HENSEL PHELPS CONSTRUCTION CO | B= | C | 05/26/2020 | Building | JEREMYA | JEREMYA | | B= | C | 6582640 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 05/05/2020 | Framing at storage room A1112 OK | JEREMYA | JEREMYA | | BFR | P | 6561837 |
HENSEL PHELPS CONSTRUCTION CO | BSP | P | 04/24/2020 | partial final for rooms 1107/1107A/1107B only -- complete other finals/rest ok for these rooms | SCOTTS | SCOTTS | | BSP | P | 6550793 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 04/17/2020 | above grid penetrations at rated walls ok | SCOTTS | SCOTTS | | BFR | P | 6543677 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 04/01/2020 | 3rd drywall layer on soffit is complete/floor penetrations complete/still need above lid inspection per previous comments | SCOTTS | SCOTTS | | BFR | P | 6527959 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 03/31/2020 | plumbing drain penetration and first layer of horizontal assembly on file | SCOTTS | SCOTTS | | BFR | P | 6526181 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 03/24/2020 | need to attach plumbing permit and have inspections / OK to attach photo of fire caulking at plumbing drain through floor at break room wall and first layer and 1/2 layer of rock at horizontal assembly at smoke barrier (page A400) to online inspection request / all interior non-bearing framing OK at all smoke partitions and smoke barriers and non-rated walls / grid-x hard lid framing OK / discussed accessible elements with contractor / discussed need for above ceiling before dropped ceiling tiles are installed / still need electrical inspection | DANE | DANE | | BFR | P | 6519742 |
ENCORE ELECTRIC, INC. | E= | C | 05/20/2020 | FIRE ALARM INSPECTION: | RANDY | RANDY | | E= | C | 6578940 |
ENCORE ELECTRIC, INC. | E= | C | 05/19/2020 | | RANDY | RANDY | | E= | C | 6576714 |
ENCORE ELECTRIC, INC. | ER | P | 05/05/2020 | cardiac registration and storage walls | RANDY | RANDY | | ER | P | 6561936 |
ENCORE ELECTRIC, INC. | ER | P | 04/29/2020 | FIRE ALARM INSPECTION: Registration A1105, A1105A & A1105B - Ceilings - Ok | BRETC | BRETC | | ER | P | 6556146 |
ENCORE ELECTRIC, INC. | ER | P | 04/29/2020 | Registration A1105, A1105A & A1105B - Ceilings - Ok | BRETC | BRETC | | ER | P | 6556145 |
ENCORE ELECTRIC, INC. | E= | P | 04/27/2020 | FIRE ALARM INSPECTION: FA with electric | RANDY | RANDY | | E= | P | 6551927 |
ENCORE ELECTRIC, INC. | ER | P | 04/27/2020 | FIRE ALARM INSPECTION: FA with electric | RANDY | RANDY | | ER | P | 6551926 |
ENCORE ELECTRIC, INC. | E= | P | 04/24/2020 | FIRE ALARM INSPECTION: chaplin and security offices ok | RANDY | RANDY | | E= | P | 6551826 |
ENCORE ELECTRIC, INC. | ER | P | 04/24/2020 | chaplin and security offices ok | RANDY | RANDY | | ER | P | 6551825 |
ENCORE ELECTRIC, INC. | ER | P | 04/20/2020 | FIRE ALARM INSPECTION: FA with electric | RANDY | RANDY | | ER | P | 6545610 |
ENCORE ELECTRIC, INC. | ER | P | 04/20/2020 | above ceilings security rm, break rm, Chaplin office----marked on plans | RANDY | RANDY | | ER | P | 6545606 |
ENCORE ELECTRIC, INC. | ER | P | 03/31/2020 | remainder of soffit | MATTHEW | MATTHEW | | ER | P | 6526711 |
ENCORE ELECTRIC, INC. | ER | P | 03/30/2020 | soffit marked on plans ----- access doors marked on plans | MATTHEW | MATTHEW | | ER | P | 6525586 |
ENCORE ELECTRIC, INC. | ER | P | 03/26/2020 | walls marked on approved plans E201------ need fire alarm rough attachment------- I spoke with contractor about accessibility requirements | MATTHEW | MATTHEW | | ER | P | 6522272 |
ENCORE ELECTRIC, INC. | ER | R | 03/24/2020 | contractor called wrong permit | MATTHEW | MATTHEW | | ER | R | 6519358 |
MECHONE, INC. | H= | C | 05/18/2020 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6574302 |
MECHONE, INC. | H= | P | 05/11/2020 | FIRE DAMPER RETAINING ANGLE, BREAKAWAY CONNECTIONS, ACCESS DOOR AND STICKER OK. MECHANICAL FINAL PENDING NEED TO SEE 6" SUPPLY AIR IN STG A1112. PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6567758 |
MECHONE, INC. | HD | C | 05/08/2020 | ONE FIRE DAMPER FRAMING OK. NEED TO SEE RETAINING ANGLE, ACCESS DOOR, BREAKAWAY CONNECTIONS AND LABEL. | DUSTINS | DUSTINS | | HD | C | 6566015 |
MECHONE, INC. | HD | P | 05/07/2020 | NEED FIRE DAMPER FRAMING INSTALLED PER INSTALLATION INSTRUCTIONS. | DUSTINS | DUSTINS | | HD | P | 6564014 |
MECHONE, INC. | H= | P | 04/30/2020 | MECHANICAL FINAL PENDING: NEED TO SEE COMPLETE INSTALLATION OF FIRE DAMPER FOR TB 247, PLEASE HAVE INSTALLATION INSTRUCTIONS ON SITE FOR INSPECTION. PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6557123 |
MECHONE, INC. | HD | P | 04/20/2020 | STILL NEED CLARIFICATION FROM ENGINEER ON FIRE DAMPERS AND DUCTS INSIDE CLOUDED DELTA 1. DELTA 1 STATES TO REFER TO ASI 1, PER ARCHITECTURAL PAGES ASI 1 IS NOT USED. RECEIVED RFI RESPONSE TO ENGINEER APPROVAL OF USING EXISTING 8" ROUND FOR RETURN AIR IN BREAK ROOM A1103, WILL ATTACH TO PERMIT. MECHANICAL FINAL OK IN BREAK ROOM A1103 ONLY PENDING TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | HD | P | 6545532 |
MECHONE, INC. | HD | P | 03/23/2020 | NEED ELECTRICAL AND PLUMBING CONTRACTORS TO ATTACH TO PERMIT. NEED ENGINEER TO ADDRESS FIRE DAMPERS AND DUCTS INSIDE CLOUDED DELTA 1. DELTA 1 STATES TO REFER TO ASI 1, PER ARCHITECTURAL PAGES ASI 1 IS NOT USED. ENGINEER TO ADDRESS IF EXISTING 8" ROUND FOR RETURN AIR CAN BE USED IN BREAK ROOM. OTHER SUPPLY/RETURN AIR DUCTS OK, OK TO WRAP. | DUSTINS | DUSTINS | | HD | P | 6518381 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 05/22/2020 | Ok. | DANR | DANR | | P= | C | 6581617 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 04/06/2020 | Ok. Note: By final need engineer splice showing new DWV tie in location. | DANR | DANR | | PTO | C | 6532506 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/26/2020 | In wall DWV and domestic water ok. | DANR | DANR | | PTO | P | 6522584 |
OLSON PLUMBING & HEATING COMPANY | XPS | T | 04/10/2020 | PAID (REC#1673404): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: Revised waste line routing to reflect what was installed in the field | TCRIPPEN | TCRIPPEN | | XPS | T | 6537190 |
HENSEL PHELPS CONSTRUCTION CO | XES | P | 03/23/2020 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised fixture type P1. | BERTHA | BERTHA | | XES | P | 6518080 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 03/19/2020 | PAID (REC#1669549): PLAN SPLICE FEE: $50 by: DANM for Construction: Various revisions throughout architectural sheets | DANM | DANM | | XBS | T | 6516505 |