THOMAS GENERAL CONTRACTORS, INC. | B= | C | 09/21/2020 | | NATHAN | NATHAN | | B= | C | 6712318 |
THOMAS GENERAL CONTRACTORS, INC. | B= | T | 08/25/2020 | PAID (REC#1707287): TCO. Additional Inspections Required (computer generated): ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet, GRANT DRUMMOND II Mechanical Final Inspection is not Completed yet. | GITA | GITA | | B= | T | 6683971 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 08/25/2020 | Temp CO: All finals are completed or pending ( Expires: 9/24/2020 12:00:00 AM) | GITA | GITA | | B= | P | 6683969 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 08/20/2020 | pending completed core/shell permit and required final inspections B= okay -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet, ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet, GRANT DRUMMOND II Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 6679882 |
THOMAS GENERAL CONTRACTORS, INC. | BSP | P | 06/16/2020 | stair drywall attachment for rated assembly completed | NATHAN | NATHAN | | BSP | P | 6606421 |
THOMAS GENERAL CONTRACTORS, INC. | BSP | P | 06/11/2020 | Under stair drywall not ready. | NATHAN | NATHAN | | BSP | P | 6601027 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 06/04/2020 | Bar walls/Fire protection at Stairs room 107 | NATHAN | NATHAN | | BFR | P | 6593579 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 05/29/2020 | kitchen framing only with completed required inspections. | NATHAN | NATHAN | | BFR | P | 6587633 |
DILLER ELECTRIC LLC | E= | C | 08/04/2020 | | BRIAN | BRIAN | | E= | C | 6660187 |
DILLER ELECTRIC LLC | E= | P | 07/31/2020 | some outlets under hood need gfci cb/ | JOHNN | JOHNN | | E= | P | 6657470 |
DILLER ELECTRIC LLC | ER | P | 05/28/2020 | bar area walls, Discussed accessibility requirements with contractor / | JOHNN | JOHNN | | ER | P | 6585754 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | C | 09/17/2020 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6708881 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 09/03/2020 | PARTIAL PENDING TAB REPORT NOTES: PLAN SPLICE FOR CORRECTED DUCT SIZING AT GREASE DUCT / ALL OTHER CORRECTIONS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 6695724 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 09/02/2020 | NO CORRECTIONS MADE - NEED ALL PREVIOUS ITEMS ADDRESSED BEFORE NEXT INSPECTION | JERRYF | JERRYF | | H= | P | 6694203 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | L | 08/27/2020 | CANCELED AT CALL AHEAD BY STEVE CLARK | JERRYF | JERRYF | | H= | L | 6687858 |
DRUMMOND PLUMBING LLC | H= | C | 08/26/2020 | CORRECTION MADE AT RANGE | JERRYF | JERRYF | | H= | C | 6686077 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 08/21/2020 | NEED THE FOLLOWING TO COMPLETE FINAL - TAG ALL EXHAUST FANS ON ROOF - INSTALL GREASE WRAP PILLOWS AT DOORS PER INSTALL MANUAL - TAB REPORT - ALL EQUIPMENT INSTALLED UNDER HOODS - PLAN SPLICE FOR GREASE DUCT SIZING CHANGE PER PREVIOUS NOTES - COMPLETE CONDENSATE DRAINS AT COOLERS NOTES: SMOKE SHUTDOWN MONITORED BY FIRE PANEL - INTERLOCKS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 6681697 |
DRUMMOND PLUMBING LLC | H= | P | 08/21/2020 | NEED REGULATOR AT 4 BURNER RANGE INSTALLED CORRECTLY - CONTRACTOR TO ATTACH PICTURES TO NEXT INSPECTION REQUEST | JERRYF | JERRYF | | H= | P | 6681683 |
DRUMMOND PLUMBING LLC | H= | P | 08/19/2020 | INSPECTION WAS FOR GAS FINAL ON KITCHEN EQUIPMENT, 2 LB LETTER ON FILE, TIE DOWNS IN PLACE AND FLEX CONNECTORS INSTALLED, NEED TO REPLACE BLUE VENT LIMITER CAP WITH BRASS CAP AND RECALL WHEN READY | BENH | BENH | | H= | P | 6677758 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 08/18/2020 | NEED THE FOLLOWING - ROOF INSPECTION - PLAN REVISION FOR GREASE DUCT SIZING CHANGE - ROOF INSPECTION - GREASE DUCT ACCESS DOOR INSPECTION (NEED INSTALL MANUAL FOR GREASE WRAP) - COOLERS ADDED TRANSFERRED FROM M84789 TO THIS PERMIT - TAB REPORT NOTES: INTERLOCKS OK | JERRYF | JERRYF | | H= | P | 6676405 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | L | 08/17/2020 | CANCELED BY CONTRACTOR | JERRYF | JERRYF | | H= | L | 6674396 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HRP | P | 08/11/2020 | NEED WALK IN COOLERS ATTACHED TO THIS PERMIT AT THIS TIME COOLERS ARE ATTACHED TO M84789 NOTES: PRESSURE TEST AND DRAINS ARE COMPLETE - BY FINAL NEED CONDENSER TAGGED TO AREA SERVED | JERRYF | JERRYF | | HRP | P | 6668545 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 07/28/2020 | INSPECTION WAS FOR GREASE WRAP ON LOWER LEVEL HOOD GOING UP TO FAN ON ROOF, CONTRACTOR HAD PICTURES OF 1ST LAYER AND I INSPECTED 2ND LAYER AND BANDING, OK TO COVER WHERE GREASE DUCT PASSES THROUGH 2ND FLOOR AND GOES TO ROOF, QUESTIONING ACCESS DOOR INSTALLATION IT IS ALL CLOSED UP WITH WRAP AND THERE IS NO WAY WITHOUT REMOVING GREASE DUCT WRAP TO GET TO ACCESS DOOR. REFER TO INSTALLATION INSTRUCTIONS | BENH | BENH | | HD | P | 6652725 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | L | 07/23/2020 | CANCELED BY JERRY HOFFMAN AFTER CONSULT DID NOT HAVE WRAP INSTALL MANUAL ONSITE - CONTRACTOR TO RESCHEDULE | JERRYF | JERRYF | | HD | L | 6647663 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 07/13/2020 | NEED INTERIOR WELDS AT SECTION BETWEEN HOODS GROUND SMOOTH AND INSPECTION CALLED | JERRYF | JERRYF | | HD | P | 6634983 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 07/10/2020 | 3 HOLES IN DUCT AT HOOD TO VERTICAL TURN - NEED ALL INTERIOR DUCT WELDS GROUND SMOOTH AND RE INSPECTED | JERRYF | JERRYF | | HD | P | 6633735 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 07/09/2020 | LIGHT TEST OK AT SECOND FLOOR DUCT STILL NEED TIE AT 1ST FLOOR AND CURB PLATE | JERRYF | JERRYF | | HD | P | 6632359 |
DRUMMOND PLUMBING LLC | HC | C | 06/24/2020 | OK TO SET 2# METER | JERRYF | JERRYF | | HC | C | 6616053 |
DRUMMOND PLUMBING LLC | HI | C | 06/24/2020 | BY FINAL NEED 2# APPROVAL LETTER - VERIFY FINAL CONNECTIONS / REGULATORS / LABELS / TIE DOWNS NOTES: PRESSURE TEST OK AND PIPING PER BLUE BEAM PAGE 38 | JERRYF | JERRYF | | HI | C | 6616052 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 06/23/2020 | LIGHT TEST OK ON VERTICAL DROP INCLUDING 1 45 AND 1 90 - STILL NEED TIE TO HORIZONTAL AT HOOD AND DUCT UP TO CURB DROP - NEED PLAN REVISION FOR DUCT SIZE CHANGE TO MATCH INSTALLED | JERRYF | JERRYF | | HD | P | 6614131 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 06/08/2020 | NEED PLAN REVISION FOR GREASE DUCT PER PREVIOUS NOTES NOTES: LIGHT TEST OK ON HOOD 2 | JERRYF | JERRYF | | HD | P | 6596537 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 06/05/2020 | NEED PLAN REVISED FOR DUCT SIZE TO INSTALLED PLAN CALLS FOR 30 X 10 HAS 18 X 14 INSTALLED NOTES: LIGHT TEST OK ON DUCT DIRECTLY ABOVE 10' HOOD ONLY - STILL NEED DUCT AT BOTH ENDS | JERRYF | JERRYF | | HD | P | 6595167 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 05/29/2020 | HOOD WALL OK | JERRYF | JERRYF | | HD | P | 6587363 |
DRUMMOND PLUMBING LLC | P= | C | 08/19/2020 | | SAMH | SAMH | | P= | C | 6678719 |
DRUMMOND PLUMBING LLC | PTO | C | 06/16/2020 | | SAMH | SAMH | | PTO | C | 6605768 |
DRUMMOND PLUMBING LLC | PTO | P | 05/28/2020 | In wall piping at hood wall complete. | SAMH | SAMH | | PTO | P | 6586448 |