post address on house, 5" high with 1/2" wide stroke min. / Combo. smoke/CO detector to be installed within immediate vicinity of bedrooms, main floor - smoke only installed / Smoke detector to be installed in Master Bedroom / Install and seal attic access drywall in garage ceiling and install min. 1/2" drywall at faucets in garage-dwelling separation wall / Handrail to be continuous to top of stair landing and shall return to adjacent walls at all ends / Finish installing surfaces/mantel/hearth around wood burning fireplace in Family Room - provide manufacturer's installation instructions listing clearances to combustible surfaces / Need to insulate perimeter rim joist // Rest of building final OK - No A/C, rear deck, unfinished basement. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | CHUCK | CHUCK | | B= | R | 6368469 |
HOMEOWNER | BLA | C | 04/29/2019 | | DALE | DALE | | BLA | C | 6181812 |
HOMEOWNER | BLA | P | 04/26/2019 | entry weep screed raised at entry door - Still need to address weep screed at all other remaining areas / Seal penetration at electrical panel box at north elevation | JUSTINL | JUSTINL | | BLA | P | 6179402 |
HOMEOWNER | BLA | P | 04/24/2019 | 1. Weep screed pressed tight to foundation at multiple locations around house - Need to provide minimum 1/2" gap between weep screed and poured surface / 2. No flat work poured at entry and walk out - Weep screed appears to be below where flat work will be poured - Ensure that there will be 1/2" gap between weep screed and poured surface // Rest of Lath OK at all sides of home | JUSTINL | JUSTINL | | BLA | P | 6177219 |
HOMEOWNER | BIN | P | 03/25/2019 | ES report not required - insulation OK | LONNYS | LONNYS | | BIN | P | 6142560 |
HOMEOWNER | BIN | P | 03/21/2019 | need ES report for blown in wool insulation / observed 6" insulation at exterior walls / need to inspect unfinished basement insulation at final | LONNYS | LONNYS | | BIN | P | 6139433 |
HOMEOWNER | BFR | P | 03/12/2019 | both north east windows missing 4th middle trimmer and ST18 / OK to insulate | LONNYS | LONNYS | | BFR | P | 6131119 |
HOMEOWNER | BFR | R | 03/08/2019 | missing anchor bolt right side of garage at break / missing through bolts at both 4-ply girders / still need to inspect all lateral braceing / cut access to over framing over fire place / missing 2nd H2.5 all T03 trusses MBR / both north east windows missing 4th middle trimmer and ST18 / missing all HTS20s over front entrance / glue shims in beam pockets / untreated wood used at sill plate EE of long beam in basement / discusses all items with home owner on site | LONNYS | LONNYS | | BFR | R | 6128166 |
HOMEOWNER | BSP | P | 01/25/2019 | deck framing OK / deck cover lid and posts OK / garage narrow braced wall OK / discussed framing questions with homeowner - lath to be requested at later date as BLA once complete | LONNYS | LONNYS | | BSP | P | 6088465 |
HOMEOWNER | BSP | R | 12/07/2018 | porch lid missing all MTS12s / porch posts missing post caps / garage narrow braced OK per engineer framing changes | LONNYS | LONNYS | | BSP | R | 6046074 |
HOMEOWNER | BSP | P | 12/07/2018 | engineer letter for narrow braced wall on file | LONNYS | LONNYS | | BSP | P | 6045622 |
HOMEOWNER | BSP | R | 11/30/2018 | REAR DECK FRAMING ONLY: need pier observation for deck piers - not inspected by PPRBD / deck post caps to be LPCZ6s installed in pairs / deck ledger to have 4 ledger locks 16" OC / deck rim joists missing LUS26Zs EE / all other deck framing OK | LONNYS | LONNYS | | BSP | R | 6039095 |
HOMEOWNER | BFN | C | 10/22/2018 | Foundation design on file | JEREMYA | JEREMYA | | BFN | C | 6001503 |
HOMEOWNER | BFT | C | 10/22/2018 | Homeowner has been made aware that permit must be pulled prior to starting work. | JEREMYA | JEREMYA | | BFT | C | 6001488 |
HOMEOWNER | BFI | C | 10/09/2018 | | DALE | DALE | | BFI | C | 5990145 |
HOMEOWNER | BFD | C | 10/09/2018 | Engineers observation Letter received / dampproofing ok / soils received | DALE | DALE | | BFD | C | 5990138 |
HOMEOWNER | BFN | P | 10/09/2018 | Engineers observation Letter received / need stamped foundation design | DALE | DALE | | BFN | P | 5990131 |
HOMEOWNER | BFT | R | 10/09/2018 | permit was pulled on 9/28, eng. inspection on 9/25, need to call Jeremy Anderson / eng. observation received | DALE | DALE | | BFT | R | 5990127 |
HOMEOWNER | E= | C | 10/11/2019 | | TOMC | TOMC | | E= | C | 6366258 |
HOMEOWNER | E= | R | 10/09/2019 | need afci & gfci on washer , need gfci in unfinished basement , garage , kitchen | TOMC | TOMC | | E= | R | 6363628 |
HOMEOWNER | ES | C | 03/07/2019 | Residential Underground: 200-amp 3 Wire New Residence ok to set meter. / | TOMC | TOMC | | ES | C | 6127007 |
HOMEOWNER | ER | C | 03/01/2019 | Discussed AFCI/GFCI/TR requirements with owner. / no central vac , unfinished basement , | TOMC | TOMC | | ER | C | 6121863 |
HOMEOWNER | EUG | C | 02/26/2019 | EUG OK TO COVER ----4/0----- | GREGM | GREGM | | EUG | C | 6117227 |
HOMEOWNER | ES | R | 02/25/2019 | Residential Underground: service lateral not ran at this time , sub-panel feeders not terminated , need access to ufer connection | TOMC | TOMC | | ES | R | 6116900 |
HOMEOWNER | ER | R | 02/25/2019 | (1) need 20 amp circuit for bathroom receptacles (2) need 2 - 20 amp kitchen counter circuits (3) dining room / nook need to be on 20 amp circuit in 12 gauge wire (4) add receptacle in master bedroom and second bedroom (5) add smoke detector in basement (6) add w/p receptacle on front and back of house accessible from grade (7) add light by basement walk-out and panel (8) float neutral in basement panel ------ complete re-inspection | TOMC | TOMC | | ER | R | 6116885 |
HOMEOWNER | ESL | C | 10/10/2018 | 2 inch PVC schedule 80 in basement slab for well wire. | JOSEPH | JOSEPH | | ESL | C | 5990651 |
HOMEOWNER | H= | C | 10/14/2019 | Per homeowner, kitchen exhaust to be done in future with a new permit. | MARK | MARK | | H= | C | 6366707 |
HOMEOWNER | H= | P | 10/09/2019 | Kitchen exhaust may be installed prior to final or a new permit will be required when installing. Note: Unfinished basement with 6" outside air to return. Direct vent furnace and tankless water heater. | MARK | MARK | | H= | P | 6363431 |
HOMEOWNER | HC | C | 03/07/2019 | RELEASE METER | BILLS | BILLS | | HC | C | 6126781 |
HOMEOWNER | HI | C | 03/07/2019 | 10LB TEST OK. 1 1/4" MAIN, 1 FURNACE, 1 TANKLESS WATER HEATER, 1 OVEN, 1 COOKTOP, 1 DRYER, 1 3/4" EXTERIOR STUB AT BACK DECK | BILLS | BILLS | | HI | C | 6126773 |
HOMEOWNER | HRR | C | 03/05/2019 | SOLID FUEL BURNING FIREPLACE TO BE INSPECTED BY BUILDING INSPECTOR. | KYLEW | KYLEW | | HRR | C | 6124230 |
HOMEOWNER | HRR | P | 03/04/2019 | PRIME AND GLUE CONCENTRIC VENTS TO WYES. ADD BATH FAN IN MAIN PART OF MASTER BATHROOM ( WINDOW DOES NOT MEET 4%). SEAL TOP OF ALL MAIN LEVEL RETURNS. INSTALL 3 SCREWS IN ALL HEAT RUN CONNECTIONS. INSTALL OUTSIDE AIR TO RETURN WITH DAMPER PER DUCT DESIGN. SEAL RETURN PANNING BETWEEN TRUNK LINES IN BASEMENT CEILING. NOTES: UNFINISHED BASEMENT, OUTSIDE AIR TO RETURN, DIRECT VENT FURNACE, DIRECT VENT TANKLESS WATER HEATER, NO A/C. | KYLEW | KYLEW | | HRR | P | 6123476 |
HOMEOWNER | P= | C | 10/14/2019 | Corrections made | MALYNDA | MALYNDA | | P= | C | 6367506 |
HOMEOWNER | P= | P | 10/11/2019 | Still need aav at left master lav and basement lav, need correct pipe and size at T&P, rest ok Potable water test received. Note: no irrigation | MALYNDA | MALYNDA | | P= | P | 6366031 |
HOMEOWNER | P= | P | 10/09/2019 | Master tub spout needs an air gap, caulk and secure laundry sink, missing aav at left master lav, need hammer arrestor for dishwasher, cap all future piping in basement, Pex T&P at water heater must be a minimum of 1", need aav at basement lav, rest ok. Note: Still need potable water certificate | MALYNDA | MALYNDA | | P= | P | 6363057 |
HOMEOWNER | PTO | C | 03/04/2019 | | TAYLOR | TAYLOR | | PTO | C | 6123333 |
HOMEOWNER | PTO | L | 02/26/2019 | field cancelled. | TAYLOR | TAYLOR | | PTO | L | 6117617 |
HOMEOWNER | PTO | P | 02/25/2019 | lost test all DWV, install 3 piece shower drain at master, support vents throughout, replace field made trap at washer, grade issues at DWV throughout, need listing for master shower valve, rest ok, unfinished basement, aav's at left master lav, kitchen, basement, note: mixing valve above water heater. | TAYLOR | TAYLOR | | PTO | P | 6116225 |
HOMEOWNER | PTO | P | 02/15/2019 | not ready. | TAYLOR | TAYLOR | | PTO | P | 6108832 |
HOMEOWNER | PWO | C | 02/05/2019 | need certificate of potable water by final. | TAYLOR | TAYLOR | | PWO | C | 6097933 |
HOMEOWNER | PB | C | 10/12/2018 | corrections made | JOSEPHD | JOSEPHD | | PB | C | 5993205 |
HOMEOWNER | PB | P | 10/11/2018 | need vent between toilet and tub on right hand side, need to install lav drain at left hand bathroom | JOSEPHD | JOSEPHD | | PB | P | 5992126 |
HOMEOWNER | PB | P | 10/10/2018 | can not use san tee's on horizontal, trap arm to tub to long, need p-trap installed at tub and floor drain | JOSEPHD | JOSEPHD | | PB | P | 5990932 |