ELITE PROPERTIES OF AMERICA, INC. | B= | C | 03/04/2020 | | CHUCK | CHUCK | | B= | C | 6499359 |
ELITE PROPERTIES OF AMERICA, INC. | B= | P | 02/10/2020 | Temp CO: Extension per MM ( Expires: 3/11/2020 12:00:00 AM) | GITA | GITA | | B= | P | 6477403 |
ELITE PROPERTIES OF AMERICA, INC. | B= | P | 01/10/2020 | Temp CO: Extension ( Expires: 2/9/2020 12:00:00 AM) | GITA | GITA | | B= | P | 6449978 |
ELITE PROPERTIES OF AMERICA, INC. | B= | P | 12/13/2019 | Temp CO: OK for TCO per MMand BW ( Expires: 1/12/2020 12:00:00 AM) | GITA | GITA | | B= | P | 6427746 |
ELITE PROPERTIES OF AMERICA, INC. | B= | P | 12/06/2019 | Still need to complete core and shell - Other items corrected -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | TIMOTHYS | TIMOTHYS | | B= | P | 6419810 |
ELITE PROPERTIES OF AMERICA, INC. | B= | P | 11/19/2019 | need to complete core and shell / all sliding doors need to be adjusted so that the handle can be accessed from the inside of the offices / paper towel dispensers in both restrooms are both in the clear floor space for the toilets -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 6404777 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | P | 09/30/2019 | framing is complete per splice and plan/complete other rough inspections -- Reviewed Accessible Elements / | SCOTTS | SCOTTS | | BFR | P | 6351955 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | R | 09/05/2019 | Frame plans still show Type A walls braced to structure (some only braced to adjacent non bearing walls) and Type D wall detail shows to attach to slip track at roof deck / No plan update on file for drop ceiling framing/hard lid ceilings in bathrooms / Plans for bathroom dimensions have been corrected to reflect actual layout. | CHUCK | CHUCK | | BFR | R | 6324961 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | R | 09/03/2019 | Changes in layout, bracing and addition of drop ceiling to be spliced into plans. | CHUCK | CHUCK | | BFR | R | 6321272 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | R | 08/22/2019 | Bathroom framing dimensions do not reflect plan dimensions as per Sht. A1.0/A3.0, detail 5 / Type A/D wall are not braced/attached to structure above as shown on details as per Sht. A1.0 / Framing for drop ceilings in bathrooms not shown on plans. | CHUCK | CHUCK | | BFR | R | 6310620 |
ENCORE ELECTRIC, INC. | E= | C | 12/02/2019 | | BRET | BRET | | E= | C | 6412386 |
ENCORE ELECTRIC, INC. | E= | P | 11/01/2019 | ok pending core and shell final | BRET | BRET | | E= | P | 6385507 |
ENCORE ELECTRIC, INC. | ER | P | 09/24/2019 | suspended ceiling ok, bath lids not ready | BRET | BRET | | ER | P | 6346220 |
ENCORE ELECTRIC, INC. | EP | R | 09/24/2019 | panel not ready | BRET | BRET | | EP | R | 6346205 |
ENCORE ELECTRIC, INC. | ES | C | 09/24/2019 | Commercial Service: 200 amp service need meter set for 5750 made to main disconnect only existing 800 amp service on core and shell | BRET | BRET | | ES | C | 6346194 |
ENCORE ELECTRIC, INC. | ER | P | 08/21/2019 | walls ok | BRET | BRET | | ER | P | 6308622 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 10/30/2019 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. PICTURES OF CORRECTIONS ALSO ATTACHED WITH BALANCE REPORT. MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6383363 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 09/26/2019 | LABEL T-STATS AND REMOTE INDICATORS PER PLAN. INSTALL REMOTE INDICATOR FOR RTU-6. PERMANENTLY LABEL RTU'S WITH ADDRESS 2750. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 6349573 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 08/30/2019 | CONNECTIONS TO EXHAUST FANS ABOVE HARD LID OK, NO ROOF TODAY | BENH | BENH | | HD | P | 6320048 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 08/21/2019 | SUPPLY/RETURN AIR MAIN TRUNKS AND LATERALS OK, OK TO WRAP. EXHAUST DUCTS ABOVE CEILING OK, NEED TO SEE CONNECTIONS IN BATH ROOMS. SMOKE DETECTORS ALL INTERNALLY MOUNTED IN RTU'S. AT FINAL VERIFY REMOTE INDICATORS INSTALLED. FYI: PERMITS PULLED AFTER 7-1-19 ALL RTU'S EITHER NEW OR REPLACEMENT NEED TO HAVE A WATER LEVEL MONITORING DEVICE INSTALLED AND P-TRAPS TO BE INSTALLED PER INSTALLATION INSTRUCTIONS. | DUSTINS | DUSTINS | | HD | P | 6308350 |
KAMPP-L ENTERPRISES, INC. | P= | C | 10/17/2019 | | TAYLOR | TAYLOR | | P= | C | 6371710 |
KAMPP-L ENTERPRISES, INC. | PTO | C | 08/29/2019 | Check water heater at final. | SAMH | SAMH | | PTO | C | 6318976 |
ELITE PROPERTIES OF AMERICA, INC. | XBS | T | 09/23/2019 | PAID (REC#1632152): PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Revised wall bracing detail, ceiling, framing at water heater platform. | BPHILLIPS | BPHILLIPS | | XBS | T | 6343990 |
ELITE PROPERTIES OF AMERICA, INC. | XBS | T | 08/30/2019 | PAID (REC#1626945): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised wall types at restrooms | SHELLEY | SHELLEY | | XBS | T | 6320701 |