RAINE BUILDING LLC. | B= | C | 04/25/2019 | All other required Final inspections are complete. (This is a computer generated result) | RICHB | RICHB | | B= | C | 6177520 |
RAINE BUILDING LLC. | B= | P | 04/22/2019 | Need to complete Mechanical. Additional Inspections Required (computer generated): JOHNSON BROTHERS PLUMBING & HEATING Mechanical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | P | 6174111 |
RAINE BUILDING LLC. | B= | P | 04/05/2019 | final OK pending other finals. Additional Inspections Required (computer generated): JOHNSON BROTHERS PLUMBING & HEATING Mechanical Final Inspection is not Completed yet, PROCOM ELECTRICAL SERVICES, INC. Electrical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 6156282 |
RAINE BUILDING LLC. | BFR | P | 02/14/2019 | Framing OK pending other Roughs / discussed accessible elements | RICHB | RICHB | | BFR | P | 6107415 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 04/22/2019 | | CRAIGS | CRAIGS | | E= | C | 6173590 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 03/25/2019 | Above ceilings okay | CHIPO | CHIPO | | ER | P | 6143608 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 03/07/2019 | FIRE ALARM INSPECTION: FA complete / | ROB | ROB | | E= | C | 6127506 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 03/07/2019 | FIRE ALARM INSPECTION: FA rough ok / | ROB | ROB | | ER | C | 6127424 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 03/07/2019 | FIRE ALARM INSPECTION: FA rough ok / | ROB | ROB | | E= | C | 6127425 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 02/08/2019 | all walls | GARYL | GARYL | | ER | P | 6101789 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | C | 04/25/2019 | RECEIVED STAMPED ENGINEER LETTER APPROVING THE OUTSIDE AIR READINGS FROM THE TEST AND BALANCE REPORT. ( SEE IMAGES) | LIDO | LIDO | | H= | C | 6177519 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 04/23/2019 | TEST AND BALANCE REPORT REVIEW: REFER TO NOTES DATED 4-22-19 FOR THE OUTSIDE AIR. ( BALANCE COMPANY CAN CONTACT ME AT # 719-327-2928 ) BETWEEN 7:30 AND 8:30.) | LIDO | LIDO | | H= | P | 6174989 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 04/22/2019 | ADJUSTED NOTES 4/22/19 (LM) TEST AND BALANCE REPORT REVIEW: THE PLANS ARE MISSING THE EXISTING ROOF TOP SCHEDULE THIS IS NEEDED FOR THE REQUIRED OUTSIDE AIR , ENGINEER WILL NEED TO PROVIDE AND HAVE PLANS REVISED AND APPROVE TO SPLICE INTO PLANS OR A STAMPED ENGINEER LETTER APPROVING THE OUTSIDE AIR READING . REPORT IS MISSING READINGS FOR VAV-2-86 . REPORT SHOWS A FPB-2-1 THAT IS NOT SHOWN ON THE PLANS. | LIDO | LIDO | | H= | P | 6173147 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 04/18/2019 | BEING THAT THE DESIGNED CFM'S ARE LESS THAN 2000 A DUCT DETECTOR WILL NOT BE REQUIRED . PARTIAL PENDING : TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6169912 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 04/08/2019 | PARTIAL PENDING :MISSING DUCT DETECTOR FOR FBP-1 AND REMOTE SMOKE INDICATOR (LED)/ NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6159428 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 03/21/2019 | NEED TO RESEARCH TRANSFERS IN WALLS TO SEE IF WALLS ARE RATED -ECT . WILL ADD TO NOTES IN THE MORNING .NEED TO LABEL CONDENSER ON ROOF FOR AREA SERVED AND BLOWER UNIT IN TELCOM ROOM . NEED TO COMPLETE CONDENSATE DISPOSAL FOR MINI SPLIT AND FBP-1 ,NEED TO .SEE SECONDARY PROTECTION FOR FBP-1 . CONTRACTOR NEEDS TO PROVIDE VERIFICATION THAT FBP-1 SHUTS DOWN PER NOTE 1 FROM THE EQUIPMENT SCHEDULE PLAN PAGE M0.1 .RETURN AIR IN OFFICE #212 IS BLOCKING THE TRANSFER AIR.NEED TEST AND BALANCE REPORT | LIDO | LIDO | | H= | P | 6140354 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | HD | P | 03/21/2019 | NEED TO RESEARCH TRANSFERS IN WALLS TO SEE IF WALLS ARE RATED -ECT . WILL ADD TO NOTES IN THE MORNING .NEED TO LABEL CONDENSER ON ROOF FOR AREA SERVED AND BLOWER UNIT IN TELCOM ROOM . NEED TO COMPLETE CONDENSATE DISPOSAL FOR MINI SPLIT AND FBP-1 ,NEED TO .SEE SECONDARY PROTECTION FOR FBP-1 . CONTRACTOR NEEDS TO PROVIDE VERIFICATION THAT FBP-1 SHUTS DOWN PER NOTE 1 FROM THE EQUIPMENT SCHEDULE PLAN PAGE M0.1 .RETURN AIR IN OFFICE #212 IS BLOCKING THE TRANSFER AIR.NEED TEST AND BALANCE REPORT | LIDO | LIDO | | HD | P | 6140313 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | HSP | P | 02/14/2019 | LINE SET IN WALL FOR AC-1 OK. | LIDO | LIDO | | HSP | P | 6106767 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | P= | C | 04/05/2019 |
| JOHNS | JOHNS | | P= | C | 6156224 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | PTO | C | 02/13/2019 | ok for test / design and ok for 3/4 COPPER CONDENSATE IN WALL. NOTE: aav @ sink, check insta hot water htr @ final (under break sink) | JOHNS | JOHNS | | PTO | C | 6106478 |