TRAIL STAR DEVELOPMENT, LLC | B= | C | 08/16/2019 | All other required Final inspections are complete. (This is a computer generated result) | DAKOTAB | DAKOTAB | | B= | C | 6303502 |
TRAIL STAR DEVELOPMENT, LLC | B= | P | 08/16/2019 | Building final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | DAKOTAB | DAKOTAB | | B= | P | 6303407 |
TRAIL STAR DEVELOPMENT, LLC | B= | R | 08/16/2019 | Test and balance report is to be uploaded as a mechanical inspection. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), MCNITT BROTHERS HEATING Mechanical Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | R | 6303043 |
TRAIL STAR DEVELOPMENT, LLC | BFR | P | 07/19/2019 | items corrected / framing OK pending other roughs | DANE | DANE | | BFR | P | 6270184 |
TRAIL STAR DEVELOPMENT, LLC | BFR | R | 07/12/2019 | C note on plans calls for walls to be full height to under side of roof and float but walls at storage room and water heater are not full height / need to add in the pony wall that has been added at the southwest corner of the main room where the plan note L calls for a new counter at max 36" high but does not mention a new wall or height | DANE | DANE | | BFR | R | 6261924 |
JNB ELECTRIC, INC. | E= | C | 08/15/2019 | | BRET | BRET | | E= | C | 6302651 |
JNB ELECTRIC, INC. | E= | R | 08/14/2019 | field canceled not ready | BRET | BRET | | E= | R | 6300410 |
JNB ELECTRIC, INC. | E= | R | 08/09/2019 | gfci protect all receptacles within 6' of sinks, gfci receptacles cannot be located behind coolers, panel schedule, verify breaker for cooler condenser is correct, call for new panel (ep )inspection with final | BRET | BRET | | E= | R | 6295294 |
JNB ELECTRIC, INC. | ER | C | 08/06/2019 | cut in boxes complete, no ceiling work | BRET | BRET | | ER | C | 6289984 |
JNB ELECTRIC, INC. | ER | P | 08/05/2019 | serving area half wall ok | BRET | BRET | | ER | P | 6288477 |
JNB ELECTRIC, INC. | ER | P | 07/12/2019 | walls ok | BRET | BRET | | ER | P | 6262232 |
JNB ELECTRIC, INC. | ESL | C | 07/09/2019 | 3/4 " conduit from kitchen wall to serving line | BRET | BRET | | ESL | C | 6257512 |
MCNITT BROTHERS HEATING | H= | C | 08/16/2019 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. MECHANICAL AND GAS FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6303078 |
MCNITT BROTHERS HEATING | H= | P | 08/15/2019 | TEST AND BALANCE REPORT RECEIVED, NEED TO REVIEW AND SCAN ONTO PERMIT IN THE MORNING. KITCHEN INTERLOCKS CONFIRMED. MECHANICAL AND GAS FINAL OK PENDING REVIEW OF TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6301939 |
MCNITT BROTHERS HEATING | HV | C | 08/14/2019 | WATER HEATER VENT OK. | DUSTINS | DUSTINS | | HV | C | 6300024 |
MCNITT BROTHERS HEATING | HD | P | 08/14/2019 | CHANGED TO HD INSPECTION. KITCHEN INTERLOCKS ARE NOT WORKING WITH RTU-5 PER PLAN, SEE M1.0 (BDA 10) MECHANICAL AND GAS FINAL PENDING KITCHEN INTERLOCKS AND TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | HD | P | 6300021 |
COLORADO COMMERCIAL REFRIGERATION, INC | H= | C | 08/12/2019 | NO LEAKAGE ALARMS REQUIRED, SEE M1.1 (BDA 11). REFRIGERATION FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6296548 |
MCNITT BROTHERS HEATING | HD | P | 08/09/2019 | NEED GASKET FOR GREASE FANS TO BE UNDER FANS, NOT GREASE DUCT. NEED TO VERIFY KITCHEN INTERLOCKS. SEAL EXHAUST DUCTS ON ROOF. GUARD RAILING INSTALLED ON ROOF. PER ENGINEER WATER HEATER VENT IS BEING RELOCATED, NEED INSPECTION ON VENT WHEN RELOCATED. | DUSTINS | DUSTINS | | HD | P | 6294858 |
MCNITT BROTHERS HEATING | HC | C | 08/09/2019 | TOTAL LOAD 1250 CFH. SYSTEM OPERATING AT .5 PSIG | DUSTINS | DUSTINS | | HC | C | 6294851 |
MCNITT BROTHERS HEATING | HI | C | 08/09/2019 | 10 LB TEST OK. PIPING PER PLAN. TOTAL LOAD 1250 CFH. REGULATORS INSTALLED, QUICK DISCONNECTS AND RESTRAINTS INSTALLED. | DUSTINS | DUSTINS | | HI | C | 6294847 |
MCNITT BROTHERS HEATING | HD | P | 08/07/2019 | GREASE DUCT WRAP FIRST LAYER OK, OK FOR SECOND LAYER. SUPPLY AIR AND EXHAUST AIR ABOVE STORAGE 103 OK. | DUSTINS | DUSTINS | | HD | P | 6291485 |
MCNITT BROTHERS HEATING | HI | P | 08/06/2019 | 10 LB TEST OK. PIPING PER PLAN. TOTAL LOAD 1250 CFH. CHECK REGULATOR AND CONNECTIONS TO EQUIPMENT AT FINAL. | DUSTINS | DUSTINS | | HI | P | 6289826 |
MCNITT BROTHERS HEATING | HD | P | 08/06/2019 | GREASE DUCT LIGHT TEST ON SITE. NO HOLES FOUND IN EITHER GREASE DUCTS, OK TO WRAP WITH GREASE WRAP. | DUSTINS | DUSTINS | | HD | P | 6289804 |
MCNITT BROTHERS HEATING | HI | P | 08/05/2019 | NO TEST ON GAS PIPING. PIPING PER PLAN FOR KITCHEN. STILL NEED TO SEE ROOF GAS PIPING. | DUSTINS | DUSTINS | | HI | P | 6288003 |
MCNITT BROTHERS HEATING | HD | P | 08/05/2019 | GREASE DUCT LIGHT TEST ON SITE. FOUND FOUR HOLES IN SOUTH GREASE DUCT. TEN PLUS HOLES IN NORTH GREASE DUCT. STOPPED INSPECTION. RE-INSPECT ALL GREASE DUCT BUTT WELDS. | DUSTINS | DUSTINS | | HD | P | 6287996 |
MCNITT BROTHERS HEATING | HD | P | 08/02/2019 | TWO LAYERS OF GREASE WRAP OK ON TWO DUCT DROPS ONLY. STILL NEED TO SEE BUTT WELDS ON DROPS TO DUCTS AND CONNECTIONS TO HOOD. | DUSTINS | DUSTINS | | HD | P | 6286207 |
MCNITT BROTHERS HEATING | HD | P | 08/01/2019 | GREASE DUCT LIGHT TEST ON SITE. TWO DROPS OK TO INSULATE WITH TWO LAYERS AND DROP THROUGH CURB. FOUR PIECES OF DUCT SIGNED AND DATED OK, NEED TO SEE BUTT WELDS. | DUSTINS | DUSTINS | | HD | P | 6285279 |
MCNITT BROTHERS HEATING | HD | P | 07/30/2019 | NEED CONTRACTOR TO ADD EXHAUST FANS AND 2 COMMERCIAL DUCTS TO SCOPE OF WORK. HOOD WALL FREE OF COMBUSTIBLE MATERIAL. MAKE UP AIR DUCTS OK. ALL SUPPLY/RETURN AIR MAIN TRUNKS AND LATERALS OK EXCEPT MISSING SUPPLY AIR TO STORAGE 103. EXHAUST DUCTS PRE-EXISTING EXCEPT THE ON IN STORAGE 103 WAS RELOCATED AND NOT CONNECTED IN CEILING SPACE. NO ROOF TODAY. | DUSTINS | DUSTINS | | HD | P | 6281713 |
COLORADO COMMERCIAL REFRIGERATION, INC | HSP | P | 07/29/2019 | MECHANICAL EQUIPMENT ON ROOF WITHIN 10' OF ROOF EDGE WILL REQUIRE GUARD RAILS PER 2015 IMC 304.11 | DUSTINS | DUSTINS | | HSP | P | 6279334 |
COLORADO COMMERCIAL REFRIGERATION, INC | HRP | P | 07/26/2019 | NEED MECHANICAL CONTRACTOR TO ATTACH TO PERMIT. NEED GAS CONTRACTOR TO ATTACH TO PERMIT. NEED CONTRACTOR THAT INSTALLED WATER HEATER VENT TO ATTACH TO PERMIT AND CALL FOR INSPECTION. HOOD WALL WILL REQUIRE A MECHANICAL INSPECTION, PVC IN WALL AND HOOD IS NOT ZERO CLEARANCE AT REAR. TWO 325 LB TEST OK ON LINE SET FOR FREEZER AND COOLER. | DUSTINS | DUSTINS | | HRP | P | 6278178 |
CELTIC IRON PLUMBING LLC | P= | C | 08/16/2019 | engineers letter received and sent to scanning, rest ok | JOHNS | JOHNS | | P= | C | 6302970 |
CELTIC IRON PLUMBING LLC | PTO | C | 08/14/2019 | | JOHNS | JOHNS | | PTO | C | 6300454 |
CELTIC IRON PLUMBING LLC | PB | C | 08/14/2019 | | JOHNS | JOHNS | | PB | C | 6300443 |
CELTIC IRON PLUMBING LLC | P= | P | 08/14/2019 | **STILL TO TO REVISE PLANS addressing relocated hand sink, refer to previous PTO notes **STILL NEED ENGINEERS LETTER for deleting the floor sink by freezer, refer to PB notes
rest ok | JOHNS | JOHNS | | P= | P | 6300437 |
CELTIC IRON PLUMBING LLC | PTO | P | 07/30/2019 | **NEED TO REVISE PLANS to show kitchen north west hand sink has been relocated to kitchen north east wall w/ indirect waste to existing floor sink and the deletion of the floor sink for condensate by freezer, CAN COMPLETE ONCE REVISIONS ARE COMPLETE
**STILL NEED engineers letter allowing the deletion of floor sink for condensate by freezer, CAN COMPLETE PB ONCE ENGINEERS LETTER RECEIVED NOTE: engineers letter for material received and sent to scannIng
FOR PTO- PENDING REVISIONS. NOTE: vtr (existing), aav @ front west floor sink, aav @ mop sink (in room), aav @ front hand sink (under cab)
| JOHNS | JOHNS | | PTO | P | 6282268 |
CELTIC IRON PLUMBING LLC | PB | P | 07/05/2019 | need engineer letter for cellular core pvc, and for elimination of floor sink for condensate by freezer, test ok cover at own risk | JOSEPHD | JOSEPHD | | PB | P | 6254232 |
CELTIC IRON PLUMBING LLC | XPS | T | 08/15/2019 | PAID (REC#1622540): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Plumbing splice 8/15/19: Delta 4 revisions hand sink added, deleted floor sink for cooler condensate | SHANEN | SHANEN | | XPS | T | 6301546 |
COLORADO COMMERCIAL REFRIGERATION, INC | XMS | T | 07/26/2019 | PAID (REC#1617423): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouded revisions | DALEH | DALEH | | XMS | T | 6277867 |
TRAIL STAR DEVELOPMENT, LLC | XBS | T | 07/18/2019 | PAID (REC#1615201): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Clarify wall types | MICHAELA | MICHAELA | | XBS | T | 6267923 |