WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 11/23/2020 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 6785215 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 10/05/2020 | Building final complete pending other final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet, PEAK HEATING & AIR COND, INC. Mechanical Final Inspection is not Completed yet, PROCOM ELECTRICAL SERVICES, INC. Electrical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 6729767 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFT | P | 08/28/2020 | Interior wall framing OK | JEREMYA | JEREMYA | | BFT | P | 6690246 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 07/21/2020 | Framing OK, will need penetration details for all items penetrating rated assemblies // Complete other rough inspections | JEREMYA | JEREMYA | | BFR | P | 6644861 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 11/23/2020 | Corrections made | BRETC | BRETC | | E= | C | 6785214 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 10/23/2020 | Label VAV's in panel, Look at brkrs to which ones are present / Rest - Ok | BRETC | BRETC | | E= | P | 6753026 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 10/06/2020 | 1 VAV's inside main box ground wire strands falling off of screw / Install new VAV brkr's (1) 40 amp brkr feeding 20 amp fused at disconnect VAV / Add receptacles in conference rm | BRETC | BRETC | | E= | P | 6731412 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 10/05/2020 | Complete re inspect / label 3 vav's and remove bond screws where neutrals are landed / | BRETC | BRETC | | E= | P | 6730364 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 09/11/2020 | Above ceilings / 4 - VAV will still need to be looked at, leave tiles out around VAV's | BRETC | BRETC | | ER | P | 6703066 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 09/02/2020 | Walls Only - Ok | BRETC | BRETC | | ER | P | 6694239 |
PROCOM ELECTRICAL SERVICES, INC. | ER | R | 08/27/2020 | Need Fire alarm inspection called in and attached to permit / all electrical grid wires need to be attached to hard lid framing / | BRETC | BRETC | | ER | R | 6688493 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 07/20/2020 | Corrections made / Walls only - Ok | BRETC | BRETC | | ER | P | 6643233 |
PROCOM ELECTRICAL SERVICES, INC. | ER | R | 07/17/2020 | all switches need to be 48" to top / complete re inspect / Look @ R4C feed 100 amp? | BRETC | BRETC | | ER | R | 6641338 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 11/05/2020 | CORRECTIONS MADE. SEE IMAGES. | LIDO | LIDO | | H= | C | 6765582 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 11/03/2020 | REVISED TEST AND BALANCE REPORT RECEIVED SEE IMAGES / FINAL PENDING : MISSING THERMOSTAT FOR TF-1/ LABEL ALL THERMOSTATS / OK TO ATTACH PICTURE OF CORRECTION TO AN INSPECTION REQUEST / | LIDO | LIDO | | H= | P | 6762421 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 10/27/2020 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. TEST AND BALANCE REPORT MISSING OUTSIDE AIR READINGS. | DUSTINS | DUSTINS | | H= | P | 6754852 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 09/25/2020 | FINAL PENDING : MISSING THERMOSTAT FOR TF-1/ LABEL ALL THERMOSTATS / NEED TEST AND BALANCE REPORT / OK TO ATTACH PICTURE OF CORRECTION TO AN INSPECTION REQUEST / | LIDO | LIDO | | H= | P | 6720483 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 09/24/2020 | BUILDING LOCKED. NO ACCESS. | LIDO | LIDO | | H= | P | 6718900 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 09/01/2020 | NEED CONSULT WITH BUILDING FOR EXISTING DUCT PENETRATIONS THROUGH RATED WALL ASSEMBLY ALL DUCT ROUGH OK . OK TO WRAP / | LIDO | LIDO | | HD | P | 6692709 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 07/27/2020 | PLANS SHOW EXISTING 14" X 10" RETURN AIR FIRE OR FIRE SMOKE DAMPER IN WALL BETWEEN HALLWAY AND ROOM # 208, A NEW DAMPER IS BEING INSTALLED. REVISED AND APPROVED PLANS ARE REQUIRED TO REFLECT ?FIRE DAMPER OR FIRE SMOKE DAMPER BEING INSTALLED ( Symbol used for the damper does not match the legend on plan page M1.0 / revised plans must show a symbol from the legend to know if damper is a fire or a fire smoke damper ) / FPB-1-6 -MISSING 4 SUPPLY BRANCH LINES , REST OF DUCT ROUGH OK. OK TO WRAP / VAV1-3 - MISSING 2 8" SUPPLY BRANCH LINES. REST OF DUCT ROUGH OK , OK TO WRAP VAV -1-1- DUCT ROUGH OK, OK TO WRAP/ VAV-1-5- DUCT ROUGH OK, OK TO WRAP / FPB-1-4 - DUCT ROUGH OK , OK TO WRAP / | LIDO | LIDO | | HD | P | 6651655 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 10/21/2020 | corrections made | JOSEPHD | JOSEPHD | | P= | C | 6749528 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 10/20/2020 | sink still crossed, still need to see over head water pipe insulation, other corrections made | JOSEPHD | JOSEPHD | | P= | P | 6747669 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 10/06/2020 | need high loop at dishwasher, need backflow for coffee dispenser, sink crossed, need over head water pipe insulation, rest ok | JOSEPHD | JOSEPHD | | P= | P | 6731457 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 09/01/2020 | correction made note: check over head water pipe insulation at final | JOSEPHD | JOSEPHD | | PTO | C | 6692344 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 08/25/2020 | re-grade 2" cast under floor from sink drop to 3" connection, need to see pipe insulation installed per plan page 02\M.0, overhead vent and water pipe ok | JOSEPHD | JOSEPHD | | PTO | P | 6684662 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 07/20/2020 | Need inspection under floor and overhead / In wall DWV and domestic water ok. | DANR | DANR | | PTO | P | 6643097 |
PROCOM ELECTRICAL SERVICES, INC. | XES | T | 08/31/2020 | PAID (REC#1709681): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised power and lighting for background changes. | BERTHA | BERTHA | | XES | T | 6690989 |
PEAK HEATING & AIR CONDITIONING, INC. | XMS | P | 08/28/2020 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical | JUSTINC | JUSTINC | | XMS | P | 6689619 |
WELLS & WEST GENERAL CONTRACTORS, INC. | XBS | T | 08/28/2020 | PAID (REC#1709202): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add conference room and office | MICHAELA | MICHAELA | | XBS | T | 6689528 |