WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 11/23/2020 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 6785209 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 10/05/2020 | Building final complete pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet, PEAK HEATING & AIR COND, INC. Mechanical Final Inspection is not Completed yet, PROCOM ELECTRICAL SERVICES, INC. Electrical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 6729775 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 07/21/2020 | Framing OK, will need penetration details for all items penetrating rated assemblies // Complete other rough inspections | JEREMYA | JEREMYA | | BFR | P | 6644868 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 11/23/2020 | Corrections made | BRETC | BRETC | | E= | C | 6785208 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 10/23/2020 | Label VAV's in panel, Look at brkrs to which one is present / Rest - Ok | BRETC | BRETC | | E= | P | 6753024 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 10/06/2020 | 4 VAV's inside main box ground wire strands falling off of screw / Install new VAV brkr's (2) 40 amp brkr feeding 20 amp fused at disconnect VAV / Add receptacles in conference rm | BRETC | BRETC | | E= | P | 6731395 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 10/05/2020 | Trouble shoot exit lights / TS fridge circuit / Spark rings in break rm / | BRETC | BRETC | | E= | P | 6730360 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 09/02/2020 | Hallway into 251/271 ceiling - Ok / 271 ceiling VAV 480v bond bushing both concentric knockout connectors / 2ND VAV not wired, is not on drawings? / Need to Look at EWH, location and size. / IT closet light missing / Rest of ceiling - Ok | BRETC | BRETC | | ER | P | 6694250 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 07/20/2020 | Corrections made / Walls only - Ok | BRETC | BRETC | | ER | P | 6643235 |
PROCOM ELECTRICAL SERVICES, INC. | ER | R | 07/17/2020 | all switches need to be 48" to top / complete re inspect | BRETC | BRETC | | ER | R | 6641336 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 11/05/2020 | CORRECTIONS MADE. SEE IMAGES. | LIDO | LIDO | | H= | C | 6765760 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 11/03/2020 | Revised test and balance report received. See images / FINAL PENDING : 6" SUPPLY FROM VAV 1-8 TO CORRIDOR AND FIRE SMOKE DAMPER ELIMINATED. NEED REVISED AND APPROVED PLANS / LABEL ALL THERMOSTATS / OK TO ATTACH PICTURE OF LABELED THERMOSTATS TO AN INSPECTION REQUEST / | LIDO | LIDO | | H= | P | 6762486 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 10/27/2020 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. TEST AND BALANCE REPORT MISSING OUTSIDE AIR READINGS. | DUSTINS | DUSTINS | | H= | P | 6754796 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 09/25/2020 | FINAL PENDING : 6" SUPPLY FROM VAV 1-8 TO CORRIDOR AND FIRE SMOKE DAMPER ELIMINATED. NEED REVISED AND APPROVED PLANS / LABEL ALL THERMOSTATS / NEED TEST AND BALANCE REPORT / OK TO ATTACH PICTURE OF CORRECTION TO AN INSPECTION REQUEST / | LIDO | LIDO | | H= | P | 6720477 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 09/24/2020 | BUILDING LOCKED. NO ACCESS. | LIDO | LIDO | | H= | P | 6718899 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 09/01/2020 | 6" SUPPLY FROM VAV 1-8 TO CORRIDOR AND FIRE SMOKE DAMPER ELIMINATED. NEED REVISED AND APPROVED PLANS / ALL DUCT ROUGH OK. OK TO WRAP. ALL SUPPLY FLEX DUCT, GRILLS AND RETURN LAY - INS OK . | LIDO | LIDO | | HD | P | 6692716 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 07/27/2020 | FPB-1-3 -NEED TO RESEARCH 16" X 14" DUCT PENETRATION THROUGH WALL SEPARATING RETAIL SPACE 251 AND 271. DUCT PENETRATION MAY NEED PROTECTION AT WALL / DAMPER FRAME INSPECTION - MISSING SCREWS WERE THE VERTICAL STUDS TIE INTO THE TOP TRACK / VAV-08-1 - FINISH SEALING THE TRUNK LINE, MISSING 8" SUPPLY FOR ROOM 202 . REST OF DUCT ROUGH OK , OK TO WRAP / | LIDO | LIDO | | HD | P | 6651644 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 10/21/2020 | corrections made | JOSEPHD | JOSEPHD | | P= | C | 6749530 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 10/06/2020 | need high loop at dishwasher, need backflow at coffee maker, need over head water pipe insulation, sink crossed | JOSEPHD | JOSEPHD | | P= | P | 6731467 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 09/01/2020 | note: shark bite tees removed no letter needed, check over head insulation at final | JOSEPHD | JOSEPHD | | PTO | C | 6692336 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 08/25/2020 | need engineer letter for shark bite tee's at main connection, need to see pipe insulation per plan page 02\M.0 over head water pipe and vent ok save for letter for tee's, under floor ok | JOSEPHD | JOSEPHD | | PTO | P | 6684486 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 07/20/2020 | Need inspection under floor and overhead / In wall DWV and domestic water ok. | DANR | DANR | | PTO | P | 6643102 |
PEAK HEATING & AIR CONDITIONING, INC. | XMS | T | 11/03/2020 | PAID (REC#1727030): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Removed supply and return from hall | JUSTINC | JUSTINC | | XMS | T | 6763263 |