GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 06/02/2020 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 6589641 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 01/13/2020 | pending completion of mech final, building okay. Additional Inspections Required (computer generated): COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 6451639 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/15/2019 | pending other required inspections - non bearing non rated wall framing, soffit framing and unistrut install okay | BOBF | BOBF | | BFR | P | 6400381 |
ENCORE ELECTRIC, INC. | E= | C | 01/08/2020 | letter received stating the area is a dry location | CRAIGS | CRAIGS | | E= | C | 6446129 |
ENCORE ELECTRIC, INC. | E= | R | 12/09/2019 | all receptacles need to meet 517.20 of the NEC --- or a letter from the governing body stating this is not a wet procedure area ---- occupancy I-2 condition 2 | CRAIGS | CRAIGS | | E= | R | 6420616 |
ENCORE ELECTRIC, INC. | ER | C | 12/09/2019 | | CRAIGS | CRAIGS | | ER | C | 6420610 |
ENCORE ELECTRIC, INC. | ER | R | 12/02/2019 | raceway to the lights has to be an approved equipment ground ( I.E . hospital grade mc or hard metal conduit | CRAIGS | CRAIGS | | ER | R | 6412730 |
ENCORE ELECTRIC, INC. | ER | P | 11/07/2019 | walls OK | CRAIGS | CRAIGS | | ER | P | 6392134 |
COLORADO SHEET METAL CO., INC. | H= | C | 06/02/2020 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6589640 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 05/19/2020 | PLAN REVISION IS COMPLETE | JERRYF | JERRYF | | H= | C | 6576579 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 12/20/2019 | PARTIAL PENDING PLAN REVISION PER PREVIOUS NOTES NOTES: ALL FINAL CONNECTIONS AND CONTROLS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 6434601 |
COLORADO SHEET METAL CO., INC. | H= | P | 12/20/2019 | PARTIAL PENDING TAB REPORT | JERRYF | JERRYF | | H= | P | 6434598 |
COLORADO SHEET METAL CO., INC. | HD | L | 12/06/2019 | CANCELED BY CONTRACTOR AT CALL AHEAD | JERRYF | JERRYF | | HD | L | 6419275 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 11/06/2019 | STILL NEED TIE INS AT MAINS AND HUMIDIFIER - PLAN REVISION SHOWING ACTUAL ROUTING - CONTRACTOR TO SUPPLY PICTURES OF TIE INS AT MAINS - NEED PERMIT CORRECTIONS MADE CSM SHOWS 1 HUMIDIFIER AND OLSON SHOWS 2 - NEED HWP PIPING ADDED TO PERMIT WORK SCOPE NOTES: PRESSURE TEST OK ON HWP PIPING MAIN FROM CATH LAB TO NEAR CHASE AT MAIN LINE - CONDENSATE DRAIN OK | JERRYF | JERRYF | | HWP | P | 6390565 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/28/2019 | PERMIT SHOWS 2 CONTRACTORS CLAIMING HUMIDIFIER / NEED 1 CONTRACTOR TO CLAIM HUMIDIFIER NOTES: ABOVE CEILING SA / RA MAINS AND RUN OUTS AND OK | JERRYF | JERRYF | | HD | P | 6382105 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 12/20/2019 | Ok. | DANR | DANR | | P= | C | 6434542 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 11/22/2019 | | TAYLOR | TAYLOR | | PTO | C | 6408559 |
OLSON PLUMBING & HEATING COMPANY | P= | P | 11/22/2019 | still need to add drain for condensate to scope of work, rest ok. | TAYLOR | TAYLOR | | P= | P | 6408552 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 11/07/2019 | in wall DWV and H2O ok, add drain for condensate to scope of work. | TAYLOR | TAYLOR | | PTO | P | 6391991 |
OLSON PLUMBING & HEATING COMPANY | XMS | T | 02/06/2020 | PAID (REC#1660603) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice re routed lines . | TCRIPPEN | TCRIPPEN | | XMS | T | 6475206 |