WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 04/20/2020 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 6545736 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 01/30/2020 | final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), GRANT DRUMMOND II Plumbing Final Inspection is not Completed yet, PEAK HEATING & AIR COND, INC. Mechanical Final Inspection is not Completed yet, PROCOM ELECTRICAL SERVICES, INC. Electrical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 6469613 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 11/12/2019 | new interior light gauge framing OK pending other roughs / need to attach all mechanical electrical and plumbing permits and have all inspections / discussed accessible elements | DANE | DANE | | BFR | P | 6395970 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 04/20/2020 | correction made | BRETC | BRETC | | E= | C | 6545734 |
PROCOM ELECTRICAL SERVICES, INC. | E= | R | 04/06/2020 | Circuits on plans - OK / Cannot use tandem breakers, they are not listed for this panel, need to add sub panel. | BRETC | BRETC | | E= | R | 6532698 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 12/30/2019 | ceilings only | RANDY | RANDY | | ER | P | 6439284 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 03/19/2020 | TEST AND BALANCE REPORT RECEIVED / THERMOSTATS IN PLACE ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6515289 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 03/11/2020 | TEST AND BALANCE REPORT REVIEW - MISSING OUTDOOR AIR READINGS. STILL NEED TO VERIFY ALL THREE THERMOSTATS. OK TO ATTACH PICTURES TO THE NEXT INSPECTION REQUEST. | LIDO | LIDO | | H= | P | 6506913 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 01/27/2020 | FINAL PENDING: INSTALL ALL THREE THERMOSTATS. OK TO ATTACH PICTURES TO THE NEXT INSPECTION REQUEST/ NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6465057 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 11/19/2019 | ALL VAV'S AND FPB LOW PRESSURE MAIN TRUNKS AND LATERALS OK, OK TO WRAP. NEED TO SEE MEDIUM PRESSURE DUCTS, VAV'S AND FPB INSTALLED AND DUCT CONNECTIONS. VAV-2 MISSING END CAP ON MAIN TRUNK. NO FLEX AND DIFFUSERS. | DUSTINS | DUSTINS | | HD | P | 6404473 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 11/18/2019 | DOOR LOCKED AT 3:30 PM. | NANCY | NANCY | | HD | P | 6402972 |
DRUMMOND PLUMBING LLC | P= | C | 02/07/2020 | | SAMH | SAMH | | P= | C | 6476998 |
DRUMMOND PLUMBING LLC | PTO | C | 11/22/2019 | | SAMH | SAMH | | PTO | C | 6408357 |