MARK YOUNG CONSTRUCTION, INC. | B= | C | 08/20/2019 | All other required Final inspections are complete. (This is a computer generated result) | SCOTTS | SCOTTS | | B= | C | 6307612 |
MARK YOUNG CONSTRUCTION, INC. | B= | P | 07/25/2019 | . Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | SCOTTS | SCOTTS | | B= | P | 6277470 |
MARK YOUNG CONSTRUCTION, INC. | BFR | P | 05/01/2019 | incorrect inspection requested / no inspection performed | BRIANB | BRIANB | | BFR | P | 6184445 |
MARK YOUNG CONSTRUCTION, INC. | BFR | P | 02/13/2019 | PARTIAL ONLY / observed light gauge non-load bearing wall framing in mother's room and knee wall framing in break room / observed hard lid framing in mothers room / pending other rough inspections / went over accessible elements with the site superintendent / Training with PPRBD inspector Justin / went over plan sticker including type of construction - occupancies and other required inspections for permit / went over light gauge framing details on plan and inspection processes / discussed and reviewed accessible elements for permitted scope of work | BRIANB | BRIANB | | BFR | P | 6106562 |
MARK YOUNG CONSTRUCTION, INC. | BSP | P | 02/13/2019 | Training with Brian B - Reviewed code study for occupancy and type of construction - Training on light gage steel framing in 5B construction - Reviewed multiple use occupancy - Navigating commercial plans - Code interpretation and application - Reviewed accessible elements of a break room | JUSTINL | JUSTINL | | BSP | P | 6106556 |
MARK YOUNG CONSTRUCTION, INC. | BSP | L | 02/11/2019 | training with inspector Brian B. / could not locate contractor - call ahead verified - left voice mail with contractor walked entire site | LONNYS | LONNYS | | BSP | L | 6104002 |
MARK YOUNG CONSTRUCTION, INC. | BFR | L | 02/11/2019 | walked entire store and unable to contact superintendent onsite for inspection / no answer at call ahead number provided - left v.m / no inspection performed | BRIANB | BRIANB | | BFR | L | 6103998 |
DIVERSIFIED ELECTRIC & CONTROLS, L.L.C. | E= | C | 05/14/2019 | E= OK -----REFRIGERATION CASES ------ | GREGM | GREGM | | E= | C | 6197982 |
DIVERSIFIED ELECTRIC & CONTROLS, L.L.C. | E= | R | 05/10/2019 | NOT READY------- | GREGM | GREGM | | E= | R | 6194862 |
BIBLE ELECTRIC, INC. | E= | C | 04/23/2019 | LIGHTING @ BAKERY------OUTLETS @ MANAGER STATION -------- | GREGM | GREGM | | E= | C | 6174799 |
BIBLE ELECTRIC, INC. | E= | P | 04/18/2019 | 6 POWER DROPS @ ENTRY----3 POWER DROPS @ SEASONAL AREA------POWER DROP @ JEWELRY----2 POWER DROPS @ CHANGING AREA ---3 POWER DROPS @ CLOTHING ----- | GREGM | GREGM | | E= | P | 6170191 |
BIBLE ELECTRIC, INC. | E= | P | 04/17/2019 | POWER @ LIGHTING IN PHARMACY OK-------4 POWER DROPS IN COSMETICS OK-----3 POWER DROPS IN LAWN @ GARDEN OK-----POWER DROP IN AUTOMOTIVE OK -----POWER DROP IN SPORTING OK----- | GREGM | GREGM | | E= | P | 6168375 |
BIBLE ELECTRIC, INC. | E= | P | 04/15/2019 | electronics and grocery | TOMC | TOMC | | E= | P | 6165470 |
BIBLE ELECTRIC, INC. | ER | P | 04/15/2019 | power poles and double duplexs in electronics , lighting in grocery | TOMC | TOMC | | ER | P | 6165466 |
BIBLE ELECTRIC, INC. | E= | P | 03/01/2019 | PARTIAL FINAL BREAK RM OK-----MOTHERS RM OK ----MENS RM OK---LADIES RM OK----VENDING AREA OK------ | GREGM | GREGM | | E= | P | 6121094 |
BIBLE ELECTRIC, INC. | ER | P | 02/19/2019 | CEILING AND WALLS IN BREAK RM OK----- | GREGM | GREGM | | ER | P | 6110623 |
BIBLE ELECTRIC, INC. | ER | P | 02/13/2019 | WALLS WEST END OF BREAK ROOM OK------ | GREGM | GREGM | | ER | P | 6105878 |
BIBLE ELECTRIC, INC. | ER | P | 02/12/2019 | OK WALLS AND CEILING IN MOTHERS ROOM----- Electrical Rough ok, FA not complete ---------------do not sheetrock--------------- / FA NEEDS TO CALL INSP. | GREGM | GREGM | | ER | P | 6104653 |
REEVES SPECIALTY SERVICES, INC. | H= | C | 07/22/2019 | RECEIVED REVISED TEST AND BALANCE REPORT ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6271141 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 06/05/2019 | PARTIAL PENDING - TEST AND BALANCE REPORT REVIEW : PHARMACY - RETURN AIR IS OUTSIDE THE 10% PLUS OR MINUS ALLOWED. NEED REVISED TEST AND BALANCE REPORT OR A STAMPED ENGINEER LETTER APPROVING THE READINGS. | LIDO | LIDO | | H= | P | 6220243 |
HUSSMANN SERVICES CORPORATION | H= | C | 05/30/2019 | REFRIGERATION FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6214187 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 05/29/2019 | RTU-1 IS SHOWN ON THE TEST AND BALANCE REPORT BUT THERE IS NO RTU-1 SHOWN ON PLANS . TEST AND BALANCE REPORT REVIEW : MISSING SUPPLY AIR READINGS FOR THE FOLLOWING ROOMS -HEALTH SERVICES,TOILET AND MOTHERS ROOM. NEED REVISED TEST AND BALANCE REPORT OR ENGINEER STAMPED LETTER APPROVING THE READINGS.
| LIDO | LIDO | | H= | P | 6212637 |
HUSSMANN SERVICES CORPORATION | H= | P | 05/14/2019 | PARTIAL PENDING: CORRECT SCOPE OF WORK TO SHOW 53 REACH IN COOLER / FREEZERS
| LIDO | LIDO | | H= | P | 6198966 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 05/10/2019 | RTU-1 IS SHOWN ON THE TEST AND BALANCE REPORT BUT THERE IS NO RTU-1 SHOWN ON PLANS . TEST AND BALANCE REPORT REVIEW : MISSING SUPPLY AIR READINGS FOR THE FOLLOWING ROOMS -HEALTH SERVICES,TOILET AND MOTHERS ROOM. CONTRACTOR TO CALL ME MONDAY MORNING BETWEEN 7:30 AND 8:30 (LIDO) 719- 327-2928
| LIDO | LIDO | | H= | P | 6194650 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 04/25/2019 | PARTIAL PENDING : NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6178243 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 04/22/2019 | ((STILL NEED ROOF AND MEAT UTILITY INSPECTED .))PHARMACY : IN HEALTH SERVICES MISSING RETURN AIR /AN EXHAUST WAS INSTALLED AND TIED-INTO THE EXISTING EXHAUST FOR THE TOILET ROOM THIS IS NOT PER PLAN. MISSING SUPPLY IN TOILET ROOM. MISSING 24"DAMPER FOR RETURN IN PHARMACY AND MISSING RELOCATED THERMOSTAT. MOTHERS ROOM: NEED DAMPERS VERIFIED FOR EXHAUST AND SUPPLY. NEED TEST AND BALANCE REPORT BY FINAL. | LIDO | LIDO | | HD | P | 6174155 |
REEVES SPECIALTY SERVICES, INC. | HD | R | 04/18/2019 | CHANGED TO( HD) NO MECHANICAL ROUGH INSPECTIONS HAVE BEEN COMPLETED / ALL MECHANICAL WORK IS COVERED UP BY CEILING . CONTRACTOR TO CALL ME IN THE MORNING TO DISCUSS THIS. ON NEXT INSPECTION CONTRACTOR WILL NEED TO PROVIDE A CONTRACT NUMBER AND MEET INSPECTOR FOR INSPECTION | LIDO | LIDO | | HD | R | 6170636 |
INTERSTATE MECHANICAL, INC. | P= | C | 05/02/2019 | | SAMH | SAMH | | P= | C | 6185604 |
INTERSTATE MECHANICAL, INC. | PTO | C | 04/30/2019 | | SAMH | SAMH | | PTO | C | 6182673 |
INTERSTATE MECHANICAL, INC. | P= | P | 04/30/2019 | Need to add Thermal expansion tank after check valve at break room water heater. Rest OK. | SAMH | SAMH | | P= | P | 6182670 |
INTERSTATE MECHANICAL, INC. | P= | P | 04/29/2019 | Need to check break room sink and water heater. Need air gap at eye wash drain. Clarify scope of work on permit. | SAMH | SAMH | | P= | P | 6181666 |
INTERSTATE MECHANICAL, INC. | P= | P | 04/26/2019 | Call ahead sent at 9:05am. Called contractor 2 additional times (no answer). Need contractor on site for water heater locations. | SAMH | SAMH | | P= | P | 6179096 |
INTERSTATE MECHANICAL, INC. | PB | C | 04/01/2019 | Underground DWV to beer coolers OK. | SAMH | SAMH | | PB | C | 6150669 |
INTERSTATE MECHANICAL, INC. | PTO | P | 02/13/2019 | rear rest room area, mother's room sink ok | TED | TED | | PTO | P | 6105783 |