ELDER-JONES, INC. | B= | C | 11/22/2019 | All other required Final inspections are complete. (This is a computer generated result) | LONNYS | LONNYS | | B= | C | 6407982 |
ELDER-JONES, INC. | B= | P | 11/14/2019 | building final OK pending other required inspections / complete E= and H=. Additional Inspections Required (computer generated): EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, MAGNUM EDGE,INC. Mechanical Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 6400012 |
ELDER-JONES, INC. | BFR | P | 11/01/2019 | above grid ok/reviewed accessibility and final inspection request process | SCOTTS | SCOTTS | | BFR | P | 6385841 |
ELDER-JONES, INC. | BFR | P | 09/13/2019 | need to attach mech to permit, pending completion of other required inspections, interior framing okay | BOBF | BOBF | | BFR | P | 6335131 |
EL PASO ELECTRIC, LLC. | E= | C | 11/15/2019 | complete / | MIGUEL | MIGUEL | | E= | C | 6400596 |
EL PASO ELECTRIC, LLC. | EP | C | 11/08/2019 | New panel fed from existing disconnect okay / new 200 amp fuses in disconnect okay / other disconnect with fuses removed and in locked off position okay | CHIPO | CHIPO | | EP | C | 6392912 |
EL PASO ELECTRIC, LLC. | E= | R | 10/31/2019 | No ready for final | JOSEPH | JOSEPH | | E= | R | 6384521 |
EL PASO ELECTRIC, LLC. | ER | P | 10/31/2019 | Drop ceilings ok except leave out ceiling tiles along exterior wall in order to verify addition of 7 lockable disconnects for signs. / Still need to have inspection for power distribution / | JOSEPH | JOSEPH | | ER | P | 6384515 |
EL PASO ELECTRIC, LLC. | EUG | C | 10/28/2019 | EUG to free standing sign okay--all EUG complete | CHIPO | CHIPO | | EUG | C | 6381690 |
EL PASO ELECTRIC, LLC. | EUG | P | 10/03/2019 | 1- 3/4" pvc for sign on NE corner of building just past sidewalk / | MIGUEL | MIGUEL | | EUG | P | 6356242 |
EL PASO ELECTRIC, LLC. | ESL | P | 09/12/2019 | 3/4" pvc to floor boxes in sales area and cashier area marked on plans | CRAIG | CRAIG | | ESL | P | 6333356 |
EL PASO ELECTRIC, LLC. | ER | P | 09/12/2019 | walls / hard lid ceiling ok marked on plans Discussed accessibility requirements with contractor / | CRAIG | CRAIG | | ER | P | 6333354 |
MAGNUM EDGE,INC. | H= | C | 11/22/2019 | TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | H= | C | 6407981 |
MAGNUM EDGE,INC. | H= | P | 11/14/2019 | FINAL PENDING - Provide a good test and balance report for review | MARKB | MARKB | | H= | P | 6399565 |
MAGNUM EDGE,INC. | HSP | R | 11/14/2019 | Test and balance report provided - RTU-1 outside air and EF-1 values not within 10% of approved plans | MARKB | MARKB | | HSP | R | 6398844 |
MAGNUM EDGE,INC. | H= | L | 11/13/2019 | No access - painting parking lot. | MARKB | MARKB | | H= | L | 6397429 |
MAGNUM EDGE,INC. | HD | C | 10/30/2019 | FOR FINAL - Install remote indicator for smoke shutdown and provide test and balance report for review. ALL FLEX, DIFFUSERS, TRANSFER OPENINGS AND EXHAUST COMPLETE. SMOKE DUCT DETECTOR FOR RTU-3 CONFIRMED. | MARKB | MARKB | | HD | C | 6383784 |
MAGNUM EDGE,INC. | HD | P | 10/11/2019 | ABOVE CEILING DUCT - SUPPLY/RETURN/EXHAUST, MAINS/BRANCHES/FLEX INSTALL PER PLAN SPLICE OK TO WRAP EXCEPT: Missing exhaust in room 105 (storage). | MARKB | MARKB | | HD | P | 6365588 |
MAGNUM EDGE,INC. | HD | R | 10/09/2019 | All trunk duct for all RTU'S installed is ran different with different sizes than approved plans. Stopped inspection - no approved mechanical splice on file at this time. | MARKB | MARKB | | HD | R | 6363101 |
MAGNUM EDGE,INC. | HD | P | 09/30/2019 | NEED TO RESEARCH IF THERE ARE ANY DEMISING WALL PENETRATIONS. STILL NEED RTU-2 SYSTEM AND DUCT ABOVE ALL HARD-LIDS INSPECTED. MISSING ALL TRANSFER AIR OPENINGS IN THE WALL SHOWN ON PLANS BELOW CEILING THROUGH OUT BUILDING. STILL NEED ROOF. RTU-1 : MISSING 8" SUPPLY AIR BRANCH AND 6" EXHAUST AIR BRANCH IN ROOM # 105. RTU-3 PLANS SHOW 24 X 24 SUPPLY AIR TRUNK LINE TO BE INSTALL 24 X 18 INSTALLED / INSTALL PER PLAN OR REVISED AND APPROVED PLANS ARE REQUIRED . PLANS SHOW 24 X 24 RETURN AIR TRUNK LINE TO BE INSTALL 26 X 18 INSTALLED / INSTALL PER PLAN OR REVISED AND APPROVED PLANS ARE REQUIRED . MISSING 1- 8" SUPPLY AIR RUN IN ROOM # 101. | LIDO | LIDO | | HD | P | 6352109 |
DRUMMOND PLUMBING LLC | P= | C | 10/30/2019 | Ok. | DANR | DANR | | P= | C | 6383604 |
DRUMMOND PLUMBING LLC | PTO | C | 09/19/2019 | Ok. Note: by final need engineer letter for no recirc line.check water heater - backflow at final - overhead insulation at final.. | DANR | DANR | | PTO | C | 6341310 |
DRUMMOND PLUMBING LLC | PB | C | 09/16/2019 | See plan splice 9/13/2019. | DANR | DANR | | PB | C | 6335704 |
DRUMMOND PLUMBING LLC | PTO | P | 09/13/2019 | In wall DWV and domestic water break room wall - mop sink wall - drinking fountain wall: Ok to insulate domestic hot, rest ok in wall these areas. Note: need plan splice water piping move underground and backflow location. | DANR | DANR | | PTO | P | 6334347 |
DRUMMOND PLUMBING LLC | PB | P | 09/13/2019 | Need plans splice showing backflow and piping relocation for domestic water, cover at own risk. | DANR | DANR | | PB | P | 6333978 |
DRUMMOND PLUMBING LLC | PB | P | 09/10/2019 | Need plans splice showing backflow and piping relocation for domestic water, CSU inspects water before water entry backflow, DWV ok. | DANR | DANR | | PB | P | 6329921 |
MAGNUM EDGE,INC. | XMS | T | 10/10/2019 | PAID (REC#1636422) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouds | DALEH | DALEH | | XMS | T | 6364157 |
DRUMMOND PLUMBING LLC | XPS | T | 09/13/2019 | PAID (REC#1629950): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: 9/13/19: Delta 3 revisions P1.1 added building and irrigation back-flow preventer. | SHANEN | SHANEN | | XPS | T | 6335157 |