HAYS CONSTRUCTION COMPANY, INC. | B= | C | 09/26/2019 | items corrected | DANE | DANE | | B= | C | 6348802 |
HAYS CONSTRUCTION COMPANY, INC. | B= | P | 09/17/2019 | need to post address / women's restroom is the only restroom in the scope of work - women's toilet is more than 18" from wall to center line - mirror is higher than 40 " to the reflective surface in the women's restroom - missing knee protection at the sink in the women's restroom / need to install restroom sign at women's restroom / need to complete all other finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), COOLING CUBED, LLC. Mechanical Final Inspection is not Completed yet, CSP PLUMBING SERVICES Plumbing Final Inspection is not Completed yet, MECHANICAL RESOURCES LLC Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 6338534 |
HAYS CONSTRUCTION COMPANY, INC. | BFR | P | 08/23/2019 | met contractor on site and discussed accessible elements / no above ceiling inspection required for non-rated and acoustical tile ceilings / no new framing / framing still OK pending other roughs | DANE | DANE | | BFR | P | 6312010 |
HAYS CONSTRUCTION COMPANY, INC. | BFR | P | 08/06/2019 | new interior wood framing OK pending other roughs / need to attach mechanical permit and have inspections / discussed accessible elements with contractor including accessible elements for the west restroom that is being reconfigured - need flush valve on open side and sink no higher than 34" and mirror no higher than 40" to the rflective surface | DANE | DANE | | BFR | P | 6289710 |
COLORADO ELECTRICAL SERVICES INC | E= | C | 09/16/2019 | Interior remodel complete | CHIPO | CHIPO | | E= | C | 6336871 |
COLORADO ELECTRICAL SERVICES INC | ER | P | 08/29/2019 | 1) trench to pre-menue board ok, 2) ceilings ok thru out EXISTING RTU's | GARYL | GARYL | | ER | P | 6318522 |
COLORADO ELECTRICAL SERVICES INC | ER | P | 07/30/2019 | All new walls okay, several existing with cut-in boxes,, all mc cable ,,, NOTE!! it's the old taco Buenos restaurant , now Dutch bros coffee, CAN NOT ENTER JOB SITE FROM ACADEMY | GARYL | GARYL | | ER | P | 6281911 |
MECHANICAL RESOURCES LLC | H= | C | 09/26/2019 | REVISED TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6348245 |
MECHANICAL RESOURCES LLC | H= | P | 09/19/2019 | TEST AND BALANCE REPORT REVIEW : RTU-2 IS SHOWING THE READINGS FOR THE # 5 AND # 6 SUPPLY AIR GRILLS IN THE MEN'S AND WOMEN'S RESTROOMS , PLANS SHOW THESE SUPPLY RUNS OFF RTU-1 AND THE READINGS FOR THESE TWO SUPPLY GRILLS ARE OUTSIDE THE ALLOWED 10% . NEED REVISED TEST AND BALANCE REPORT.
| LIDO | LIDO | | H= | P | 6340444 |
ALNOR INC. | H= | C | 09/18/2019 | HEAT FINAL OK.
| LIDO | LIDO | | H= | C | 6339125 |
MECHANICAL RESOURCES LLC | H= | P | 09/18/2019 | TEST AND BALANCE REPORT IS BEING REVIEWED. CORRECTION MADE ( SEE IMAGES ) | LIDO | LIDO | | H= | P | 6339009 |
MECHANICAL RESOURCES LLC | HD | C | 09/09/2019 | PARTIAL PENDING: NEED TO RESEARCH AIR CURTAIN PULLING AIR FROM ABOVE A DROP CEILING. MISSING TRANSFER AIR FOR STORAGE ROOM. RTU-1 AND RTU-2 TOP OF THERMOSTAT IS INSTALL OVER 48" ABOVE FINISHED FLOOR. MISSING TEMPERATURE SENSOR FOR RTU-1. NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | HD | C | 6329055 |
MECHANICAL RESOURCES LLC | HC | C | 08/23/2019 | METER RELEASE OK / GAS LOAD NOW IS 559K | LIDO | LIDO | | HC | C | 6311783 |
MECHANICAL RESOURCES LLC | HI | P | 08/23/2019 | AFTER FURTHER REVIEW DEMO SPLICE IS NOT REQUIRED AND GAS DOES NOT NEED TO BE ADDED TO THE SCOPE OF WORK .REFRIGERATION CONTRACTOR NEEDS TO ATTACH TO PERMIT. | LIDO | LIDO | | HI | P | 6311767 |
MECHANICAL RESOURCES LLC | HI | P | 08/22/2019 | NEED CONSULT WITH PLAN REVIEW TO DETERMINE IF GAS DEMO REQUIRES A SPLICE / WILL ADD TO NOTES AFTER . CONTRACTOR TO ADD GAS TO THERE SCOPE OF WORK. REFRIGERATION CONTRACTOR NEEDS TO ATTACH TO PERMIT. (10 lb TEST OK .) | LIDO | LIDO | | HI | P | 6311457 |
CSP PLUMBING SERVICES, LLC | P= | C | 09/24/2019 | Corrections made. | SAMH | SAMH | | P= | C | 6345515 |
CSP PLUMBING SERVICES, LLC | P= | P | 09/16/2019 | Complete insulation in ceiling. Rest ok. Photo ok to complete. | SAMH | SAMH | | P= | P | 6336878 |
CSP PLUMBING SERVICES, LLC | PTO | C | 09/16/2019 | Splice for water pipe size approved. | SAMH | SAMH | | PTO | C | 6336877 |
CSP PLUMBING SERVICES, LLC | PB | C | 09/16/2019 | Cellular core pvc, and Combination waste and vent approved by engineer. See images. | SAMH | SAMH | | PB | C | 6336865 |
CSP PLUMBING SERVICES, LLC | PB | P | 08/30/2019 | Added p4 and p5 sinks. Still need engineers letter for cellular core pipe, and combination waste and vent at floor sinks. | SAMH | SAMH | | PB | P | 6320989 |
CSP PLUMBING SERVICES, LLC | PTO | P | 08/14/2019 | Need to add splice for change in water pipe sizing. Rest OK. | SAMH | SAMH | | PTO | P | 6300525 |
CSP PLUMBING SERVICES, LLC | PTO | P | 08/06/2019 | Re-size CW at south wall and rapid rinse sink per drawing. Re-size FW and CW at service area per drawing. ( Need engineers sizing for in wall FW at service area. ). Verify insulation and filter rack. DWV ok. | SAMH | SAMH | | PTO | P | 6290803 |
CSP PLUMBING SERVICES, LLC | PB | P | 07/19/2019 | Need engineers approval for cellular core pvc, and combination waste and vent at floor sinks. Cover at own risk. | SAMH | SAMH | | PB | P | 6269993 |
CSP PLUMBING SERVICES, LLC | PB | P | 07/18/2019 | Complete floor sink rough in by EQ-9, Need approval for cellular core PVC underground, Need engineers approval for 4" combination waste and vent at floor sink by EQ-4. Cover at own risk. | SAMH | SAMH | | PB | P | 6269222 |
HAYS CONSTRUCTION COMPANY, INC. | XBS | P | 08/22/2019 | PLAN SPLICE: (No Fee) by: DANM for Construction: Minor revisions to architectural dwgs including adding a door | DANM | DANM | | XBS | P | 6311296 |
CSP PLUMBING SERVICES, LLC | XPS | T | 08/22/2019 | PAID (REC#1624526) PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Plumbing splice 8/22/19: Delta 11 revisions P1.0 adjusted fixture schedule and sanitary sizing calculations, P2.0 added P-4, P-5 and piping, P4.0 adjusted sanitary isometric | SHANEN | SHANEN | | XPS | T | 6311261 |