SNYDER BUILDING CONSTRUCTION, LLC | B= | C | 09/12/2019 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 6332492 |
SNYDER BUILDING CONSTRUCTION, LLC | B= | P | 08/16/2019 | Building final OK pending all other finals complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 6303467 |
SNYDER BUILDING CONSTRUCTION, LLC | B= | P | 08/15/2019 | Temp CO: All finals are complete or pending ( Expires: 9/14/2019 12:00:00 AM) | GITA | GITA | | B= | P | 6302212 |
SNYDER BUILDING CONSTRUCTION, LLC | B= | P | 08/14/2019 | Need to install occ load sign / All other aspects of building final OK / Need all other finals complete -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), PRESTIGE MECHANICAL CONTRACTORS,INC Mechanical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 6300674 |
REEVES SPECIALTY SERVICES, INC. | BSP | P | 08/05/2019 | ADDITIONAL PLAN REVIEW TIME: From: DALEH fitchen diffuser cfm | DALEH | DALEH | | BSP | P | 6288801 |
SNYDER BUILDING CONSTRUCTION, LLC | BSP | P | 07/18/2019 | Double layer 5/8 rock per approved listing on both sides of wall OK / Head wall OK | NICK | NICK | | BSP | P | 6268088 |
SNYDER BUILDING CONSTRUCTION, LLC | BSP | P | 06/24/2019 | 2nd layer rock at kitchen and electrical panel OK per approved listing / Still need head wall detail / Still need to fire caulk all penetrations / Need to install rock on opposing unit | NICK | NICK | | BSP | P | 6241707 |
SNYDER BUILDING CONSTRUCTION, LLC | BSP | P | 06/18/2019 | Fire barrier inspection per splice per IBC 721 listing / Need double layer 1/2" both sides of wall / Need to fire caulk all penetrations / Need head wall detail for top of wall | NICK | NICK | | BSP | P | 6234785 |
SNYDER BUILDING CONSTRUCTION, LLC | BSP | R | 06/07/2019 | Unable to read plans on contractors computer for new listing going to be used for rated wall / Need to splice into approved plans / American rock still installed and will not meet U404 listing for USG rock | NICK | NICK | | BSP | R | 6224288 |
SNYDER BUILDING CONSTRUCTION, LLC | BSP | R | 05/31/2019 | U404 is a proprietary listing using USG American Gypsum installed | NATHAN | NATHAN | | BSP | R | 6215894 |
SNYDER BUILDING CONSTRUCTION, LLC | BFR | P | 05/31/2019 | backing installed at restrooms, rated listing U404 provided calls for USG drywall American Gypsum used drywall needs to match or change listing and provide full listing. | NATHAN | NATHAN | | BFR | P | 6215876 |
SNYDER BUILDING CONSTRUCTION, LLC | BSP | P | 05/30/2019 | Need detail to verify screw pattern and drywall | JEREMYA | JEREMYA | | BSP | P | 6214500 |
SNYDER BUILDING CONSTRUCTION, LLC | BFR | P | 05/30/2019 | Interior wall framing OK // Need detail for rated wall between suites // Discussed accessible elements | JEREMYA | JEREMYA | | BFR | P | 6214499 |
CASCADE ELECTRIC, LLC. | E= | C | 07/26/2019 | corrections made | GARYL | GARYL | | E= | C | 6278838 |
CASCADE ELECTRIC, LLC. | E= | R | 07/25/2019 | Need gfci protection on recept in bar area by sink, | GARYL | GARYL | | E= | R | 6277514 |
CASCADE ELECTRIC, LLC. | ER | P | 07/16/2019 | "cloud" and above coolers ok | GARYL | GARYL | | ER | P | 6265902 |
CASCADE ELECTRIC, LLC. | ES | C | 07/03/2019 | Commercial Service: 2 Meter sets, 200 amp 120/208 4-wire, UNITS 3171 C., 3171 D, | GARYL | GARYL | | ES | C | 6253444 |
CASCADE ELECTRIC, LLC. | ER | P | 06/25/2019 | all ceilings EXCEPT over coolers etc | GARYL | GARYL | | ER | P | 6243782 |
CASCADE ELECTRIC, LLC. | ER | P | 05/29/2019 | all walls,ok | JOHNN | JOHNN | | ER | P | 6213034 |
CASCADE ELECTRIC, LLC. | ER | P | 05/22/2019 | hard lids in bathrooms | GARYL | GARYL | | ER | P | 6207876 |
CASCADE ELECTRIC, LLC. | ESL | C | 05/01/2019 | slab--ok | BRIAN | BRIAN | | ESL | C | 6183882 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | C | 08/15/2019 | SEE IMAGES FOR VENT CORRECTIONS | JERRYF | JERRYF | | H= | C | 6301332 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | P | 08/14/2019 | PARTIAL PENDING VENT CORRECTION ON ROOF OK TO ATTACH PICTURES TO NEXT INSPECTION REQUEST | JERRYF | JERRYF | | H= | P | 6300156 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | P | 08/09/2019 | PARTIAL PENDING: SUPPORT VENT AND INTAKE PER THE INSTALLATION INSTRUCTIONS INSIDE TENANT SPACE AND ON ROOF. MISSING INTAKE CONDENSATE AND TRAP . | LIDO | LIDO | | H= | P | 6294878 |
REEVES SPECIALTY SERVICES, INC. | H= | C | 08/09/2019 | HEAT FINAL OK. | LIDO | LIDO | | H= | C | 6294870 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 08/08/2019 | TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) STILL NEED ROOF INSPECTION. | LIDO | LIDO | | H= | P | 6292785 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 08/02/2019 | TEST AND BALANCE REPORT REVIEW ONLY :(THE CFM'S ARE NOT SHOWN ON THE PLANS FOR 7 - 24X24 SUPPLY GRILLS FROM RTU-3E / NEED REVISED AND APPROVED SPLICE TO SHOW THE CFM'S .) RTU-3E AND RTU -4E ARE NOT IDENTIFIED ON THE TEST AND BALANCE REPORT ACCURATELY / NEED REVISED TEST AND BALANCE REPORT AND TEST AND BALANCE REPORT WILL NEED TO BE COMPLETED PER THE SPLICE. | LIDO | LIDO | | H= | P | 6286037 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HC | C | 08/01/2019 | OK TO RELEASE EXISTING 2 lb METER / ADDED GAS LOAD 199.9 K BTU'S | LIDO | LIDO | | HC | C | 6284593 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 07/31/2019 | PARTIAL PENDING: NEED REVISED AND APPROVED PLANS FOR DUCT DESIGN CHANGES ABOVE BAR / THREE SUPPLY GRILLS ARE NOW INSTALLED IN A HARD LID INSTEAD OF SURFACE MOUNT EXPOSED.ACCESS TO ROOF IS LOCKED / NEED ROOF ACCESS FOR INSPECTION .NEED TEST AND BALANCE REPORT | LIDO | LIDO | | H= | P | 6283413 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HC | P | 07/30/2019 | (( CAN NOT RELEASE METER TILL GAS SPLICE HAS GONE THROUGH PLANS AND REVIEW FOR APPROVAL. )) | LIDO | LIDO | | HC | P | 6281011 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | P | 07/29/2019 | PLAN SPLICE REQUIRED - ENGINEERED GAS PLAN HAS A DESIGN PRESSURE OF 14" W.C. BUT BUILDING HAS A 2 PSI SYSTEM INSTALLED. FINISH ONLY HAS GAS NEEDED FOR WATER HEATER BUT PLAN ALSO SHOWS RTU'S.(( CAN NOT RELEASE METER TILL SPLICE HAS GONE THROUGH PLANS AND REVIEW FOR APPROVAL. )) SUPPORT VENT AND INTAKE PER THE INSTALLATION INSTRUCTIONS. MISSING INTAKE CONDENSATE AND TRAP . VENT AND INTAKE ON THE ROOF IS LESS THAN 10 FEET FROM PARAPET / NEED TO RAISE VENT AND INTAKE 24 INCHES ABOVE PARAPET PER PAGE # 26. | LIDO | LIDO | | H= | P | 6280299 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HV | P | 07/29/2019 | NEED TO SUPPORT VENT AND INTAKE PER THE INSTALLATION INSTRUCTIONS. MISSING INTAKE CONDENSATE AND TRAP . VENT AND INTAKE ON THE ROOF IS LESS THAN 10 FEET FROM PARAPET / NEED TO RAISE VENT AND INTAKE 24 INCHES ABOVE PARAPET PER PAGE # 26. | LIDO | LIDO | | HV | P | 6280274 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 07/24/2019 | (( CONTRACTOR THAT INSTALLED WATER HEATER VENT NEEDS TO ADD TO THERE SCOPE OF WORK AND CALL FOR INSPECTION)) NEED REVISED AND APPROVED PLANS FOR DUCT DESIGN CHANGES ABOVE BAR / THREE SUPPLY GRILLS ARE NOW INSTALLED IN A HARD LID INSTEAD OF SURFACE MOUNT EXPOSED. INSTALL REMOTE SMOKE INDICATOR FOR RTU-4E. INSTALL TOP OF THERMOSTATS NO HIGHER THAN 48" OFF FINISHED FLOOR. MISSING 2 - CO2 SENCORS REFER TO NOTE # 11. NEED CONDENSATE INSTALLED FOR COOLER / COOLER AND FREEZER ARE SELF CONTAINED. STILL NEED TO INSPECT ROOF. NEED TEST AND BALANCE REPORT . | LIDO | LIDO | | H= | P | 6274977 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | P | 05/28/2019 | ----PLAN SPLICE REQUIRED - ENGINEERED GAS PLAN HAS A DESIGN PRESSURE OF 14" W.C. BUT BUILDING HAS A 2 PSI SYSTEM INSTALLED. FINISH ONLY HAS GAS NEEDED FOR WATER HEATER BUT PLAN ALSO SHOWS RTU'S----
10 PSI PRESSURE TEST OK, PIPING PER PLAN. 2 PSI APPROVAL FROM CSU ON FILE. Still need final connections and regulator installed. | MARKB | MARKB | | HI | P | 6212034 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 05/23/2019 | NEED ALL EXHAUST FAN DUCTS COMPLETED AND INSPECTED - STILL NEED ROOF INSPECTION NOTES: ALL ABOVE CEILING SA / RA MAINS AND RUN OUTS INCLUDING HARD LID AREA'S OK | JERRYF | JERRYF | | HD | P | 6209261 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | C | 09/12/2019 | Water main size corrected. See images. | SAMH | SAMH | | P= | C | 6332491 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 08/15/2019 | still need engineer letter for water pipe sizing from inspection on 5/22/19 other letter ok | JOSEPHD | JOSEPHD | | P= | P | 6301475 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 08/14/2019 | need engineer letters, other corrections made | JOSEPHD | JOSEPHD | | P= | P | 6301050 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 07/29/2019 | left hand bathroom lav to high, need access to aav's at bar, no hot water, check air gaps at sinks next trip, need letters from previous inspections, | JOSEPHD | JOSEPHD | | P= | P | 6280344 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | C | 05/24/2019 | Check water heater, and back VTR clearance at final, Need engineers letter for existing 2"x1" tee supplying 1-1/4" main, And use of trap guards in lieu of trap primers, Need owners letter to approve PEX. | SAMH | SAMH | | PTO | C | 6209952 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 05/22/2019 | Check insulation, Anchor flanges, Note: Check water heater at final. Need owner approval for PEX water lines, Need engineers letter for trap guard, Need engineers letter for existing 2'x1" tee supplying 1-1/4" main. Check back VTR clearance at final. | SAMH | SAMH | | PTO | P | 6206801 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PB | C | 04/23/2019 | Need to revise plans to show trap guards in lieu of trap primers. | SAMH | SAMH | | PB | C | 6174647 |
REEVES SPECIALTY SERVICES, INC. | XMS | T | 07/31/2019 | PAID (REC#1618616): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouded revisions | DALEH | DALEH | | XMS | T | 6282963 |
SNYDER BUILDING CONSTRUCTION, LLC | XBS | T | 07/10/2019 | PAID (REC#1614009): PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Revised demising wall to UL U411 | LBENNETT | LBENNETT | | XBS | T | 6258453 |
SNYDER BUILDING CONSTRUCTION, LLC | XBS | T | 06/13/2019 | PAID (REC#1606900): PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Rated demising wall per IBC 907.2.1 | LBENNETT | LBENNETT | | XBS | T | 6230547 |
PRESTIGE MECHANICAL CONTRACTORS,INC | XPS | T | 06/06/2019 | PAID (REC#1605681): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Plumbing splice 6/6/19: Delta 5 revision - Trap guard detail in lieu of trap primer detail | SHANEN | SHANEN | | XPS | T | 6222165 |