ELDER CONSTRUCTION, INC. | B= | C | 08/17/2021 | State plumbing inspection certificate on file | JUSTINL | JUSTINL | | B= | C | 7074369 |
ELDER CONSTRUCTION, INC. | B= | P | 08/16/2021 | Still need copy of state plumbing inspection certificate - State certificate for electrical inspection on file / Observed remaining final inspections corrections noted in B= 5-11-2021 / Pending other final inspections / OK to attach state plumbing inspection certificate to inspection request - no follow up field inspection needed -- Schedule a new Building Final when above items are complete. | JUSTINL | JUSTINL | | B= | P | 7073636 |
ELDER CONSTRUCTION, INC. | BSP | P | 06/03/2021 | Engineer judgment for steel beam penetrations and multiple electrical penetrations on file | DAKOTAB | DAKOTAB | | BSP | P | 6989281 |
ELDER CONSTRUCTION, INC. | BSP | P | 06/03/2021 | Engineer letter for welding/bolting on file -- 3rd party observation for spray applied fire protection on file | DAKOTAB | DAKOTAB | | BSP | P | 6989276 |
ELDER CONSTRUCTION, INC. | B= | P | 05/11/2021 | Still need to inspect firestopping at penetrations at 1hr fire partition at corner of wrestling room and in storage adjacent to wresting room where voids were -- Need firestop details for all penetrations at 1hr fire partition walls to be uploaded and upload detail for expansion joints at 1hr fire partition / fire stopping at bar joist penetrations OK - firestop at expansion joint OK per details on site -- Need 3rd party observations for welding/bolting and for spray applied fire coating -- Need State electrical and plumbing inspection documents -- EXTERIOR INSPECTIONS// missing truncated domes at both curb ramp locations and missing landings both locations / rest of exterior final OK / Pending other finals -- Schedule a new Building Final when above items are complete. | LONNYS | LONNYS | | B= | P | 6964593 |
ELDER CONSTRUCTION, INC. | B= | R | 03/31/2021 | Need full inspection on exterior -- Interior of addition only inspected -- SINGLE USE RESTROOM-- Need to install knee protection at sink -- MENS AND WOMENS RESTROOM - Need to install knee protection at sinks -- Still need to inspect all firestopping at penetrations at 1hr fire partition -- Need firestop detail for all penetrations at 1hr fire partition walls -- Need listing for expansion joints at 1hr fire partition -- Need 3rd party observations for welding/bolting and for spray applied fire coating -- Need State electrical and plumbing inspection documents -- Pending other finals | DAKOTAB | DAKOTAB | | B= | R | 6917569 |
ELDER CONSTRUCTION, INC. | BLA | P | 03/18/2021 | Lath at parapet walls on roof OK | DAKOTAB | DAKOTAB | | BLA | P | 6903589 |
ELDER CONSTRUCTION, INC. | BFR | P | 03/04/2021 | ABOVE LID -- Multiple penetrations at 1hr fire partition not firestopped -- Still need listing for joist penetrations into fire partition and for all penetrations through out | DAKOTAB | DAKOTAB | | BFR | P | 6888558 |
ELDER CONSTRUCTION, INC. | BSP | P | 02/18/2021 | Observed mineral wool stuffed into cavity at expansion joint at 1hr fire barriers -- Still need listing on file for expansion joint firestopping | DAKOTAB | DAKOTAB | | BSP | P | 6873949 |
ELDER CONSTRUCTION, INC. | BLA | P | 02/12/2021 | Lath at all entryways OK | DAKOTAB | DAKOTAB | | BLA | P | 6869677 |
ELDER CONSTRUCTION, INC. | BFR | P | 02/10/2021 | Hard lid framing at 535,536, and 537 OK -- Reviewed need for listings for all penetrating items at 1hr fire barrier at wrestling room -- Discussed need for listing for rated expansion joist at wrestling room rated walls and inspection process | DAKOTAB | DAKOTAB | | BFR | P | 6866499 |
ELDER CONSTRUCTION, INC. | BIN | P | 02/04/2021 | Remainder of interior thermal insulation OK | DAKOTAB | DAKOTAB | | BIN | P | 6860138 |
ELDER CONSTRUCTION, INC. | BFR | P | 02/04/2021 | Remainder of interior light gauge framing OK -- Hard lid framing in rooms 522,523,545,546,546A OK -- Discussed need for firestopping detail at truss penetrations into 1hr fire partition, 3rd party welding/bolting observation, and 3rd party spray applied fire coating observation | DAKOTAB | DAKOTAB | | BFR | P | 6860137 |
ELDER CONSTRUCTION, INC. | BLA | P | 01/28/2021 | Stucco lath at expansion joint on east and west elevation OK | DAKOTAB | DAKOTAB | | BLA | P | 6851893 |
ELDER CONSTRUCTION, INC. | BIN | P | 01/26/2021 | Exterior thermal at north wall and framed wall from NE corner to CMU wall OK | JEREMYA | JEREMYA | | BIN | P | 6848848 |
ELDER CONSTRUCTION, INC. | BFR | P | 01/26/2021 | RC for sound at band and choir rooms OK | JEREMYA | JEREMYA | | BFR | P | 6848841 |
ELDER CONSTRUCTION, INC. | BSP | P | 01/21/2021 | Training with Lonny on E occupancies with type I-B construction -- Discussed penetrations into 2hr fire wall as well as head of wall detail | DAKOTAB | DAKOTAB | | BSP | P | 6844473 |
ELDER CONSTRUCTION, INC. | BLA | P | 01/21/2021 | All lath at area B OK | DAKOTAB | DAKOTAB | | BLA | P | 6844442 |
ELDER CONSTRUCTION, INC. | BSP | P | 01/21/2021 | training with inspector Dakota B. / Type I-B construction - E occupancy / reviewed fire walls / reviewed IBC 410.5 dressing and appurtenant rooms to be 1 hr fire barriers / walked lath inspection | LONNYS | LONNYS | | BSP | P | 6844440 |
ELDER CONSTRUCTION, INC. | BLA | P | 01/19/2021 | Stucco lath at exterior of area B OK -- Stucco lath under windows at Area A OK | DAKOTAB | DAKOTAB | | BLA | P | 6840897 |
ELDER CONSTRUCTION, INC. | BIN | P | 01/14/2021 | R-19 batt insulation at area B exterior walls OK -- Still need to inspect air barrier at exterior walls | DAKOTAB | DAKOTAB | | BIN | P | 6836711 |
ELDER CONSTRUCTION, INC. | BIN | P | 01/13/2021 | Remainder of exterior rigid insulation on north elevation OK -- Discussed remaining framing items with site super as well as insulation inspection requirements | DAKOTAB | DAKOTAB | | BIN | P | 6835154 |
ELDER CONSTRUCTION, INC. | BLA | P | 01/12/2021 | West elevation OK -- Reviewed previous and upcoming inspections with site super | DAKOTAB | DAKOTAB | | BLA | P | 6833340 |
ELDER CONSTRUCTION, INC. | BIN | P | 01/11/2021 | Exterior rigid insulation at low/high roof at hallway 515 OK | DAKOTAB | DAKOTAB | | BIN | P | 6831688 |
ELDER CONSTRUCTION, INC. | BIN | P | 01/07/2021 | R19 cavity thermal insulation and plastic vapor barrier installed at wall between low/high roof in Hallway 515. Need exterior rigid insulation installed to meet R20.5 insulation value as stated in IECC form. | CHUCK | CHUCK | | BIN | P | 6829244 |
ELDER CONSTRUCTION, INC. | BSP | P | 12/28/2020 | 2" thermax (R13) rigid continuous insulation installed on exterior side of wall - Mech. Rm. 524, Electrical Rm. 525, Girls Locker Rm. 523 and Office 527 to Line A, 4. | CHUCK | CHUCK | | BSP | P | 6819984 |
ELDER CONSTRUCTION, INC. | BFR | P | 12/28/2020 | AREA A and B ---- Interior metal stud frame OK, rooms south of D line and east of Line 5 (minus B walls constructed as B1 walls between JC and Storage 548 and wall behind drinking fountains at Lines D.9,7), Office in Weight Lifting Room and Office/Storage in Wrestling Room. Still need to inspect furring channels for C4 wall types per plan and A1 walls noted in previous frame inspection. Discussed needing head of wall detail for 'D1' CMU walls supporting bar joists. | CHUCK | CHUCK | | BFR | P | 6819971 |
ELDER CONSTRUCTION, INC. | BFR | P | 12/22/2020 | AREA A and B ---- Interior metal stud frame OK, rooms north of D line and west of Line 5 (minus A1 frame not constructed yet at exterior walls in Choir 1 and 2 and Practice Room 540). Will need to inspect furring channels for C4 wall types per plan. | CHUCK | CHUCK | | BFR | P | 6817566 |
ELDER CONSTRUCTION, INC. | BFR | P | 12/16/2020 | Re-inspection of exterior/perimeter metal stud wall frame. All OK per spliced details on file. Exterior 5/8" gyp. sheathing OK at exterior walls. Need 3rd party red iron and metal weld/red iron bolt and fire spray applied material observation paperwork | CHUCK | CHUCK | | BFR | P | 6810384 |
ELDER CONSTRUCTION, INC. | BSP | P | 12/15/2020 | Open ex./over ex. observation on file - 3000# soil bearing capacity; footing and foundation with ufer observation on file; bond beam and masonry observation on file; foundation insulation observation on file. Will need weld and bolt observations as they become available. | CHUCK | CHUCK | | BSP | P | 6807678 |
ELDER CONSTRUCTION, INC. | BFR | R | 12/10/2020 | Inspection cancelled on site. Still need exterior wall steel stud framing details spliced to plans. Discussed completing foundation inspections with contractor (Brad). | CHUCK | CHUCK | | BFR | R | 6804003 |
ELDER CONSTRUCTION, INC. | BFR | P | 12/03/2020 | Exterior wall metal stud framing inspected from Line A, 6-14. Need 'Cold Formed Metal Stud Framing and Connections' deferred submittal as noted on Sht. S-002 to verify stud connections and bracing. Various structural plan details only show 6" metal studs at 16" o.c. with clips secured to steel structure. Clips are welded to structure and will need paperwork certifying welds are completed properly. | CHUCK | CHUCK | | BFR | P | 6796081 |
ELDER CONSTRUCTION, INC. | BFR | P | 11/16/2020 | Exterior wall metal stud framing OK - Office 527, Boys Locker Rm. 522 and Girls Locker Rm. 523. Discussed 3rd party inspection paperwork with contractor on site. UPDATE by CL - Need 'Cold Formed Metal Stud Framing and Connections' deferred submittal' as noted on Sht. S-002 spliced to plans. | CHUCK | CHUCK | | BFR | P | 6778302 |
COLORADO SHEET METAL CO., INC. | H= | C | 04/29/2021 | MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6951744 |
COLORADO SHEET METAL CO., INC. | H= | P | 04/29/2021 | RECEIVED IMAGES OF ROOF ACCESS LADDERS INSTALLED, SEE IMAGES. NEED ON SITE INSPECTION TO VERIFY MEASUREMENTS ON LADDER. WILL SCHEDULE INSPECTION FOR TODAY. | DUSTINS | DUSTINS | | H= | P | 6951177 |
COLORADO SHEET METAL CO., INC. | H= | P | 04/06/2021 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. MECHANICAL FINAL PENDING: NEED PERMANENT ROOF ACCESS TO BOTH NEW ROOFS PER 2015 IMC 306.5. | DUSTINS | DUSTINS | | H= | P | 6922916 |
COLORADO SHEET METAL CO., INC. | HRP | C | 03/26/2021 | 400 LB TEST OK ON LINE SET FOR MINI SPLIT. | DUSTINS | DUSTINS | | HRP | C | 6912713 |
COLORADO SHEET METAL CO., INC. | H= | P | 03/26/2021 | MECHANICAL FINAL PENDING: NEED PERMANENT ROOF ACCESS TO BOTH NEW ROOFS PER 2015 IMC 306.5. PROVIDE TEST AND BALANCE REPORT FOR FINAL. | DUSTINS | DUSTINS | | H= | P | 6912707 |
COLORADO SHEET METAL CO., INC. | H= | P | 03/25/2021 | ALL THERMOSTATS AND CO2 SENSORS INSTALLED. ALL UNIT HEATERS INSTALLED. MECHANICAL FINAL PENDING: STILL NEED TO LABEL EXHAUST FANS AND CONDENSER ON ROOF. NEED PERMANENT ROOF ACCESS TO BOTH NEW ROOFS PER 2015 IMC 306.5. NEED TO SEE SMOKE DETECTORS FOR RTU'S MOVING OVER 2000 CFM. NEED TO SEE WATER LEVEL MONITORING DEVICES IN RTU'S. NEED TO SEE MINI SPLITS INSTALLED. PROVIDE TEST AND BALANCE REPORT FOR FINAL. | DUSTINS | DUSTINS | | H= | P | 6910742 |
COLORADO SHEET METAL CO., INC. | H= | P | 03/11/2021 | ALL SUPPLY/RETURN/EXHAUST/TRANSFER AIR DUCTS, FLEX AND DIFFUSERS OK. MECHANICAL FINAL PENDING: NEED TO SEE ALL THERMOSTATS AND CO2 SENSORS INSTALLED. LABEL EXHAUST FANS AND CONDENSER ON ROOF. NEED PERMANENT ROOF ACCESS. NEED TO SEE SMOKE DETECTORS FOR RTU'S MOVING OVER 2000 CFM. NEED TO SEE WATER LEVEL MONITORING DEVICES IN RTU'S. NEED TO SEE UNIT HEATERS AND MINI SPLITS INSTALLED. PROVIDE TEST AND BALANCE REPORT FOR FINAL. | DUSTINS | DUSTINS | | H= | P | 6896320 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/25/2021 | MH101A AND MH101B (BDA 70 AND 71) SUPPLY/RETURN AIR FLEX AND DIFFUSERS OK. EXHAUST DUCTS AND DIFFUSERS OK. TRANSFER AIR DUCTS OK. | DUSTINS | DUSTINS | | HD | P | 6881028 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/10/2021 | MH101B (BDA 71) MEDIUM/LOW PRESSURE SUPPLY/RETURN AIR MAIN TRUNKS AND LATERALS OK, OK TO WRAP. EXHAUST DUCTS OK. | DUSTINS | DUSTINS | | HD | P | 6866123 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/27/2021 | MH101A AND MH101B (BDA 70 AND 71) MEDIUM/LOW PRESSURE SUPPLY/RETURN AIR MAIN TRUNKS AND LATERALS OK, OK TO WRAP. EXHAUST DUCTS OK, TRANSFER AIR DUCTS OK. | DUSTINS | DUSTINS | | HD | P | 6850114 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/19/2021 | MH101A AND MH101B (BDA 70 AND 71) MEDIUM/LOW PRESSURE SUPPLY/RETURN AIR MAIN TRUNKS AND LATERALS OK, OK TO WRAP. EXHAUST AIR DUCTS OK. | DUSTINS | DUSTINS | | HD | P | 6839623 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/31/2020 | MH101A (BDA 70) MEDIUM/LOW PRESSURE SUPPLY/RETURN AIR MAIN TRUNKS AND LATERALS OK, OK TO WRAP. EXHAUST AIR DUCTS OK. | DUSTINS | DUSTINS | | HD | P | 6823360 |
ELDER CONSTRUCTION, INC. | XBS | T | 04/01/2021 | PAID (REC#1770770): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Minor layout revisions - sink change | MICHAELA | MICHAELA | | XBS | T | 6919080 |
ELDER CONSTRUCTION, INC. | XBS | T | 12/15/2020 | PAID (REC#1736710): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Steel wall framing | MICHAELA | MICHAELA | | XBS | T | 6807401 |