SEEGER HOMES, INC | B= | C | 11/18/2019 | Insignia # 2019-2437 | JUSTINL | JUSTINL | | B= | C | 6403128 |
SEEGER HOMES, INC | B= | P | 11/12/2019 | Gutters/downspouts/extensions not installed / Need to install handrail to attic stairway / Door to unconditioned attic to be insulated and weatherstripped to a level equivalent to insulation on surrounding surfaces. -- Schedule a new Building Final when above items are complete. | CHUCK | CHUCK | | B= | P | 6396071 |
SEEGER HOMES, INC | BIN | C | 11/05/2019 | | CHUCK | CHUCK | | BIN | C | 6388666 |
SEEGER HOMES, INC | BSP | P | 11/04/2019 | Anchor steel posts in basement, anchor interior stair landing posts and deck framing on back of garage OK. | CHUCK | CHUCK | | BSP | P | 6387640 |
SEEGER HOMES, INC | BFR | C | 11/04/2019 | | CHUCK | CHUCK | | BFR | C | 6387639 |
SEEGER HOMES, INC | BIN | P | 11/01/2019 | 3rd party air leakage report on file. Need to complete BFR inspection. | CHUCK | CHUCK | | BIN | P | 6385265 |
SEEGER HOMES, INC | BFR | R | 10/30/2019 | Garage - sill plate anchor bolts too close to edge of plate (shall be located in middle third of plate), left wall / Missing sill anchor bolt within 12" of plate end, garage service door / Basement - Missing stud posts at specified distances / Need to secure bottom of steel posts and stairway landing posts. | CHUCK | CHUCK | | BFR | R | 6383734 |
SEEGER HOMES, INC | BSP | P | 10/28/2019 | Rear deck piers OK. | CHUCK | CHUCK | | BSP | P | 6382076 |
SEEGER HOMES, INC | BSP | P | 10/28/2019 | Updated plans to add landing at rear of garage on file. | CHUCK | CHUCK | | BSP | P | 6381522 |
SEEGER HOMES, INC | BTD | C | 10/03/2019 | | SCOTTS | SCOTTS | | BTD | C | 6356568 |
SEEGER HOMES, INC | BTD | R | 09/27/2019 | Unable to see anchor bolts at concrete foundation - missing H3 every 3rd joist or 16d nails at 6" o.c. to tie building joists to plates / Missing 3" steel posts to support steel beam at marriage line. | CHUCK | CHUCK | | BTD | R | 6350785 |
SEEGER HOMES, INC | BFD | C | 08/08/2019 | Drain usable to daylight at walk out / Damp proof OK / Drain ok / Contractor to backfill per requirements of Soils Report / | JUSTINL | JUSTINL | | BFD | C | 6294068 |
SEEGER HOMES, INC | BFI | C | 08/08/2019 | R10 installed at walk out | JUSTINL | JUSTINL | | BFI | C | 6294046 |
SEEGER HOMES, INC | BFN | C | 08/05/2019 | Foundation wall reinforcement ok per plan on file | TIMOTHYS | TIMOTHYS | | BFN | C | 6289103 |
SEEGER HOMES, INC | BFT | C | 07/23/2019 | Reinforced footers OK per approved foundation design on file | JUSTINL | JUSTINL | | BFT | C | 6274306 |
SEEGER HOMES, INC | BFT | P | 07/23/2019 | Soils and open hole on file - 3000 PSF ( verified ) / Drain usable / 5% // Still need to perform site inspection for footers or provide 3rd party observation | JUSTINL | JUSTINL | | BFT | P | 6272915 |
LAKE STAR ELECTRIC, INC. | E= | C | 11/11/2019 | E= OK ------ | GREGM | GREGM | | E= | C | 6395239 |
LAKE STAR ELECTRIC, INC. | ES | C | 10/29/2019 | Residential Underground: 200-amp 3 Wire New Residence ok NEED METER SEAL. / | GREGM | GREGM | | ES | C | 6382806 |
LAKE STAR ELECTRIC, INC. | ER | C | 10/29/2019 | ER OK ------ GARAGE AND UNFINISHED BASEMENT ------- | GREGM | GREGM | | ER | C | 6382801 |
LAKE STAR ELECTRIC, INC. | EUG | C | 10/04/2019 | EUG OK -----4/0 ------ | GREGM | GREGM | | EUG | C | 6358541 |
LAKE STAR ELECTRIC, INC. | ES | R | 10/04/2019 | Residential Underground: HOUSE WAS LOCKED NEED ACCESS TO PANEL ------- | GREGM | GREGM | | ES | R | 6358532 |
ALL SEASONS HEATING AND AIR CONDITIONING | H= | C | 11/07/2019 | Note: Unfinished attic, unfinished basement, furnace is direct vented, water is electric. | MARK | MARK | | H= | C | 6392141 |
ALL SEASONS HEATING AND AIR CONDITIONING | HC | C | 11/07/2019 | RELEASE METER | MARK | MARK | | HC | C | 6392140 |
ALL SEASONS HEATING AND AIR CONDITIONING | HRR | C | 11/07/2019 | | MARK | MARK | | HRR | C | 6392130 |
ALL SEASONS HEATING AND AIR CONDITIONING | HRR | P | 10/21/2019 | need to rsearch kitchen exhaust, other corrections have been made. | MARK | MARK | | HRR | P | 6375385 |
ALL SEASONS HEATING AND AIR CONDITIONING | H= | P | 10/21/2019 | Will update in the am regarding kitchen exhaust at roof deck. Other corrections have been made. Was able to check furnace vent connections and pitch under floor in attic. slope is ok. | MARK | MARK | | H= | P | 6375384 |
ALL SEASONS HEATING AND AIR CONDITIONING | HRR | P | 10/08/2019 | Changed from H= to HRR. Need to extend kitchen exhaust entirely through the roof deck. B vent is in contact with the roof deck, part of the furnace vent is enclosed and I need to be able to see it because it has been modified from the original design. Note: MFG home, direct vent furnace, electric water heater, no a/c. | MARK | MARK | | HRR | P | 6362196 |
R AND D PLUMBING | HI | C | 10/07/2019 | 10 lb test ok. Note: 11/4" main. Meter at the house. This is a mfg home. 1- furnace, 1- range, 1- fireplace. | MARK | MARK | | HI | C | 6360626 |
R AND D PLUMBING | P= | C | 11/06/2019 | Potable Water Certificate Received | MALYNDA | MALYNDA | | P= | C | 6389493 |
R AND D PLUMBING | P= | P | 11/05/2019 | Need Certificate of potable water. Rest OK. | SAMH | SAMH | | P= | P | 6388890 |
R AND D PLUMBING | PTO | C | 11/05/2019 | | SAMH | SAMH | | PTO | C | 6388887 |
R AND D PLUMBING | PB | C | 08/21/2019 | Note: need certificate of potable water by final | MALYNDA | MALYNDA | | PB | C | 6309347 |
SEEGER HOMES, INC | XBS | T | 10/25/2019 | PAID (REC#1640281) PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Added landing to back of garage. | BPHILLIPS | BPHILLIPS | | XBS | T | 6381261 |