GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 06/29/2020 | | DAKOTAB | DAKOTAB | | B= | C | 6620429 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | C | 06/29/2020 | Items from previous inspection corrected | DAKOTAB | DAKOTAB | | BFR | C | 6620428 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 01/07/2020 | Need to firecaulk electrical conduits in equipment rooms 2566 at top of wall -- Need to firecaulk electrical penetrations in equipment room 2568 and on opposite side of wall in corridor 2563 -- Above lid for EVS 2565, Alcoves 2569 and 2570, equipment room 2571, and corridor 2563 other than what is noted OK -- Training with Justin | DAKOTAB | DAKOTAB | | BFR | P | 6445547 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/07/2020 | Training with PPRBD inspector Dakota B - I 2 occupancy - Smoke partitions and smoke barriers continuity - Fire partitions - Accessible elements - head of wall details - Membrane penetrations and through penetrations of fire barriers - smoke barriers and smoke partitions | JUSTINL | JUSTINL | | BSP | P | 6445535 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 12/19/2019 | Above lid penetrations and hard lid framing in O.R. 17 OK -- Discussed need to splice in O.R 6 into plans for new duct work being installed | DAKOTAB | DAKOTAB | | BFR | P | 6432464 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/27/2019 | Interior light gauge frame at O.R. 17 and room 2623 OK | DAKOTAB | DAKOTAB | | BFR | P | 6411704 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 11/15/2019 | Building final at O.R. 9, O.R. 12, Equipment rooms 2561 and 2556, Scrub alcove 2552C and 2552D, Hallway 2552 from grid line 5 to 8, corridor 2600 from grid line XC to XE, and elevator lobby 2602 OK pending other finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet, U.S.ENGINEERING CONSTRUCTION, LLC Mechanical Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | P | 6400793 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/14/2019 | Above lid at elevator lobby 2602 OK | DAKOTAB | DAKOTAB | | BFR | P | 6398882 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/08/2019 | Interior light gauge framing at anesthesia work room 2611 and equipment room 2621 OK | DAKOTAB | DAKOTAB | | BFR | P | 6393753 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/05/2019 | Interior light gauge framing at O.R 17 OK pending other roughs -- Interior light gauge frame in corridor 2577 at door 2577B OK -- Hard lid frame and above lid penetrations in O.R 16 OK | DAKOTAB | DAKOTAB | | BFR | P | 6388819 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 10/30/2019 | ABOVE LID -- All penetrations above lid and head of wall details at O.R. 9, O.R.12, Alcoves 2552C and 2552D, and corridor 2563 OK | DAKOTAB | DAKOTAB | | BFR | P | 6383658 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 10/25/2019 | Wall framing and hard lid frame at OR 16, equipment 2571, and alcove 2570 OK | DAKOTAB | DAKOTAB | | BFR | P | 6381162 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 10/14/2019 | Wall framing and hard lid framing at OR14,OR15 OK -- Wall framing at equipment rooms 2566,2568,2575 and EVS 2565 OK -- Reviewed rated walls per splice at 2611 and 2621 and inspection process | DAKOTAB | DAKOTAB | | BFR | P | 6367399 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 10/02/2019 | ABOVE LID INSPECTION -- Above lid inspection for drywall and penetrations at smoke partitions for O.R 9, O.R 12, Equipment rooms 2561 and 2556 OK -- Met with framing foreman to discuss upcoming inspection as well as phased project | DAKOTAB | DAKOTAB | | BSP | P | 6355178 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 09/25/2019 | partial framing for anesthesia room/equipment room/ vendor room/ framing is per plan | SCOTTS | SCOTTS | | BFR | P | 6347750 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 09/04/2019 | wall framing and hard lid framing complete for OR 9 | SCOTTS | SCOTTS | | BFR | P | 6323873 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 08/23/2019 | wall framing and hard lid framing for OR 9 complete -- partial framing for OR14/15/16 for walls and associated equipment rooms per plan | SCOTTS | SCOTTS | | BFR | P | 6312864 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 07/25/2019 | partial framing for OR 9/equipment room 2623 and 2621/anesthesia 2611/vendor 2606/OR 17 -- rear wall of common 3 not ready yet -- framing observed to be per plans and listings | SCOTTS | SCOTTS | | BFR | P | 6277531 |
ENCORE ELECTRIC, INC. | E= | C | 05/04/2020 | FIRE ALARM INSPECTION: | RANDY | RANDY | | E= | C | 6560430 |
ENCORE ELECTRIC, INC. | E= | C | 11/15/2019 | OR 9 and 12 | RANDY | RANDY | | E= | C | 6401447 |
ENCORE ELECTRIC, INC. | ER | P | 10/30/2019 | FIRE ALARM INSPECTION: FA with electric | RANDY | RANDY | | ER | P | 6383767 |
ENCORE ELECTRIC, INC. | ER | P | 10/30/2019 | OR 1 and 12 ceilings+corridors marked on plans | RANDY | RANDY | | ER | P | 6383766 |
ENCORE ELECTRIC, INC. | ER | P | 10/23/2019 | FIRE ALARM INSPECTION: field cancelled | RANDY | RANDY | | ER | P | 6378708 |
ENCORE ELECTRIC, INC. | ER | P | 10/23/2019 | field cancelled | RANDY | RANDY | | ER | P | 6378543 |
ENCORE ELECTRIC, INC. | ER | P | 09/10/2019 | SPD walls----OR 14 walls | RANDY | RANDY | | ER | P | 6330629 |
ENCORE ELECTRIC, INC. | ER | P | 09/04/2019 | OR 12 hard lid marked on plans | RANDY | RANDY | | ER | P | 6324249 |
ENCORE ELECTRIC, INC. | ER | P | 08/23/2019 | OR 9 hardlid marked on plans | RANDY | RANDY | | ER | P | 6312252 |
ENCORE ELECTRIC, INC. | ER | P | 07/31/2019 | OR 12 | RANDY | RANDY | | ER | P | 6283944 |
ENCORE ELECTRIC, INC. | ER | P | 07/23/2019 | 2nd fl OR room marked on plans | RANDY | RANDY | | ER | P | 6274149 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | C | 04/06/2020 | PHASE -1- MECHANICAL HEAT FINAL COMPLETE / ENGINEER STAMPED TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6531578 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 03/06/2020 | PHASE-1 : HYDRONIC HEAT FINAL COMPLETE. | LIDO | LIDO | | H= | C | 6502242 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 11/20/2019 | THIS INSPECTION WAS A RE-INSPECTION FROM 10-14-19. PLANS HAVE BEEN REVISED/APPROVED FOR NEW LOW PRESSURE STEAM AND LOW PRESSURE CONDENSATE FOR RTU-12. PIPING PER PLAN SPLICE. INSULATION AND LABELING OK. | DUSTINS | DUSTINS | | H= | P | 6406240 |
U.S. ENGINEERING CONSTRUCTION, LLC | HSP | P | 11/11/2019 | ((THE WRONG PERMIT WAS CALLED IN / NOTES FROM THIS INSPECTION TRANSFERRED TO PERMIT # M52955. 2ND FLOOR MH123 ( BDA 163) SPLICE DATED 11/1/19 : TWO DAMPERS COMPLETE / VAV 2-218 AND LOW PRESSURE DUCT ROUGH COMPLETE.)) | LIDO | LIDO | | HSP | P | 6395302 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 10/30/2019 | (HWP) PHASE -1 - PARTIAL PENDING: NEED REVISED AND APPROVED PLANS FOR NEW LOW PRESSURE STEAM, LOW PRESSURE CONDENSATE AND HUMIDIFIER INSTALLED FOR RTU-12 IN THE SUPPLY TRUNK LINE ))4TH FLOOR MP143 ( BDA 42) RTU-12 CHILLED WATER SUPPLY AND RETURN / HEAT HEAT WATER SUPPLY AND RETURN UNDER OPERATING PRESSURE ,NO VISIBLE LEAKS , OK TO WRAP AND LABEL / FINAL CONNECTION TO RTU-12 OK. | LIDO | LIDO | | H= | P | 6383994 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 10/24/2019 | ( HVAC) PHASE - 1 - PARTIAL HEAT FINAL PENDING- 4TH FLOOR PLAN PAGE M-143 ( BDA 39) NEED REVISED / APPROVED PLAN FOR ADDED HUMIDIFIER IN SUPPLY TRUNK LINE FROM RTU-12 / NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6379729 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 10/14/2019 | 4TH FLOOR MP-143 ( BDA 42) (( NEED REVISED AND APPROVED PLANS FOR NEW LOW PRESSURE STEAM AND LOW PRESSURE CONDENSATE INSTALLED FOR RTU-12 )) 100 LB TEST FOR LOW PRESSURE STEAM AND 100 LB TEST FOR LOW PRESSURE CONDENSATE OK. | LIDO | LIDO | | HWP | P | 6367776 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 10/10/2019 | 4TH FLOOR MP-143 ( BDA 42) NEED REVISED AND APPROVED PLANS FOR NEW LOW PRESSURE STEAM AND LOW PRESSURE CONDENSATE INSTALLED / STILL NEED AIR TEST. 100 LB TEST FOR CHILLED WATER SUPPLY AND RETURN OK / INSTALLED PER PLAN /OK TO WRAP AND LABEL. 90 LB TEST OK FOR HEAT WATER SUPPLY AND RETURN OK / INSTALLED PER PLAN / OK TO WRAP AND LABEL.
| LIDO | LIDO | | HWP | P | 6365234 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 10/08/2019 | (PHASE - 1 ) PARTIAL PENDING : NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6362276 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 10/03/2019 | (( PHASE-1 )) PHASE -1 PENDING : TOP OF THERMOSTATS IN (OR - 9) AND ( OR -12) TO BE INSTALLED 48" ABOVE FINISHED FLOOR. NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6356764 |
OLSON PLUMBING & HEATING COMPANY | HD | C | 10/03/2019 | ((PHASE - 1)) DUCT ROUGH FOR PHASE-1 ONLY COMPLETE. | LIDO | LIDO | | HD | C | 6356760 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 10/02/2019 | 2ND FLOOR SPLICE MH-123 ( BDA 139) : OR-9 AND OR-12 VISUAL AND DIGITAL PRESSURE MONITOR CONTROL BOX (NOTE# 2) IS INSTALLED IN A WORK SPACE. / INSTALL OK. | LIDO | LIDO | | HD | P | 6354743 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 09/30/2019 | 2ND FLOOR SPLICE MH-123 ( BDA 139) : OR-9 AND OR-12 NEED TO RESEARCH VISUAL AND DIGITAL PRESSURE MONITOR CONTROL BOX (NOTE# 2) FOR ACCESSIBILITY. INSTALL THERMOSTAT 48" ABOVE FINISHED FLOOR OR INSTALL LOCK BOX . SUPPLY AND RETURN GRILLS AND REGISTERS OK. PRESSURE SENSOR ( NOTE # 1) OK. | LIDO | LIDO | | HD | P | 6352783 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 09/26/2019 | 2ND FLOOR M123 ( BDA 139 ) SPLICE : NEED REVISED AND APPROVED SPLICE FOR THE FOLLOWING - RETURN AIR DUCT CHANGED FROM 16 " ROUND TO 14 X 14 AND TWO 12 " BRANCH LINES ROUTED TO CORRIDOR / VAV2-239 MOVED FROM CORRIDOR TO ROOM # 2573 / VAV2-236 MOVED FROM CORRIDOR TO ROOM # 2575. FIRE DAMPER FOR RETURN AIR ABOVE THE DOUBLE DOORS. DUCT ROUGH IN ROOM #2575 OK / OK TO WRAP. ( OR 16 ) DUCT ROUGH OK / OK TO WRAP. VAV 2-234 AND VAV 2-233 LOW PRESSURE DUCT OK / OK TO WRAP. 1- DAMPER COMPLETE. ((NEED TO HIGHLIGHT PLANS ON NEXT INSPECTION.))
| LIDO | LIDO | | HD | P | 6349793 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 09/24/2019 | 2ND FLOOR MH-123 ( BDA 125) TWO FIRE DAMPERS SHOWN ON PLANS ARE NOT BEING INSTALLED FOR 10" SUPPLY RUN TO EQUIPMENT ROOM 2566 / ENGINEER TO ADDRESS . VAV 2-237 - SUPPLY LOW PRESSURE DUCT ROUGH AND RETURN AIR DUCT ROUGH FOR (OR) 15 OK / OK TO WRAP. VAV-2-238 AND LOW PRESSURE SUPPLY DUCT ROUGH OK / OK TO WRAP . 6- FIRE DAMPERS COMPLETE. | LIDO | LIDO | | HD | P | 6346110 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 09/19/2019 | 2ND FLOOR MP123 ( BDA 126) NEED REVISED AND APPROVED PLANS FOR HEAT WATER SUPPLY AND RETURN ROUTING IN CORRIDOR CHANGED FOR VAV-2-238 , 2-239, 2-240 AND VAV - 2-239 MOVED HALL TO ROOM # 2573. TWO 100 lb TESTS FOR HEAT WATER SUPPLY AND RETURN OK FOR VAV - VAV-2-233, 2-234, 2-236, 2-237, 2-238 , 2-239, 2-240 / INSTALL OK OK TO WRAP AND LABEL. | LIDO | LIDO | | HWP | P | 6341584 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 09/11/2019 | 2ND FLOOR MH-123 ( BDA 125) VAV -2-240 : MEDIUM PRESSURE DUCT TO VAV AND VAV INSTALL OK / SUPPLY LOW PRESSURE AND RETURN DUCT ROUGH IN OR # 14 OK / OK TO WRAP. VAV2-237 : VAV INSTALLED , LOW PRESSURE DUCT STUBBED INTO OR # 15 OK / OK TO WRAP. 4TH FLOOR MH-143 ( BDA39)- SUPPLY AND RETURN DUCT ROUGH FOR AHU-12 OK / OK TO WRAP | LIDO | LIDO | | HD | P | 6331782 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 09/11/2019 | 2ND FLOOR M-123 ( BDA-126) 30 - lb TEST FOR LOW PRESSURE STEAM OK / INSTALLED PER PLAN / OK TO WRAP AND LABEL. | LIDO | LIDO | | HWP | P | 6331781 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 09/09/2019 | 2ND FLOOR MP-123 ( BDA 126) VAV-2-241 AND VAV-2-242 - HEAT WATER SUPPLY AND RETURN FINAL TIE-IN OK / UNDER OPERATING PRESSURE NO VISIBLE LEAKS / OK TO INSULATE AND LABEL. | LIDO | LIDO | | HWP | P | 6328360 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 09/04/2019 | 2ND FLOOR MH-123 ( BDA 125) NEED TO RESEARCH DAMPER FRAMING IN A SHAFT WALL ABOVE A DOOR. 2- DAMPERS COMPLETE. | LIDO | LIDO | | HD | P | 6324168 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/28/2019 | 2ND FLOOR ( BDA 125) MH-123 : 7- DAMPER FRAMES OK. | LIDO | LIDO | | HD | P | 6317738 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/26/2019 | 2ND FLOOR ( BDA 125) MH-123 : 2- DAMPERS COMPLETE. 3- DAMPER FRAMES OK. | LIDO | LIDO | | HD | P | 6314190 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/21/2019 | 4TH FLOOR ( BDA 39) MH143 - 3- FIRE SMOKE DAMPERS COMPLETE AT SHAFT. | LIDO | LIDO | | HD | P | 6309186 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/16/2019 | 2ND FLOOR ( BDA125) MH-123 -ROOM EAST OF ELEVATOR # 13 : 42 X 26 RETURN AIR TRUNK LINE OK / OK TO WRAP. | LIDO | LIDO | | HD | P | 6303665 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/13/2019 | 2ND FLOOR ( BDA-125) MH-123: OR # 9 AND OR #12 - ALL ABOVE CEILING DUCT ROUGH AND DUCT ROUGH IN CHASE OK / OK TO WRAP. | LIDO | LIDO | | HD | P | 6298714 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/12/2019 | MULTIPLE CHANGES TO FIRE DAMPER LOCATION, TYPE OF FIRE DAMPER, ELIMINATED FIRE DAMPERS AND DUCT DESIGN - BEFORE THESE AREAS CAN BE INSPECTED, REVISED AND APPROVED PLANS WILL BE REQUIRED FOR ALL CHANGES. 2ND FLOOR ( SPLICE DATED 6/5/19 / BDA 125 ) MH-123 ROOM # 2606 - 1 FIRE DAMPER ELIMINATED FOR 14 X 14 EXHAUST DUCT , 1 FIRE DAMPER ELIMINATED FOR VAV 2-217 - NEED REVISED AND APPROVED SPLICE. 3- FIRE DAMPER FRAMES OK. 4TH FLOOR (BDA 39) MH-143) RTU-14 - RETURN AIR FIRE SMOKE DAMPER AT SHAFT COMPLETE / PARTIAL RETURN AIR DUCT ROUGH OK, OK TO WRAP. RTU-12 - SUPPLY AIR BREAK AWAY CONNECTION TO EXISTING FIRE SMOKE DAMPER AT SHAFT OK / PARTIAL SUPPLY DUCT ROUGH OK , OK TO WRAP. OUTSIDE AIR PARTIAL DUCT ROUGH OK, OK TO WRAP.,. | LIDO | LIDO | | HD | P | 6297025 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/06/2019 | 2ND FLOOR ( BDA -125) MH123 : 9 - FIRE DAMPER FRAMES OK / HIGHLIGHTED IN BLUE ON APPROVED PLANS ON FOURTH FLOOR. | LIDO | LIDO | | HD | P | 6290215 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/02/2019 | NEED TO RESEARCH WALL TO OR# 9 FOR RATING . 2ND FLOOR SPLICE MH-123 ( BDA 123) VAV-2-242 AND VAV2-241 AND MEDIUM PRESSURE DUCT AND LOW PRESSURE DUCT OK / OK TO WRAP .OR#9 -SUPPLY , RETURN AND RETURN AIR DUCT DROPS IN EACH CORNER OF OR# 9 ROOM OK / OK TO WRAP . SUPPLY BRANCH LINES OK / OK TO WRAP . | LIDO | LIDO | | HD | P | 6286657 |
OLSON PLUMBING & HEATING COMPANY | HSP | P | 08/02/2019 | WALL RATING FOR (OR #9 ) HAS CHANGED / FIRE DAMPER IS NO LONGER REQUIRED. | LIDO | LIDO | | HSP | P | 6291016 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 07/30/2019 | 2ND FLOOR ( BDA125) MH123 - NEED REVISED AND APPROVED PLANS FOR ALL DUCT DESIGN CHANGES, DAMPER LOCATION CHANGES AND TYPE OF DAMPER CHANGES . 1- FIRE DAMPER LOCATION MOVED FROM HALL WALL TO ELEVATOR LOBBY WALL AND CHANGED TO FIRE SMOKE DAMPER / STILL NEED TO INSPECT DAMPER / FRAMING . DUCT ROUGH HIGHLIGHTED IN YELLOW AND RED ON STAMPED PLANS LOCATED ON 4TH FLOOR / OK TO INSULATE.. | LIDO | LIDO | | HD | P | 6281798 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/29/2019 | 2ND FLOOR ( BDA 126 ) PLAN PAGE MP-123 .LOW PRESSURE STEAM IS NOT INSTALLED PER PLAN FOR H2-14 / NEED REVISE AND APPROVED PLANS TO MATCH INSTALL MARKED ON STAMPED SET ON 4TH FLOOR . 30 lb TEST FOR LOW PRESSURE CONDENSATE FOR VAV TB2-106 AND H2-14 OK / OK TO INSULATE AND LABEL. HEAT WATER SUPPLY AND RETURN FOR VAV 2-31 AND 2-32 UNDER OPERATING PRESSURE NO VISIBLE LEAKS / OK TO INSULATE AND LABEL.
| LIDO | LIDO | | HWP | P | 6280989 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/24/2019 | 2ND FLOOR (BDA126) MP-123 :NEED REVISED AND APPROVED PLANS FOR ADDED VAV-2-47 , VAV2-48 AND HYDRONIC PIPING. 30 lb TEST FOR LOW PRESSURE STEAM OK / PIPE INSTALLED PER PLAN OK TO WRAP AND LABEL. 75 lb TEST FOR LOW PRESSURE CONDENSATE OK / PIPE INSTALLED PER PLAN / OK TO WRAP AND LABEL. STEAM PIPE STUBS INSTALLED FOR H-2-15 AND H-2-19 / STILL NEED FINAL CONNECTIONS.(( HIGHLIGHTED PLANS IN OFFICE ON 4TH FLOOR .)) | LIDO | LIDO | | HWP | P | 6275744 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 07/16/2019 | DUCT DESIGN CHANGES, ADDED OR DELETED SMOKE DAMPERS, FIRE DAMPERS AND FIRE SMOKE DAMPERS WILL REQUIRE A REVISED AND APPROVED SPLICE
| LIDO | LIDO | | HD | P | 6266002 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 07/16/2019 | 2ND FLOOR ( BDA 125 ) MH-123 :NEED REVISED / APPROVED SPLICE FOR 1 - ADDED FIRE SMOKE DAMPER IN WALL FOR ELEVATOR LOBBY # 2602 . 6 - DAMPER FRAMES OK . | LIDO | LIDO | | HD | P | 6265831 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 07/12/2019 | 2nd FLOOR (BDA125) MH-123 : SUPPLY MAIN TRUNK LINE DUCT ROUGH DOWN CORRIDOR AND THROUGH ELEVATOR LOBBY # 2002 OK/ OK TO WRAP. ((Note added 8/19/19 by LM. This inspection comment was copied to permit M35724 by me on 8/19/19. Wrong permit called in by contractor. This comment is not for this permit. 5- DAMPER FRAMES BY ELEVATOR OK .)) | LIDO | LIDO | | HD | P | 6262112 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 10/30/2019 | phase 1 scrub sinks | TED | TED | | P= | C | 6384035 |
OLSON PLUMBING & HEATING COMPANY | P= | P | 10/03/2019 | equipment rooms 2561 and 2556 ok | TED | TED | | P= | P | 6356707 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 10/03/2019 | evs room 2565- dwv and water in walls, ceiling and below floor ok, scrub sinks 2620b and 2577a dwv and water in walls and ceiling ok, (some scrub sinks roughed in addition permit), water mains piping over head o/r rooms 14 through 16 ok | TED | TED | | PTO | P | 6356695 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 09/19/2019 | dwv and water in walls and ceiling equipment rooms 2573 and 2575, scrub sinks in hall alcoves 2577b | TED | TED | | PTO | P | 6341110 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 09/11/2019 | dwv and water in walls and ceiling room 2604, water piping in hallways over head from 2604 to existing O.R. | TED | TED | | PTO | P | 6331497 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 08/15/2019 | OR 17, OR 14, equipment room sink, dwv in 1st floor ceiling and wall ok | TED | TED | | PTO | P | 6302382 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 08/02/2019 | 2nd floor O.R. build out, service and mop sink, (plan marked) note: some of the stub sinks where roughed in under the addition permit and will be completed under this permit | TED | TED | | PTO | P | 6286969 |
OLSON PLUMBING & HEATING COMPANY | XMS | T | 09/04/2019 | PAID (REC#1628802) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Duct layout and backgrounds revised to match (A) sheet revisions and as-built conditions. | JUSTINC | JUSTINC | | XMS | T | 6322993 |
ENCORE ELECTRIC, INC. | XES | P | 09/03/2019 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Revised background | SHELBY | SHELBY | | XES | P | 6322696 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 08/30/2019 | PAID (REC#1627029) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise and rate equipment rooms - anesthesia room | MICHAELA | MICHAELA | | XBS | T | 6320671 |
ENCORE ELECTRIC, INC. | XES | P | 08/28/2019 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: No scope of work change. Sheet EP123C was issued for background update only. | BERTHA | BERTHA | | XES | P | 6316752 |
OLSON PLUMBING & HEATING COMPANY | XPS | P | 08/21/2019 | PLAN SPLICE FEE: $0 by: SHANEN for Plumbing: Plumbing splice 8/21/19: Delta ASI-11 revisions page PG123 background update | SHANEN | SHANEN | | XPS | P | 6308392 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 08/21/2019 | PAID (REC#1624517) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise wall construction | MICHAELA | MICHAELA | | XBS | T | 6308271 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XPS | T | 07/10/2019 | PAID (REC#1616725) PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Plumbing splice 7/10/19: Delta 6 revisions PG123 key note 4, PP113 reroute waste piping to MSB-1 & S-1 removed 2" waste up to S-2, PP123 removed water piping to S-2 reroute piping to L-4 & MSB-1, P600 adjusted fixture schedule | SHANEN | SHANEN | | XPS | T | 6259345 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XES | T | 07/10/2019 | PAID (REC#1616725) PLAN SPLICE FEE: $79.17 by: BERTHA for Electrical: Revised panels, power and lighting. | BERTHA | BERTHA | | XES | T | 6258666 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XMS | P | 07/05/2019 | PLAN SPLICE FEE: $0 by: JUSTINC for Mechanical: Minor layout revisions, Humidifiers, Schedule revisions | JUSTINC | JUSTINC | | XMS | P | 6253894 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 07/03/2019 | PAID (REC#1616725) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add fired walls - revise wall types | MICHAELA | MICHAELA | | XBS | T | 6253148 |