OGC MANAGEMENT, LLC | B= | C | 06/17/2019 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 6232877 |
OGC MANAGEMENT, LLC | B= | P | 05/06/2019 | exit light added at corridor. Additional Inspections Required (computer generated): OGC MANAGEMENT, LLC Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 6188021 |
OGC MANAGEMENT, LLC | B= | P | 04/26/2019 | add exit light per plan at corridor outside office area 250 / complete required inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), OGC MANAGEMENT, LLC Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 6179422 |
OGC MANAGEMENT, LLC | BSP | P | 04/24/2019 | above ceiling marking and penetrations corrected. | NATHAN | NATHAN | | BSP | P | 6176566 |
OGC MANAGEMENT, LLC | BSP | R | 04/23/2019 | firecaulking not done and need above ceiling rated wall marking completed in new corridors. | NATHAN | NATHAN | | BSP | R | 6175179 |
OGC MANAGEMENT, LLC | B= | P | 04/22/2019 | with phased final splice and completed required inspections of outside agencies and MEP's 3rd floor or phase 1 final okay, discussed existing door at new corridor thumb turn lockset needs to be addressed. -- Schedule a new Building Final when above items are complete. | NATHAN | NATHAN | | B= | P | 6173401 |
OGC MANAGEMENT, LLC | BFR | P | 04/11/2019 | screw inspection at corridor drywall per WP 1072 okay , missing screws at above ceiling and firecaulking. | NATHAN | NATHAN | | BFR | P | 6162609 |
OGC MANAGEMENT, LLC | BFR | P | 03/26/2019 | Remove or protect icemaker line in rated wall at break room / discussed rated wall construction and using WP 1072 at 2 corridors, WEST CORRIDOR EXISTING DOOR TO SWING IN DIRECTION OF TRAVEL BY FINAL TO EXISTING CORRIDOR / DESIGN PROFESSIONAL TO ADDRESS LISTING FOR HORIZONTAL ASSEMBLY UNDER PIPES AND DUCT INSIDE RATED WALL / no new penetrations through the floor or ceiling at this time are needed / remaining framing okay with completed required inspections. Reviewed Accessible Elements / need above ceiling marking of rated walls per code by final. | NATHAN | NATHAN | | BFR | P | 6144738 |
OGC MANAGEMENT, LLC | BFR | P | 03/18/2019 | frame at 3rd floor and 2nd floor rooms 236-245, 200-227 with completed required MEP inspections, no new penetrations through floors all plumbing will attach to existing. Plans reviewed electronically / Reviewed Accessible Elements / plans in office marked for areas looked at | NATHAN | NATHAN | | BFR | P | 6135653 |
OGC MANAGEMENT, LLC | E= | C | 04/26/2019 | | BRIAN | BRIAN | | E= | C | 6179190 |
OGC MANAGEMENT, LLC | E= | P | 04/19/2019 | see plans-- | BRIAN | BRIAN | | E= | P | 6171393 |
OGC MANAGEMENT, LLC | ER | P | 04/19/2019 | see plans --blue high lighter | BRIAN | BRIAN | | ER | P | 6171386 |
OGC MANAGEMENT, LLC | E= | P | 04/16/2019 | suit 300 ok----suit 200 only in the rooms that have the file cabinets installed | BRIAN | BRIAN | | E= | P | 6167058 |
OGC MANAGEMENT, LLC | ER | P | 03/26/2019 | rest of the walls on the 2nd floor / need fire alarm permit attached | BRIAN | BRIAN | | ER | P | 6144426 |
OGC MANAGEMENT, LLC | ER | P | 03/18/2019 | partial walls on 2nd and 3rd floors --see plans | BRIAN | BRIAN | | ER | P | 6136143 |
OGC MANAGEMENT, LLC | H= | C | 06/17/2019 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6232876 |
OGC MANAGEMENT, LLC | H= | P | 04/26/2019 | PARTIAL PENDING TAB REPORT | JERRYF | JERRYF | | H= | P | 6179108 |
OGC MANAGEMENT, LLC | H= | P | 04/19/2019 | PARTIAL PENDING THE FOLLOWING - TAB REPORT - PICTURES ON FIRE DAMPER LABELS AT GRID AND DUCT ACCESS DOORS AND PICTURES OF CORRECTED SHEET ROCK AT 2 SMALL DAMPERS | JERRYF | JERRYF | | H= | P | 6171816 |
OGC MANAGEMENT, LLC | H= | P | 04/16/2019 | NEED ALL PLAN REVISIONS COMPLETED AND APPROVED - NEED FIRE DAMPERS CORRECTED HAVE BREACHES - MISSING DUCT ACCESS DOORS - MISSING RA GRILLES IN ROOMS 235 AND 243 | JERRYF | JERRYF | | H= | P | 6167539 |
OGC MANAGEMENT, LLC | HD | P | 04/04/2019 | FIRE DAMPER IN HALLWAY IN 22X16 M/P SUPPLY DUCT WEST OF ROOM # 250 OK . REVIEWED FIRE DAMPER INSTALLATION INSTRUCTION / INSTRUCTION ALLOW ANGLE TO BE FASTENED TO FRAMING AND SHEET ROCKED OVER ANGLE. | LIDO | LIDO | | HD | P | 6155212 |
OGC MANAGEMENT, LLC | HD | P | 04/02/2019 | NEED FIRE DAMPER INSTALL MANUAL TO VERIFY RETAINAGE AND NEED DAMPER AT HALLWAY INSTALLED CORRECTLY NOTES: ALL ABOVE CEILING SA MAINS / RUN OUTS AND FLEX IS COMPLETE | JERRYF | JERRYF | | HD | P | 6152453 |
OGC MANAGEMENT, LLC | HD | P | 03/22/2019 | ABOVE CEILING SA / RA MAINS AND RUN OUTS ON SOUTH EAST AND SOUTH WEST SIDE OF FLOOR - FIRE DAMPER FRAMING OK AT 4 DAMPERS | JERRYF | JERRYF | | HD | P | 6141358 |
OGC MANAGEMENT, LLC | HD | P | 03/20/2019 | NEED PLANS REVISED TO MATCH INSTALLED - ADD TRANSFER FAN FOR 2ND FLOOR TO PERMIT AND DELETE 3TD FLOOR TRANSFER FAN FROM PLANS - NEED ALL FIRE DAMPERS FRAMED CORRECTLY ON 2ND FLOOR / ONLY LOOKED AT DAMPER HOLES ON THIS FLOOR - 3TD FLOOR ABOVE CEILING SA / RA MAINS AND RUN OUTS OK | JERRYF | JERRYF | | HD | P | 6138056 |
OGC MANAGEMENT, LLC | P= | C | 04/23/2019 | correction made see images | JOSEPHD | JOSEPHD | | P= | C | 6174854 |
OGC MANAGEMENT, LLC | P= | P | 04/23/2019 | 1 drinking fountain to low, can upload image of correction, rest ok | JOSEPHD | JOSEPHD | | P= | P | 6174735 |
OGC MANAGEMENT, LLC | PTO | C | 03/29/2019 | correction made | JOSEPHD | JOSEPHD | | PTO | C | 6148595 |
OGC MANAGEMENT, LLC | PTO | P | 03/28/2019 | need to see nail protection thru out, rest ok | JOSEPHD | JOSEPHD | | PTO | P | 6147194 |
OGC MANAGEMENT, LLC | XMS | T | 04/11/2019 | PAID (REC#1589481) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout and routing revisions | JUSTINC | JUSTINC | | XMS | T | 6162587 |
OGC MANAGEMENT, LLC | XPS | T | 03/25/2019 | PAID (REC#1584780) PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Plumbing splice 3/25/19: Delta 2 revisions added and relocated S-1s and added EWCs | SHANEN | SHANEN | | XPS | T | 6143035 |