ALEXANDHER BUILDING CO, INC. | B= | C | 07/16/2019 | All other required Final inspections are complete. (This is a computer generated result) | CHUCK | CHUCK | | B= | C | 6265439 |
ALEXANDHER BUILDING CO, INC. | B= | P | 07/16/2019 | Panic bar raised and dead bolt removed at front entry. Building final OK pending completion of mechanical final inspection. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: jbumgarner@tlmfire.org or 484-0911). | CHUCK | CHUCK | | B= | P | 6264850 |
ALEXANDHER BUILDING CO, INC. | B= | P | 07/11/2019 | panic bar at main entry is too low / need to remove the dead bolt with the thumb turn on it at the main entry door / rest of suite is OK pending other finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: jbumgarner@tlmfire.org or 484-0911), External Agency Inspection Z= by TOWNOFMON is not Completed yet (Contact: Tom Martinez at 884-8036), AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 6260951 |
ALEXANDHER BUILDING CO, INC. | BFR | P | 05/13/2019 | Frame OK - discussed accessible elements with contractor. | CHUCK | CHUCK | | BFR | P | 6196686 |
EL PASO ELECTRIC, LLC. | E= | C | 07/11/2019 | | BRET | BRET | | E= | C | 6260616 |
EL PASO ELECTRIC, LLC. | EP | C | 07/11/2019 | Overcurrent protection for panel 4 located in east unit, Building owner provided letter stating compliance per National Electrical Code 240.24 | BRET | BRET | | EP | C | 6260615 |
BJ COMPANY, LLC | E= | C | 07/09/2019 | FIRE ALARM INSPECTION: rough in complete | TOMC | TOMC | | E= | C | 6256750 |
EL PASO ELECTRIC, LLC. | ER | P | 06/27/2019 | ceiling only | TOMC | TOMC | | ER | P | 6246505 |
EL PASO ELECTRIC, LLC. | ER | P | 05/14/2019 | walls | BRET | BRET | | ER | P | 6198419 |
EL PASO ELECTRIC, LLC. | ER | R | 05/09/2019 | walls except panel wall and remove power in 108 lab/prep wall | BRET | BRET | | ER | R | 6193982 |
AIRTECH MECHANICAL, INC. | H= | C | 07/16/2019 | MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6264821 |
AIRTECH MECHANICAL, INC. | H= | P | 07/16/2019 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. | DUSTINS | DUSTINS | | H= | P | 6264177 |
AIRTECH MECHANICAL, INC. | H= | P | 07/09/2019 | MECHANICAL FINAL OK PENDING: MISSING DG-1 FOR TRANSFER AIR TO IT CLOSET, LABEL CONDENSING UNIT FOR SUITE SERVED, PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6256901 |
DRUMMOND PLUMBING LLC | H= | C | 07/09/2019 | GAS FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6256895 |
DRUMMOND PLUMBING LLC | H= | P | 06/27/2019 | GAS FINAL OK PENDING: GAS FLEX CONNECTOR TO FURNACE IS UNDERSIZED FOR 120K. STILL NEED WATER HEATER VENT TERMINATION TO BE 10' AWAY OR 3' HIGHER THAN FURNACE OUTSIDE AIR INTAKE. | DUSTINS | DUSTINS | | H= | P | 6246166 |
AIRTECH MECHANICAL, INC. | HD | P | 05/29/2019 | ALL ABOVE CEILING SUPPLY/RETURN/OUTSIDE AIR OK, OK TO WRAP. EXHAUST DUCTS OK EXCEPT MISSING EXHAUST DUCT TO EXAM 105. OUTSIDE AIR INTAKE NEEDS TO BE 10' AWAY OR 3' BELOW WATER HEATER VENT TERMINATION. | DUSTINS | DUSTINS | | HD | P | 6213189 |
DRUMMOND PLUMBING LLC | HV | P | 05/29/2019 | WATER HEATER VENT ABOVE CEILING OK EXCEPT TERMINATION NEEDS TO BE 10' AWAY OR 3' HIGHER THAN FURNACE OUTSIDE AIR INTAKE. CHECK CONNECTIONS TO EQUIPMENT AT FINAL. | DUSTINS | DUSTINS | | HV | P | 6213182 |
DRUMMOND PLUMBING LLC | HC | C | 05/29/2019 | ADDING 220MBH TO EXISTING LOAD. | DUSTINS | DUSTINS | | HC | C | 6213181 |
DRUMMOND PLUMBING LLC | HI | C | 05/29/2019 | 10 LB TEST OK. PIPING PER PLAN. ADDING 220MBH TO EXISTING LOAD. | DUSTINS | DUSTINS | | HI | C | 6213172 |
DRUMMOND PLUMBING LLC | P= | C | 06/27/2019 | **STILL NEED revisions (refer to PB notes) **NEED TO add w.b. to scope of work | JOHNS | JOHNS | | P= | C | 6246660 |
DRUMMOND PLUMBING LLC | PTO | C | 05/15/2019 | BY FINAL need to add washer box to scope of work ok for test / design. NOTE: vtr (2) new, **will need roof access @ final, check water htr @ final | JOHNS | JOHNS | | PTO | C | 6199946 |
DRUMMOND PLUMBING LLC | PB | C | 04/17/2019 | **NEED to revise plans to show as built installation ok for test / design **INS NOTE: plans call for no copper in this bldg, verify @ pto | JOHNS | JOHNS | | PB | C | 6168497 |