DEI ELECTRICAL CONTRACTORS | E= | C | 11/25/2020 | | JOHNN | JOHNN | | E= | C | 6789234 |
DEI ELECTRICAL CONTRACTORS | ER | P | 09/17/2020 | went over options on location of disconnects / | BRIAN | BRIAN | | ER | P | 6709342 |
DEI ELECTRICAL CONTRACTORS | E= | R | 08/17/2020 | need the voltage / cooler labels on the equipment / need the fault current rating at the disconnects / need to splice the plans to show the vfd drive/ soft start-----/ need secondary protection on the transformers taps / | BRIAN | BRIAN | | E= | R | 6674863 |
DEI ELECTRICAL CONTRACTORS | EE | L | 07/13/2020 | Renewed online for Full Fee at 7/13/2020 8:08:56 PM (RECEIPT #: 1695363) | WEBSITE | WEBSITE | | EE | L | 6635741 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | C | 09/22/2020 | ELEVATORS COMPLETE | ROBERTV | ROBERTV | | HE= | C | 6715255 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 09/08/2020 | ALL ITEMS COMPLETE EXCEPT REPLACEMENT OF CAR #2 COUNTERWEIGHT BUFFER SLIDE GUIDES | ROBERTV | ROBERTV | | HE= | P | 6699446 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 08/18/2020 | (ALL ELEVATORS) - WILL ADD NOTES WHEN COMPLETED. | ROBERTV | ROBERTV | | HE= | P | 6677376 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 05/28/2020 | (ELEVATOR #1) - WITNESSED CATEGORY 1 AND 5 ACCEPTANCE TO MODERNIZATION. ------- BY FINAL: NEED CODE DATA PLATE ON CONTROLLER. NEED ACCEPTANCE TAG ON CONTROLLER. NEED HARD COPY OF UNIQUE TESTING PROCEDURES IN MCP. NEED EMERGENCY FIRE SERVICE OPERATION AND ALARM TESTING. NEED GENERATOR TESTING. BROKEN HOISTWAY DOOR SIGHT GUARDS NEED REPLACED. NEED TWO-WAY COMMUNICATION BETWEEN CAR AND LOBBY PANEL. NEED TO COMPLETE INSTALLATION OF FIRE COMMAND CENTER LOBBY PANEL. NEED TO TEST EMERGENCY BATTERY RESCUE OPERATION. NEED ALL ELEVATOR EQUIPMENT IDENTIFICATION LABELED AS WELL AS DESIGNATED LEVEL DOOR JAMBS. TEST AND VERIFY ALL HALL FIXTURES AND DIRECTIONAL INDICATORS. HOISTWAY DOOR UNLOCKING MEANS EXCEEDS REQUIRED 39" MAX FROM PIT LADDER. BOTTOM OF CAR GUIDE ROLLER TENSION DEVICE IS BENT FROM HITTING COMP SHEAVE ELECTRICAL SWITCH CONDUIT. | ROBERTV | ROBERTV | | HE= | P | 6675581 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 02/28/2020 | (ELEVATOR #4) - WITNESSED CATEGORY 1 AND 5 ACCEPTANCE TO MODERNIZATION. ------- BY FINAL: NEED CODE DATA PLATE ON CONTROLLER. NEED HARD COPY OF UNIQUE TESTING PROCEDURES IN MCP. NEED SIL RATED DEVICE CHECKOUT PROCEDURES. NEED EMERGENCY FIRE SERVICE OPERATION AND ALARM TESTING. NEED 125% CAPACITY GENERATOR TESTING. BROKEN HOISTWAY DOOR SIGHT GUARD NEEDS REPLACED ON 7TH FLOOR. GOVERNOR MACHINERY SPACE NEEDS MINIMUM 19 FC LIGHTING. NEED TWO-WAY COMMUNICATION BETWEEN CAR AND LOBBY PANEL. NEED TO COMPLETE INSTALLATION OF FIRE COMMAND CENTER LOBBY PANEL. NEED ALL ELEVATOR EQUIPMENT IDENTIFICATION LABELED AS WELL AS DESIGNATED LEVEL DOOR JAMBS. | ROBERTV | ROBERTV | | HE= | P | 6495692 |
THYSSENKRUPP ELEVATOR CORPORATION | HE | C | 02/12/2020 | | JANE | JANE | | HE | C | 6480567 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 09/27/2019 | (ELEVATOR #3) - NEED MACHINE ROPE AND FLOOR GUARDS INSTALLED. NEED PREVIOUSLY BROKEN HOISTWAY DOOR SIGHT GUARDS ON FLOORS "P2, 4, 9, 10" REPLACED. NEED TO ENSURE ALL HOISTWAY DOORS ARE EQUIPPED WITH PROPER AMOUNT OF LOWER TRACK DOOR GUIDES AND SAFETY RETAINERS. NEED TO PERFORM GENERATOR POWER TESTING. NEED TO VERIFY LOBBY PANEL INSTALLATION AND OPERATION AS WELL AS TWO-WAY COMMUNICATION TO EACH CAR INDIVIDUALLY FROM FIRE COMMAND CENTER. NEED TO PERFORM FIREFIGHTERS EMERGENCY OPERATION TESTING.... ELEVATOR #3 OK FOR USE BY PUBLIC. | ROBERTV | ROBERTV | | HE= | P | 6351029 |
THYSSENKRUPP ELEVATOR CORPORATION | HER | P | 08/23/2019 | Checked on progress of elevator modifications | ERIC | ERIC | | HER | P | 6311712 |
DEI ELECTRICAL CONTRACTORS | XES | T | 11/23/2020 | PAID (REC#1731732): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Adding secondary OCPD | SHELBY | SHELBY | | XES | T | 6785109 |
DEI ELECTRICAL CONTRACTORS | XES | T | 08/17/2020 | PAID (REC#1704981): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised fuse type - added let thru chart and available fault current information table. | BERTHA | BERTHA | | XES | T | 6674134 |