WANER CONSTRUCTION COMPANY, INC. | B= | C | 06/19/2019 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 6236132 |
WANER CONSTRUCTION COMPANY, INC. | B= | P | 06/14/2019 | . Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | NATHAN | NATHAN | | B= | P | 6232176 |
WANER CONSTRUCTION COMPANY, INC. | BSP | P | 06/10/2019 | above ceiling firecaulking and rated wall marking okay with completed required inspections for grid ceiling. | NATHAN | NATHAN | | BSP | P | 6225812 |
WANER CONSTRUCTION COMPANY, INC. | BSP | P | 05/30/2019 | listing changed to V455 using American Gypsum, attachment okay and firecaulking completed | NATHAN | NATHAN | | BSP | P | 6215453 |
WANER CONSTRUCTION COMPANY, INC. | BFR | P | 05/16/2019 | spliced listing to be used is U415 calling for USG material, American Gypsum has been used. New splice needs to match as built condition or build per approved splice. | NATHAN | NATHAN | | BFR | P | 6201761 |
WANER CONSTRUCTION COMPANY, INC. | BFR | P | 04/24/2019 | frame of rooms at 111,102 okay with completed required inspection, if framing for rated walls is changed or UL listing for assembly splice will be needed, design professional to designate specific system inside U419 to be used, discussed with Jeff the assembly details need to be followed. | NATHAN | NATHAN | | BFR | P | 6176892 |
ADVANCED ELECTRIC GROUP | E= | C | 06/13/2019 | office and kid care ok / | MIGUEL | MIGUEL | | E= | C | 6230747 |
ADVANCED ELECTRIC GROUP | ER | C | 06/10/2019 | above ceiling ok / | MIGUEL | MIGUEL | | ER | C | 6225891 |
ADVANCED ELECTRIC GROUP | ER | P | 04/24/2019 | new walls --ok ----note child care area | BRIAN | BRIAN | | ER | P | 6177357 |
DENVER HEATING & AIR CONDITIONING | H= | C | 06/14/2019 | DAMPER LABEL IN PLACE AND TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6231493 |
DENVER HEATING & AIR CONDITIONING | H= | P | 06/07/2019 | PARTIAL FINAL PENDING TAB REPORT AND PICTURE OF FIRE DAMPER LABEL AT CEILING GRID NOTES: ALL SA / RA GRILLES - DAMPER RETAINAGE AND ACCESS DOOR OK | JERRYF | JERRYF | | H= | P | 6223781 |
DENVER HEATING & AIR CONDITIONING | HD | P | 05/29/2019 | FIRE DAMPER FRAMING OK AT SHAFT WALL, STILL NEED TO SEE RETAINING ANGLE. NEW SUPPLY AIR DUCTS OK, OK TO WRAP. NO FLEX AND DIFFUSERS INSTALLED. | DUSTINS | DUSTINS | | HD | P | 6212724 |
DENVER HEATING & AIR CONDITIONING | HD | P | 05/24/2019 | NEED DAMPER FRAMED CORRECTLY HAD CONSULT WITH G.C ON FRAMING FOR NEXT INSPECTION PLEASE REQUEST COMMERCIAL INSPECTOR DUSTIN WHO IS FAMILIAR WITH THIS PROJECT -NOTES ABOVE CEILING SA MAINS AND RUN OUTS OK | JERRYF | JERRYF | | HD | P | 6209790 |
DENVER HEATING & AIR CONDITIONING | HD | P | 05/21/2019 | THE "J" CHANNEL TO THE RIGHT SIDE OF THE DAMPER OPENING NEEDS TO BE ONE CONTINUOUS PIECE PER THE INSTALLATION INSTRUCTIONS. | DUSTINS | DUSTINS | | HD | P | 6206440 |
DENVER HEATING & AIR CONDITIONING | HD | T | 05/20/2019 | PAID (REC#1599892): DAMPER NEED TO BE REMOVED FOR FRAMING INSPECTION - DAMPER NEEDS TO BE FRAMED CORRECTLY FOR SHAFT WALL INSTALLATION - CONTRACTOR TO VERIFY FRAMING BEFORE CALLING INSPECTION | JERRYF | JERRYF | | HD | T | 6204199 |
DENVER HEATING & AIR CONDITIONING | HD | R | 05/16/2019 | NEED DAMPER INSTALL MANUAL FOR ROUND DAMPERS TO VERIFY FRAMING REQUIREMENTS | JERRYF | JERRYF | | HD | R | 6201115 |