WESTEC CONSTRUCTION MANAGEMENT COMPANY | B= | C | 12/03/2019 | All other required Final inspections are complete. (This is a computer generated result) | BRIANB | BRIANB | | B= | C | 6413852 |
WESTEC CONSTRUCTION MANAGEMENT COMPANY | B= | P | 11/19/2019 | pending other final inspections. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet, COMFORT CONTROL, INC. Mechanical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 6403447 |
WESTEC CONSTRUCTION MANAGEMENT COMPANY | BFR | P | 11/19/2019 | letter for framing modifications on file | BRIANB | BRIANB | | BFR | P | 6403446 |
WESTEC CONSTRUCTION MANAGEMENT COMPANY | B= | P | 11/13/2019 | pending completed frame inspection and other final inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, COMFORT CONTROL, INC. Mechanical Final Inspection is not Completed yet, TICE ELECTRIC, LLC Electrical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 6397680 |
WESTEC CONSTRUCTION MANAGEMENT COMPANY | BFR | P | 11/13/2019 | missing address on stamped letter for hard lid and framing modifications / pending other rough inspections | BRIANB | BRIANB | | BFR | P | 6397649 |
WESTEC CONSTRUCTION MANAGEMENT COMPANY | BFR | P | 10/10/2019 | PARTIAL - HARD LID FRAME / missing engineering stamp on letter for hard lid framing details / observed mtl hard lid framing - still need to pick up stamped letter / pending other rough inspections / still need to address other items noted from previous frame inspection | BRIANB | BRIANB | | BFR | P | 6364361 |
WESTEC CONSTRUCTION MANAGEMENT COMPANY | BFR | P | 10/08/2019 | observed light gauge mtl. wall framing - need engineering letter for substitution of wood studs listed on the approved design / still need to inspect hard lid framing - need details for hard lid framing not found on the approved design / will need plan splice completed if removing reinforcing for bar joist from scope of permit for new RTUs / pending other rough inspections - including mechanical inspections for hood wall / reviewed accessible elements | BRIANB | BRIANB | | BFR | P | 6361535 |
TICE ELECTRIC, LLC | E= | C | 11/15/2019 | E= OK ------ | GREGM | GREGM | | E= | C | 6400440 |
TICE ELECTRIC, LLC | E= | P | 11/13/2019 | MAKE GFCI ACCESSIBLE AT HOOD ------- | GREGM | GREGM | | E= | P | 6397780 |
TICE ELECTRIC, LLC | ER | C | 11/13/2019 | ER OK ------ | GREGM | GREGM | | ER | C | 6397779 |
TICE ELECTRIC, LLC | ER | R | 10/23/2019 | exit lights need wired back to the structure ----- a/c cable off the grid by hall to the rest rooms --- low voltage of the grid multiple places ---- track lights needs supported back to the structure every 4' --- sections 4' and less need two back to the structure nec 410.154 | CRAIGS | CRAIGS | | ER | R | 6377676 |
TICE ELECTRIC, LLC | ER | P | 10/11/2019 | ER PARTIAL WALLS AND HARD LID ------- | GREGM | GREGM | | ER | P | 6365689 |
COMFORT CONTROL, INC. | H= | C | 12/03/2019 | HEAT FINAL OK. RECEIVED STAMPED ENGINEER LETTER APPROVING THE TEST AND BALANCE REPORT READINGS ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6413851 |
COMFORT CONTROL, INC. | H= | P | 12/03/2019 | KITCHEN HOOD AND EQUIPMENT INTERLOCKS OK. PARTIAL PENDING : REVISED TEST AND BALANCE REPORT OR ENGINEER STAMPED LETTER APPROVING THE READINGS. . | LIDO | LIDO | | H= | P | 6413681 |
COMFORT CONTROL, INC. | HD | P | 11/25/2019 | UPDATED 11-27-19 DS: STILL NEED TO SEE RTU FLUE SNORKEL EXTENSION. // RECEIVED LETTER FROM ENGINEER STATING RTU- 1 AND 2 ARE RUNNING CONSTANTLY FOR MAKE UP AIR TO KITCHEN. WILL SCAN ONTO PERMIT IN THE MORNING. MECHANICAL FINAL PENDING: REVISED TEST AND BALANCE REPORT. NEED TO VERIFY KITCHEN INTERLOCKS. | DUSTINS | DUSTINS | | HD | P | 6409925 |
COMFORT CONTROL, INC. | HD | P | 11/25/2019 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. READINGS FOR RTU-1 AND RTU-2 RETURN AIR ARE OUTSIDE +/- 10% ALLOWABLE READINGS. NEED REVISED TEST AND BALANCE REPORT OR ENGINEER APPROVAL OF READINGS. | DUSTINS | DUSTINS | | HD | P | 6409244 |
COMFORT CONTROL, INC. | HD | P | 11/13/2019 | CHANGED TO ( HD). NEED SPLICE PREVIOUSLY NOTED .KITCHEN HOOD INTERLOCKS NOT READY. THERMOSTATS NOT READY. RTU FLUE SNORKEL EXTENSION NOT INSTALLED. NEED TEST AND BALANCE REPORT. ((METAL AROUND HOOD ALL DIRECTIONS OK. GREASE DUCT WRAP OK. KITCHEN GREASE EXHAUST FAN ON ROOF OK )) | LIDO | LIDO | | HD | P | 6398580 |
RESCUE MECHANICAL, INC. | H= | C | 11/12/2019 | GAS HEAT FINAL OK . | LIDO | LIDO | | H= | C | 6396394 |
COMFORT CONTROL, INC. | HD | P | 11/04/2019 | EXISTING RTU-1 AND RTU-2 ARE NOT BEING CHANGED OUT WITH NEW ROOF TOP UNITS / PROVIDE REVISED AND APPROVED MECHANICAL SCHEDULE AND PLANS TO REFLECT THIS .GREASE DUCT ACCESS DOOR INSULATION IS NOT APPLIED PER THE INSTALLATION INSTRUCTIONS - WENT OVER WITH CONTRACTOR / NEED TO RE-INSPECT. SUPPLY / RETURN AND EXHAUST ABOVE CEILING FINAL COMPLETE. STILL NEED ROOF FINAL , KITCHEN HOOD AND EQUIPMENT INTERLOCKS / NEED TO VERIFY ALL THERMOSTATS AND CO SENSORS .NEED TEST AND BALANCE REPORT . | LIDO | LIDO | | HD | P | 6387991 |
RESCUE MECHANICAL, INC. | H= | P | 11/01/2019 | PARTIAL PENDING : NEED REVISED PLANS FOR GAS INSTALL CHANGES - (SEE PREVIOUS NOTES.) | LIDO | LIDO | | H= | P | 6386224 |
RESCUE MECHANICAL, INC. | HI | C | 11/01/2019 | INSPECTED THE FOLLOWING ON 10/31/19 -ANSUL VALVE INSTALLED / FINAL GAS CONNECTION TO DUEL FRYER OK / RESTRAINTS IN PLACE . | LIDO | LIDO | | HI | C | 6386223 |
COMFORT CONTROL, INC. | HD | P | 10/31/2019 | EXISTING RTU-1 AND RTU-2 ARE NO BEING CHANGED OUT WITH NEW ROOF TOP UNITS / PROVIDE REVISED AND APPROVED MECHANICAL SCHEDULE AND PLANS TO REFLECT THIS . RTU-1 FLUE VENT IS LESS THAN 10 FEET FROM RTU -2 FRESH AIR INTAKE / INSTALL FACTORY FLUE SNORKEL EXTENSION. STILL NEED ROOF EQUIPMENT INSPECTION WHEN COMPLETED. GREASE DUCT LIGHT TEST : ALL GREASE DUCT INSTALL OK / OK TO WRAP . PROVIDE PICTURES OF THE 1ST LAYER OF FIRE WRAP AT SECOND LAYER INSPECTION. | LIDO | LIDO | | HD | P | 6385103 |
COMFORT CONTROL, INC. | HD | P | 10/30/2019 | GREASE DUCT LIGHT TEST: THE TWO HOLES WELDED / OK TO APPLY 1ST LAYER AND SECOND LAYER OF GREASE DUCT WRAP FROM HOOD UP TO VERTICAL DUCT SUPPORT/ CONTRACTOR TO PROVIDE PICTURES OF 1ST LAYER OF WRAP AND INSTALLATION INSTRUCTIONS AT 2ND LAYER WRAP INSPECTION. STILL NEED GREASE DUCT DROP WELDED TO VERTICAL GREASE DUCT. | LIDO | LIDO | | HD | P | 6384146 |
RESCUE MECHANICAL, INC. | HI | P | 10/30/2019 | ONE 1" GAS OUTLET TO 1 - DUEL FRYER OFF 1-1/4" GAS LINE INSTALLED / ISOMETRIC AND NOTE 3 SHOWS A DIFFERENT INSTALL / INSTALL PER PLAN OR A REVISED AND APPROVED GAS PLAN IS REQUIRED. 10" LB TEST OK. 1-1/4"GAS INSTALLED TO COOK-LINE OK. | LIDO | LIDO | | HI | P | 6384133 |
COMFORT CONTROL, INC. | HD | P | 10/30/2019 | TYPE -1 KITCHEN HOOD REQUIRES 18" OF SMOOTH, CLEANABLE, NON ABSORBENT AND NON COMBUSTIBLE MATERIAL INSTALLED NOT LESS THAN 18" IN ALL DIRECTIONS / STILL NEED COMPLETE HOOD INSPECTION .GREASE DUCT LIGHT TEST : TWO HOLES MARKED AND DATED. STILL NEED DROP WELDED CONNECTION TO VERTICAL GREASE DUCT WHEN READY. (ALL SUPPLY, RETURN GRILLS AND REGISTERS IN SEATED DINING AREA OK. ) | LIDO | LIDO | | HD | P | 6384130 |
COMFORT CONTROL, INC. | HD | P | 10/28/2019 | GREASE DUCT LIGHT TEST FOR CURB DROP ONLY OK / OK TO APPLY 1ST LAYER AND 2ND LAYER OF WRAP/ CONTRACTOR TO PROVIDE PICTURES OF 1ST LAYER OF WRAP AND INSTALLATION INSTRUCTIONS TO INSPECTOR AT 2ND LAYER WRAP INSPECTION. RTU-2: NEED SMOKE DETECTOR. SUPPLY AND RETURN DUCT ROUGH OK / OK TO WRAP. RTU-1: MISSING SUPPLY AIR FROM 14 X 12 DUCT IN KITCHEN / REST OF SUPPLY AND RETURN AIR DUCT ROUGH OK / OK TO WRAP. | LIDO | LIDO | | HD | P | 6382304 |
COMFORT CONTROL, INC. | HD | P | 10/18/2019 | TYPE-1 HOOD INSPECTION : BACK OF HOOD IS ZERO CLEARANCE. THERE ARE COMBUSTIBLES IN THE HOOD WALL / THE REQUIRED CLEARANCES TO COMBUSTIBLES WILL NEED TO BE ACHIEVED PER EQUIPMENT SPECIFICATION FOR THE COOK-LINE EQUIPMENT BELOW HOOD / COOK-LINE EQUIPMENT SPECIFICATION WILL NEED TO BE PROVIDED TO THE INSPECTOR AT FINAL INSPECTION. CONTAINMENT WILL ALSO NEED TO BE ACHIEVED PER THE HOOD SPECIFICATIONS FOR THE COOK-LINE EQUIPMENT. . | LIDO | LIDO | | HD | P | 6374146 |
COMFORT CONTROL, INC. | HD | P | 10/07/2019 | (CONTRACTOR INSTALLING GAS MUST ATTACH TO PERMIT/ ELECTRICAL CONTRACTOR MUST ATTACH TO PERMIT.) PLANS SHOW A TYPE -1 HOOD THAT IS 0" CLEARANCE TO THE BACK / THE HOOD ON SITE IS 18" TO COMBUSTIBLES AND 3" TO LIMITED COMBUSTIBLES TO THE BACK / NEED REVISED AND APPROVED PLANS TO SHOW HOOD BEING INSTALLED . REMOVE ALL COMBUSTIBLES FROM WALL BEHIND KITCHEN TYPE -1 HOOD . | LIDO | LIDO | | HD | P | 6360254 |
PRO LINE PLUMBING LLC | P= | C | 11/01/2019 | Engineer's Letter approved for existing water heater and floor sinks. | SAMH | SAMH | | P= | C | 6385956 |
PRO LINE PLUMBING LLC | PTO | C | 10/14/2019 | Verify support on Water mains in ceiling at final. By final need Engineers letter approving use of 2 existing floor sinks, and delete new Water heater from scope of work. | SAMH | SAMH | | PTO | C | 6367153 |
PRO LINE PLUMBING LLC | PTO | P | 10/11/2019 | In wall dwv ok. Need to test and insulate in wall water lines, and inspect all overhead piping. In wall water sizing ok. | SAMH | SAMH | | PTO | P | 6365929 |
PRO LINE PLUMBING LLC | PB | P | 10/08/2019 | Need engineers letter to approve using 2 existing floor sinks in lieu of new. Rest ok. | SAMH | SAMH | | PB | P | 6361227 |
COMFORT CONTROL, INC. | XMS | T | 11/20/2019 | PAID (REC#1645885) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouds using existing rtu's | DALEH | DALEH | | XMS | T | 6405822 |
COMFORT CONTROL, INC. | XMS | T | 11/04/2019 | PAID (REC#1643979): PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: okay new splice gas connection for fryer | TCRIPPEN | TCRIPPEN | | XMS | T | 6386849 |
COMFORT CONTROL, INC. | XMS | T | 10/24/2019 | PAID (REC#1639809) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice see notes 21 and 22 on plan set | TCRIPPEN | TCRIPPEN | | XMS | T | 6378969 |