PALMER RIDGE CONSTRUCTION CO. | B= | C | 12/01/2020 | Finished basement, rear deck w/out stairs, AC | TRENTP | TRENTP | | B= | C | 6792944 |
PALMER RIDGE CONSTRUCTION CO. | B= | P | 12/01/2020 | Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 on file / Pending field inspection -- Schedule a new Building Final when above items are complete. | TRENTP | TRENTP | | B= | P | 6791810 |
PALMER RIDGE CONSTRUCTION CO. | BIN | C | 09/01/2020 | Installers cert for blown in insulation on file / Installers cert and ES report for product used for fire protection of floors on file / Will need air leakage test by final | TRENTP | TRENTP | | BIN | C | 6692011 |
PALMER RIDGE CONSTRUCTION CO. | BIN | P | 08/31/2020 | Please provide copy of Installers cert for blown in insulation, observed 4 1/2 inches over spray foam in walls / Please provide installer cert and ES report for product used for fire protection of floor in unfinished space | TRENTP | TRENTP | | BIN | P | 6691398 |
PALMER RIDGE CONSTRUCTION CO. | BIN | P | 08/31/2020 | Installers cert and evaluation report for spray foam insulation on file / Pending field inspection | TRENTP | TRENTP | | BIN | P | 6690529 |
PALMER RIDGE CONSTRUCTION CO. | BFR | C | 08/24/2020 | Item corrected | TRENTP | TRENTP | | BFR | C | 6682281 |
PALMER RIDGE CONSTRUCTION CO. | BFR | P | 08/20/2020 | Missing 1 trimmer for northern garage door left side / Rest okay | TRENTP | TRENTP | | BFR | P | 6679631 |
PALMER RIDGE CONSTRUCTION CO. | BFR | P | 08/20/2020 | Engineer letter received for following items: Anchor bolts, exterior piers, and replacement of steel post / Pending field inspection of other corrections | TRENTP | TRENTP | | BFR | P | 6679151 |
PALMER RIDGE CONSTRUCTION CO. | BFR | R | 08/17/2020 | Revised garage door framing not done at time of inspection, Will need to inspect framing, narrow braced wall fastening, and blocking of brackets once complete / Inspector unable to confirm anchor bolts at sill plate / Plans show southwest steel beam in basement is to bear on 3" steel post, beam currently bearing on (3) 2x6s / Finished basement, rear deck / NOTE: Need observation for rear exterior piers / Update TP 8/17/20 Will need to inspect stairs at final | TRENTP | TRENTP | | BFR | R | 6674979 |
PALMER RIDGE CONSTRUCTION CO. | BFR | L | 08/14/2020 | Cancelled by contractor (Kevin) | TRENTP | TRENTP | | BFR | L | 6672811 |
PALMER RIDGE CONSTRUCTION CO. | BLA | C | 08/06/2020 | | TRENTP | TRENTP | | BLA | C | 6663417 |
PALMER RIDGE CONSTRUCTION CO. | BSP | P | 06/05/2020 | Porches, decks, narrow braced walls and Notes A and S okay | TRENTP | TRENTP | | BSP | P | 6595294 |
PALMER RIDGE CONSTRUCTION CO. | BFI | C | 04/10/2020 | Rigid R10 installed at interior side of walkout foundation wall OK. | CHUCK | CHUCK | | BFI | C | 6537733 |
PALMER RIDGE CONSTRUCTION CO. | BFD | C | 04/10/2020 | Usable drain to daylight at rear walkout and foundation damp proofing OK. | CHUCK | CHUCK | | BFD | C | 6537731 |
PALMER RIDGE CONSTRUCTION CO. | BFD | P | 04/10/2020 | Soils report already on file. Need to complete drain inspection. | CHUCK | CHUCK | | BFD | P | 6537071 |
PALMER RIDGE CONSTRUCTION CO. | BFN | C | 04/10/2020 | Foundation design and foundation reinforcement with UFER observation on file. | CHUCK | CHUCK | | BFN | C | 6537062 |
PALMER RIDGE CONSTRUCTION CO. | BFT | C | 04/10/2020 | Soils report, open ex., over ex. and footing observation on file - 3500# (design verified) / 10% / usable drain required. | CHUCK | CHUCK | | BFT | C | 6537060 |
PALMER RIDGE CONSTRUCTION CO. | BFT | P | 03/31/2020 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFT | P | 6526261 |
PALMER RIDGE CONSTRUCTION CO. | BFN | P | 03/31/2020 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFN | P | 6526260 |
ROWAN ELECTRIC LLC | E= | C | 11/23/2020 | 30 amp a/c , 22 KW generator | TOMC | TOMC | | E= | C | 6786158 |
ROWAN ELECTRIC LLC | ER | C | 08/03/2020 | ER OK ------ | GREGM | GREGM | | ER | C | 6658542 |
ROWAN ELECTRIC LLC | ES | C | 07/31/2020 | Residential Underground: 200 amp 3/w: new res------ meter is sealed; need seal | MATTHEW | MATTHEW | | ES | C | 6657867 |
ROWAN ELECTRIC LLC | ER | R | 07/31/2020 | install floor box right of slider and seal openings in pan box in bathroom in guest bedroom upstairs------------- finished basement, ir ufer, no vac, no mcc's, 200 amp sub-panel and sub-panel fed with #2al wired correctly (breakers not installed) generac transfer switch is service disconnect and needs to be labeled as service disco by final | MATTHEW | MATTHEW | | ER | R | 6657864 |
ROWAN ELECTRIC LLC | EUG | C | 05/28/2020 | 250 urd | TOMC | TOMC | | EUG | C | 6586007 |
ROWAN ELECTRIC LLC | ESL | C | 05/04/2020 | floor box in basement | TOMC | TOMC | | ESL | C | 6559804 |
CUSTOM CLIMATE CONTROL | H= | C | 11/30/2020 | CORRECTION MADE, SEE IMAGES WHOLE HOUSE VENTILATION BEING ACHIEVED WITH EXHAUST FAN LOCATED IN LAUNDRY ROOM / WHOLE HOUSE VENTILATION SWITCH LOCATED IN LAUNDRY ROOM / NOTE / FINISHED BASEMENT / DIRECT VENT FURNACE X2 / A/C ROUGH COIL AND LINESET / NO OUTSIDE AIR TO FURNACE RETURN / HIGH/LOW GRILLES INTO MECHANICAL ROOM / | BILLS | BILLS | | H= | C | 6789976 |
CUSTOM CLIMATE CONTROL | H= | P | 11/25/2020 | SOUTH-WEST BASEMENT BEDROOM REQUIRES A 1" UNDER CUT AT DOOR. CONTRACTOR TO ATTACH DETAILED PICTURES AT NEXT INSPECTION REQUEST. WHOLE HOUSE VENTILATION BEING ACHIEVED WITH EXHAUST FAN LOCATED IN LAUNDRY ROOM / WHOLE HOUSE VENTILATION SWITCH LOCATED IN LAUNDRY ROOM / NOTE / FINISHED BASEMENT / DIRECT VENT FURNACE X2 / A/C ROUGH COIL AND LINESET / NO OUTSIDE AIR TO FURNACE RETURN / HIGH/LOW GRILLES INTO MECHANICAL ROOM / | BILLS | BILLS | | H= | P | 6788634 |
CUSTOM CLIMATE CONTROL | H= | P | 11/16/2020 | INSTALL GARAGE UNIT HEATER, GARAGE HEATER BVENT LACKS CLEARANCE TO DRYWALL, NEED RETURN AIR PATHWAYS AT ALL BASEMENT BEDROOMS, CONNECT CONDENSER, INSTALL GENERATOR, MISSING SUPPLY AIR AT MASTER SUITE CLOSET?, ALL EXTERIOR GAS REGULATORS TO BE RATED FOR OUTDOORS AND TO BE IN THE CORRECT POSITION.
WHOLE HOUSE VENTILATION BEING ACHIEVED WITH EXHAUST FAN LOCATED IN LAUNDRY ROOM / WHOLE HOUSE VENTILATION SWITCH LOCATED IN LAUNDRY ROOM / NOTE / FINISHED BASEMENT / DIRECT VENT FURNACE X2 / A/C ROUGH COIL AND LINESET / NO OUTSIDE AIR TO FURNACE RETURN / HIGH/LOW GRILLES INTO MECHANICAL ROOM / | BILLS | BILLS | | H= | P | 6778233 |
COLORADO GAS SYSTEMS | HO | C | 09/11/2020 | 10 LB TEST OK / 30 FT OF 3/4 INCH POLY WITH TRACER WIRE FOR FUTURE FIRE PIT | ANDREWP | ANDREWP | | HO | C | 6703027 |
CUSTOM CLIMATE CONTROL | HC | C | 07/22/2020 | RELEASE METER | ANDREWP | ANDREWP | | HC | C | 6645943 |
CUSTOM CLIMATE CONTROL | HRR | C | 07/22/2020 | | ANDREWP | ANDREWP | | HRR | C | 6645938 |
CUSTOM CLIMATE CONTROL | HRR | P | 07/20/2020 | WATER HEATER VENTING IS INCOMPLETE / MISSING BATH EXHAUST ON MAIN LEVEL/ WHOLE HOUSE VENTILATION BEING ACHIEVED WITH EXHAUST FAN LOCATED IN LAUNDRY ROOM / VERIFY WHOLE HOUSE VENTILATION SWITCH LOCATION AT FINAL /
NOTE/FINISHED BASEMENT / 2X DIRECT VENT FURNACE / NO OUTSIDE AIR TO FURNACE RETURN / A/C rough, coil and lineset. / | ANDREWP | ANDREWP | | HRR | P | 6642774 |
COLORADO GAS SYSTEMS | HI | C | 07/17/2020 | BY FINAL PROVIDE LETTER FROM BLACK HILLS APPROVING MEDIUM PRESSURE GAS FOR THIS ADDRESS / BY FINAL VERIFY REGULATORS AND ACCESS / STENCILING FOR MEDIUM PRESSURE ALREADY IN PLACE
10 LB TEST OK / 1 INCH MAIN/ 3 OUTDOOR STUBS/ 2 FURNACES/ 2 FIRE PLACE/ 1 WATER HEATER/ 1 GARAGE HEATER/ 1 RANGE | ANDREWP | ANDREWP | | HI | C | 6640887 |
WESTERN FIREPLACE SUPPLY, INC. | HV | C | 07/16/2020 | BASEMENT FIREPLACE CLEARANCE TO COMBUSTIBLES AND VENT TERMINATION OK / | ANDREWP | ANDREWP | | HV | C | 6639357 |
WESTERN FIREPLACE SUPPLY, INC. | HV | L | 07/14/2020 | HOME LOCKED RE CALL WHEN READY AND PROVIDE LOCK BOX CODE ? | TREVORH | TREVORH | | HV | L | 6637444 |
WESTERN FIREPLACE SUPPLY, INC. | HV | P | 07/13/2020 | BASEMENT FIRE PLACE VENTING NEEDS 1 INCH CLEARANCE TO FRONT OF THE FRAMING
MAIN LEVEL FIRE PLACE VENTING AND FRAMING ARE OK/ NON COM INSTALLED | ANDREWP | ANDREWP | | HV | P | 6634644 |
DBA PLUMBING LLC | P= | C | 11/06/2020 | Note: RP in mech room | MALYNDA | MALYNDA | | P= | C | 6767745 |
DBA PLUMBING LLC | P= | P | 11/06/2020 | Potable water certificate attached | MALYNDA | MALYNDA | | P= | P | 6767248 |
DBA PLUMBING LLC | PTO | C | 08/03/2020 | Ok. Note: AAV both master lavs - all basement lavs - bar / finished basement 3 bath - 1 bar - 1 laundry - 1 laundry sink / tempering at water heater for master tub / irrigation stub / need potable water certificate by final. | DANR | DANR | | PTO | C | 6659040 |
DBA PLUMBING LLC | PB | C | 04/30/2020 | Ok. Note: Need potable water certificate by final. | DANR | DANR | | PB | C | 6557080 |
PALMER RIDGE CONSTRUCTION CO. | PWO | C | 04/29/2020 | Note: Need potable water certificate by final | MALYNDA | MALYNDA | | PWO | C | 6555922 |
PALMER RIDGE CONSTRUCTION CO. | XBS | T | 08/14/2020 | PAID (REC#1704465): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise garage header | MICHAELA | MICHAELA | | XBS | T | 6672561 |
PALMER RIDGE CONSTRUCTION CO. | XMS | T | 06/09/2020 | PAID (REC#1686796): PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new duct design | TCRIPPEN | TCRIPPEN | | XMS | T | 6598154 |
PALMER RIDGE CONSTRUCTION CO. | XBS | T | 06/08/2020 | PAID (REC#1686797): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise IECC | MICHAELA | MICHAELA | | XBS | T | 6597225 |
PALMER RIDGE CONSTRUCTION CO. | XBS | T | 05/06/2020 | PAID (REC#1678623): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise deck surface and structure - change posts | MICHAELA | MICHAELA | | XBS | T | 6563055 |