PRO WALL SYSTEMS LLC | B= | C | 09/11/2019 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 6330716 |
PRO WALL SYSTEMS LLC | B= | P | 08/22/2019 | pending completion of all other required inspections, building okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COPPER SMITH ELECTRIC INC Electrical Final Inspection is not Completed yet, DMB PLUMBING SERVICES INC. Plumbing Final Inspection is not Completed yet, MICK HEATING & SHEET METAL Mechanical Final Inspection is not Completed yet, PLUMB - MERICA LLC Plumbing Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 6311392 |
PRO WALL SYSTEMS LLC | BSP | P | 08/20/2019 | training with Lonnie S. reviewed elements of final inspection, including exiting, signage, accessible elements within rest rooms, requirements for intermediate hand rails | BOBF | BOBF | | BSP | P | 6307936 |
PRO WALL SYSTEMS LLC | B= | P | 08/20/2019 | pending other required inspections / hand rails do not return at top or bottom at stairs both sidea / stair way width measured over 60" - requires intermediate hand rail / all other building final elements OK / training with inspector Bob F -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COPPER SMITH ELECTRIC INC Electrical Final Inspection is not Completed yet, DMB PLUMBING SERVICES INC. Plumbing Final Inspection is not Completed yet, MICK HEATING & SHEET METAL Mechanical Final Inspection is not Completed yet, PLUMB - MERICA LLC Plumbing Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 6307934 |
PRO WALL SYSTEMS LLC | BFR | P | 07/12/2019 | Framing complete throughout // Discussed accessible elements by final | JEREMYA | JEREMYA | | BFR | P | 6261990 |
PRO WALL SYSTEMS LLC | BFR | P | 04/12/2019 | Need to attach Electrical & Plumbing / need to inspect Restrooms 09 & 10 when demo & framing is complete / all other areas OK pending other Roughs / discussed accessible elements | RICHB | RICHB | | BFR | P | 6164410 |
COPPER SMITH ELECTRIC INC | E= | C | 08/27/2019 | | CRAIGS | CRAIGS | | E= | C | 6315804 |
COPPER SMITH ELECTRIC INC | E= | R | 08/23/2019 | no power to the downstairs mens restroom gfci | CRAIGS | CRAIGS | | E= | R | 6312659 |
COPPER SMITH ELECTRIC INC | ER | C | 08/23/2019 | | CRAIGS | CRAIGS | | ER | C | 6312648 |
COPPER SMITH ELECTRIC INC | ER | P | 07/31/2019 | grid: need 4 clips per fixture or screws, and 2 support wires caddy corner, at least 2 fixtures had plate on top coming off, complete re inspect of grid, | JOHNN | JOHNN | | ER | P | 6283470 |
COPPER SMITH ELECTRIC INC | ER | P | 07/18/2019 | 2 restrooms OK | CRAIGS | CRAIGS | | ER | P | 6268862 |
COPPER SMITH ELECTRIC INC | ER | P | 04/16/2019 | walls OK | CRAIGS | CRAIGS | | ER | P | 6166932 |
MICK HEATING & SHEET METAL CO. | H= | C | 08/26/2019 | TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | H= | C | 6313394 |
MICK HEATING & SHEET METAL CO. | H= | P | 08/19/2019 | FINAL PENDING - Provide test and balance report for review. | MARKB | MARKB | | H= | P | 6306315 |
MICK HEATING & SHEET METAL CO. | HD | C | 08/19/2019 | SPLICE, FLEX, DIFFUSERS & THERMOSTAT COMPLETE. | MARKB | MARKB | | HD | C | 6306311 |
MICK HEATING & SHEET METAL CO. | HD | P | 05/07/2019 | ----PLAN SPLICE REQUIRED FOR FILE ROOM, EXTENDED DROP CEILING AND NEED ENGINEER TO ADDRESS SUPPLY ABOVE GRID BY STAFF ROOM.---- ABOVE CEILING DUCT - SUPPLY MAINS/BRANCHES PER PLAN. No flex or diffusers | MARKB | MARKB | | HD | P | 6191744 |
DMB PLUMBING SERVICES INC. | P= | C | 08/23/2019 | Correction made, image from contractor uploaded. | DANR | DANR | | P= | C | 6311536 |
DMB PLUMBING SERVICES INC. | P= | P | 08/21/2019 | Need AAV mop sink, picture ok, rest ok. | DANR | DANR | | P= | P | 6308730 |
DMB PLUMBING SERVICES INC. | PB | C | 08/21/2019 | Corrections made. | DANR | DANR | | PB | C | 6308722 |
DMB PLUMBING SERVICES INC. | PTO | C | 08/21/2019 | Corrections made. | DANR | DANR | | PTO | C | 6308717 |
DMB PLUMBING SERVICES INC. | P= | P | 08/07/2019 | Lower level restrooms ok. Still need water to all upper fixtures, Complete mop sink, Need approved traps at upper restroom lavs, Need vacuum relief valve, shut off valve, and pan at water heater. Complete PB and PTO inspections. | SAMH | SAMH | | P= | P | 6292482 |
PLUMB - MERICA LLC | PTO | P | 07/18/2019 | Test DWV and domestic water ok, piping not per plan need plan splice, flow test moved toilets ok (need flanges anchored). | DANR | DANR | | PTO | P | 6268024 |
PLUMB - MERICA LLC | PTO | P | 06/25/2019 | In wall and over head not per plan (mop sink wrong location and overhead domestic water not per plan), missing recir line,, need proper in wall pipe support, re-inspect all, need PB complete, fix scope of work to show all 2 toilets , 1 water heater - 2 lavatories - 1 mop sink. Note: need engineer splice for all changes (moving mop sink and water heater in old location), aav mop sink. need engineer approval for ABS pipe and in wall and over head pex pipe. | DANR | DANR | | PTO | P | 6243038 |
PLUMB - MERICA LLC | PB | R | 06/25/2019 | Not ready trip fee waived this time. | DANR | DANR | | PB | R | 6242988 |
PLUMB - MERICA LLC | PB | P | 06/18/2019 | Switched to PB inspection, cannot tie mop sink drain to back to back toilets, need engineer approval for ABS, drawings show 3" waste on mop sink, need test on moved toilets, re-inspect all. | DANR | DANR | | PB | P | 6234870 |
PRO WALL SYSTEMS LLC | XBS | T | 07/29/2019 | PAID (REC#1617850) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise layout | MICHAELA | MICHAELA | | XBS | T | 6279516 |
MICK HEATING & SHEET METAL CO. | XMS | T | 07/26/2019 | PAID (REC#1617851) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouded revisions | DALEH | DALEH | | XMS | T | 6279095 |
COPPER SMITH ELECTRIC INC | XES | T | 07/26/2019 | PAID (REC#1617853) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: As builts | SHELBY | SHELBY | | XES | T | 6279048 |
PLUMB - MERICA LLC | XPS | P | 07/26/2019 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Plumbing splice 7/26/19: Delta 2 revisions new page P1.1, water heater and mop sink location, notes 8, 2-7 | SHANEN | SHANEN | | XPS | P | 6279017 |