PRO WALL SYSTEMS LLC | B= | C | 06/02/2020 | All other required Final inspections are complete. (This is a computer generated result) | CHUCK | CHUCK | | B= | C | 6589661 |
PRO WALL SYSTEMS LLC | B= | P | 05/27/2020 | Pic of corrected accessible restroom sign on file. Building final complete. Additional Inspections Required (computer generated): CLEAR WATER PLUMBING, HEATING & UTILITIE Plumbing Final Inspection is not Completed yet, MICK HEATING & SHEET METAL Mechanical Final Inspection is not Completed yet. | CHUCK | CHUCK | | B= | P | 6585085 |
PRO WALL SYSTEMS LLC | B= | P | 05/27/2020 | Need to relocate accessible womens restroom sign to latch side of door // Rest of building final OK pending completion of mechanical and plumbing final inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): CLEAR WATER PLUMBING, HEATING & UTILITIE Plumbing Final Inspection is not Completed yet, MICK HEATING & SHEET METAL Mechanical Final Inspection is not Completed yet. | CHUCK | CHUCK | | B= | P | 6584923 |
PRO WALL SYSTEMS LLC | BFR | P | 04/01/2020 | Frame OK / Reviewed accessible elements / Need to attach mechanical / Need all MEP's complete | NICK | NICK | | BFR | P | 6528219 |
MEYER ELECTRIC | E= | C | 05/22/2020 | | BRET | BRET | | E= | C | 6581260 |
MEYER ELECTRIC | E= | R | 05/20/2020 | need support wires for all receptacles in ceiling, gfci protect water cooler, gfci doesn't function in women room, gfci protect receptacle within 6' of mop sink | BRET | BRET | | E= | R | 6578093 |
MEYER ELECTRIC | ER | C | 05/19/2020 | | BRET | BRET | | ER | C | 6576939 |
MEYER ELECTRIC | ER | P | 03/31/2020 | walls and lid ok south bath lid will need 24x24 access by btime of ceiling rough | BRET | BRET | | ER | P | 6527694 |
MICK HEATING & SHEET METAL CO. | H= | C | 05/28/2020 | TEST AND BALANCE REPORT RECEIVED SEE IMAGES FINAL COMPLETE. | TREVORH | TREVORH | | H= | C | 6585492 |
MICK HEATING & SHEET METAL CO. | H= | P | 05/27/2020 | UNIT LABELED TO SUITE 130, VENTLESS WASHER/DRYER COMBO PER PLANS OK.REMOTE INDICATOR OK. FINAL PENDING---- TEST AND BALANCE REPORT | TREVORH | TREVORH | | H= | P | 6585005 |
MICK HEATING & SHEET METAL CO. | HD | P | 05/04/2020 | . ALL SUPPLY AND RETURN DIFFUSERS OK EXHAUST FAN AND DUCTING OK AT FINAL WILL NEED TO SEE DRYER PER NOTE #2 ON SHEET M1.01 , ROOF TOP UNIT NEEDS TO BE LABELED AS THE THE SUITE SERVED , REMOTE INDICATOR HAS BEEN WIRED WILL NEED TO SEE IT MOUNTED. | TREVORH | TREVORH | | HD | P | 6559679 |
MICK HEATING & SHEET METAL CO. | HD | P | 04/06/2020 | SUPPLY DUCTING PER PLAN OK, OK TO WRAP. NO FLEX OR DIFFUSERS NO EXHAUST DUCTING OR FAN AT THIS TIME AND NO ROOF.AT FINAL WILL NEED TO SEE DRYER PER NOTE #2 ON SHEET M1.01 | TREVORH | TREVORH | | HD | P | 6532644 |
CLEAR WATER PLUMBING, HEATING & UTILITIES, LLC | P= | C | 06/02/2020 | Engineers letter for AAV uploaded to images. | DANR | DANR | | P= | C | 6589660 |
CLEAR WATER PLUMBING, HEATING & UTILITIES, LLC | P= | P | 05/15/2020 | Need engineer letter for AAV at laundry / rest ok. | DANR | DANR | | P= | P | 6573392 |
CLEAR WATER PLUMBING, HEATING & UTILITIES, LLC | PTO | C | 05/15/2020 | Ok. Note: By final need engineer letter for AAV at washer. | DANR | DANR | | PTO | C | 6573388 |
CLEAR WATER PLUMBING, HEATING & UTILITIES, LLC | PTO | P | 04/09/2020 | In wall DWV and domestic water only: Ok. Note: need engineer approval for AAV at laundry by final. | DANR | DANR | | PTO | P | 6536261 |
CLEAR WATER PLUMBING, HEATING & UTILITIES, LLC | PB | C | 04/01/2020 | | TAYLOR | TAYLOR | | PB | C | 6527932 |