JM WESTON HOMES LLC | B= | C | 07/09/2019 | | NICK | NICK | | B= | C | 6256543 |
JM WESTON HOMES LLC | BIN | C | 07/09/2019 | 3rd Party Insulation Certificate on file / Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 on file / | NICK | NICK | | BIN | C | 6256538 |
JM WESTON HOMES LLC | B= | P | 07/08/2019 | Provide Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 / All other aspects of final OK -- Schedule a new Building Final when above items are complete. | NICK | NICK | | B= | P | 6255991 |
JM WESTON HOMES LLC | BIN | R | 07/08/2019 | Reviewed Air Leakage Testing Requirements Per 2015 IECC Section R402.4.1.2 to be Provided by Final Inspection / Need Air leakage testing for file / Need insulation certificate for file / Duct leakage report given in image | NICK | NICK | | BIN | R | 6255243 |
JM WESTON HOMES LLC | BFR | C | 05/30/2019 | items corrected | NATHAN | NATHAN | | BFR | C | 6214856 |
JM WESTON HOMES LLC | BFR | P | 05/28/2019 | missing anchor bolt at rear right of garage, block or drop brackets for drywall at overhead door, dry in roof, finish mineral wool draft stop 10' horizontal and vertically at floor ceiling line wall built per ASW 1000, | NATHAN | NATHAN | | BFR | P | 6211746 |
JM WESTON HOMES LLC | BSP | P | 05/20/2019 | Double layer 5/8 at soffits OK | NICK | NICK | | BSP | P | 6204968 |
JM WESTON HOMES LLC | BSP | P | 04/30/2019 | Stair landing framing OK | NICK | NICK | | BSP | P | 6182817 |
JM WESTON HOMES LLC | BSP | P | 04/29/2019 | All hold downs and sheer OK / Porch lid and post OK | NICK | NICK | | BSP | P | 6181606 |
JM WESTON HOMES LLC | BFN | C | 04/29/2019 | Foundation design on file / Open hole on file / #1000psf / No drain required / Eng letter of observation on file | NICK | NICK | | BFN | C | 6180913 |
JM WESTON HOMES LLC | BFI | P | 02/06/2019 | AUTHORIZED INSPECTION BY ENGINEER | RITA | RITA | RITA | BFI | P | 6099952 |
JM WESTON HOMES LLC | BFD | P | 02/06/2019 | AUTHORIZED INSPECTION BY ENGINEER | RITA | RITA | RITA | BFD | P | 6099951 |
JM WESTON HOMES LLC | BFT | P | 02/06/2019 | AUTHORIZED INSPECTION BY ENGINEER | RITA | RITA | RITA | BFT | P | 6099950 |
JM WESTON HOMES LLC | BFN | P | 02/06/2019 | AUTHORIZED INSPECTION BY ENGINEER | RITA | RITA | RITA | BFN | P | 6099949 |
PEAK ELECTRIC INC. | E= | C | 07/02/2019 | a/c pre wire only, | JOHNN | JOHNN | | E= | C | 6251042 |
PEAK ELECTRIC INC. | ES | C | 05/24/2019 | Residential Underground: 200-amp 3 Wire New Residence ok to set meter. / | JOHNN | JOHNN | | ES | C | 6209679 |
PEAK ELECTRIC INC. | ER | C | 05/24/2019 | --------------------------notes: no mcc,rev ufer, #8al, | JOHNN | JOHNN | | ER | C | 6209667 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | C | 07/03/2019 | | MATTM | MATTM | | H= | C | 6252584 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | P | 07/02/2019 | FURNACE CONDENSATE VENT CANNOT TERMINATE LESS THAN 1" ABOVE DRAIN CONNECTION TO FURNACE PER MANUFACTURES INSTALLATION INSTRUCTIONS PAGE 31, WHOLE HOUSE VENTILATION CONTROL SWITCH IS LOCATED IN THE LAUNDRY ROOM. NOTES: NO OUTSIDE AIR TO FURNACE RETURN, DIRECT VENT FURNACE, DIRECT VENT TANKLESS WATER HEATER, A/C ROUGH COIL AND LINESET, NO FIREPLACE | MATTM | MATTM | | H= | P | 6252017 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | P | 07/02/2019 | RECEIVED DUCT LEAKAGE REPORT FROM CONTRACTOR, SEE IMAGES. | MATTM | MATTM | | H= | P | 6250888 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HC | C | 05/23/2019 | RELEASE METER | MATTM | MATTM | | HC | C | 6208784 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | C | 05/23/2019 | BY FINAL: PROVIDE LOCATION OF WHOLE HOUSE VENTILATION CONTROL SWITCH, DUCT LEAKAGE REPORT. WHOLE HOUSE VENTILATION IS BEING ACHIEVED VIA CONSTANT FAN IN LAUNDRY ROOM NOTES: NO OUTSIDE AIR TO FURNACE RETURN, DIRECT VENT FURNACE, DIRECT VENT TANKLESS WATER HEATER, A/C ROUGH COIL AND LINESET, NO FIREPLACE | MATTM | MATTM | | HRR | C | 6208778 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | P | 05/23/2019 | RECEIVED COIL CHANGE OF EQUIPMENT LETTER FROM CONTRACTOR, SEE IMAGES. | MATTM | MATTM | | HRR | P | 6207891 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | P | 05/22/2019 | ****NOTE ADDED 5/22/19 BY MLM: PER CONVERSATION IN THE FIELD WITH BILL, CONTRACTOR MUST INSULATE FURNACE VENT PER MANUFACTURES INSTALLATION INSTRUCTIONS PAGE 23 TABLE 9****BY FINAL: PROVIDE LOCATION OF WHOLE HOUSE VENTILATION CONTROL SWITCH, COIL INSTALLED DOES NOT MATCH EQUIPMENT LISTED ON APPROVED DUCT DESIGN. CONTRACTOR MUST FILL OUT THE EQUIPMENT CHANGE FORM (RESIDENTIAL) AND ATTACH FORM TO NEXT INSPECTION REQUEST. FORM CAN BE FOUND ON THE PPRBD WEBSITE UNDER DOWNLOADS, RESIDENTIAL HANDOUTS, EQUIPMENT CHANGE RESIDENTIAL DUCT DESIGN. PROVIDE FURNACE INSTALLATION INSTRUCTIONS, LIQUID LINE TOUCHING DISSIMILAR METAL IN GARAGE, REPAIR LINESET INSULATION IN MULTIPLE PLACES, LINESET REQUIRES ADDITIONAL NAIL PROTECTION IN GARAGE, SUPPORT DRYER DUCT EVERY 4FT. WHOLE HOUSE VENTILATION IS ACHIEVE VIA CONSTANT EXHAUST FAN IN LAUNDRY ROOM. NOTES: NO OUTSIDE AIR TO FURNACE RETURN, DIRECT VENT FURNACE, DIRECT VENT TANKLESS WATER HEATER, A/C ROUGH COIL AND LINESET, NO FIREPLACE | MATTM | MATTM | | HRR | P | 6207669 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | R | 05/21/2019 | STOPPED INSPECTION, MISSING DRYER NAIL PROTECTION, SUPPORT DRYER DUCT EVERY 4FT MAXIMUM, WATER HEATER INTAKE/EXHAUST INCOMPLETE, WHOLE HOUSE VENTILATION EXHAUST DUCT MISSING, CANNOT USE 3" FLEX FOR EXHAUST DUCT ON MAIN LEVEL, REINSPECT ALL | MATTM | MATTM | | HRR | R | 6206439 |
L & L GAS SHOP, LLC. | HI | C | 05/16/2019 | 10LB TEST OK 1 1/4" MAIN 1 FURNACE 1 TANKLESS WATER HEATER 1 RANGE | MATTM | MATTM | | HI | C | 6202001 |
TRADITIONAL PLUMBING AND HEATING LLC | P= | C | 07/01/2019 | correction made | JOSEPHD | JOSEPHD | | P= | C | 6250185 |
TRADITIONAL PLUMBING AND HEATING LLC | P= | P | 06/28/2019 | aav @ upstairs hall bath needs to be vertical, need to support t&p, rest ok note: no irrigation | JOSEPHD | JOSEPHD | | P= | P | 6248011 |
TRADITIONAL PLUMBING AND HEATING LLC | P= | R | 06/27/2019 | Too many issues, not ready for inspection. | MALYNDA | MALYNDA | | P= | R | 6245953 |
TRADITIONAL PLUMBING AND HEATING LLC | PTO | C | 05/20/2019 | note: no irrigation, aav @ upstairs hall lav, 1 master lav, cwv @ 1 master lav | JOSEPHD | JOSEPHD | | PTO | C | 6204502 |
TRADITIONAL PLUMBING AND HEATING LLC | PB | C | 03/21/2019 | Correction made | MALYNDA | MALYNDA | | PB | C | 6139638 |
TRADITIONAL PLUMBING AND HEATING LLC | PB | P | 03/20/2019 | need to test fusion joint on water main, rest ok | JOSEPHD | JOSEPHD | | PB | P | 6138474 |
TRADITIONAL PLUMBING AND HEATING LLC | PB | P | 02/08/2019 | Stub in OK. | SAMH | SAMH | | PB | P | 6101600 |
JM WESTON HOMES LLC | XBS | T | 04/16/2019 | PAID (REC#1590640) PLAN SPLICE FEE: $50 by: DANM for Construction: Revise listed assembly to GA ASW 1000 | DANM | DANM | | XBS | T | 6166792 |