COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | L | 04/08/2024 | | RITA | RITA | | BE | L | 8046138 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | L | 08/30/2023 | Renewed for $192.00 at 8/30/2023 1:58:42 PM (Receipt#1983606) | ASHLEYL | ASHLEYL | | BE | L | 7842742 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BFR | P | 03/01/2023 | Inspection requested on wrong permit. | NATHAN | NATHAN | | BFR | P | 7673705 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | P | 02/14/2023 | | JANE | JANE | | BE | P | 7661583 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | P | 10/18/2022 | | AMYP | AMYP | | BE | P | 7553648 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | P | 04/27/2022 | | SIERRAC | SIERRAC | | BE | P | 7354182 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | B= | P | 11/02/2021 | Complete pending MEP and outside agency final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), TRI-STAR MECHANICAL Plumbing Final Inspection is not Completed yet. | TIMOTHYS | TIMOTHYS | | B= | P | 7163214 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | L | 11/02/2021 | Renewed for $50.00 at 11/2/2021 8:24:03 AM (Receipt#1819509) | BRITNEY | BRITNEY | | BE | L | 7162125 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | B= | P | 04/07/2021 | Need clear floor space centered on the sink at common break room remaining items okay, complete all MEP and outside agencies final inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, TRI-STAR MECHANICAL Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 6925381 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BE | C | 02/09/2021 | | SCANNING | SCANNING | | BE | C | 6864077 |
COMMERCIAL INTERIOR SPECIALISTS, LLC. | BFR | P | 08/19/2020 | Attach electrical permit and complete electric rough inspections / Light gauge steel framing at partitions wall ok / Steel framing at U419 demising wall ok | TIMOTHYS | TIMOTHYS | | BFR | P | 6678805 |
GDS ELECTRIC | E= | C | 03/11/2021 | | JOHNN | JOHNN | | E= | C | 6896698 |
GDS ELECTRIC | ER | C | 01/07/2021 | ceilings in the common area 3rd floor lobby / | BRIAN | BRIAN | | ER | C | 6828375 |
GDS ELECTRIC | ER | P | 08/31/2020 | need to put suite # on permit/ walls and hard lid in common area/reception area/will need 3 access panels in hard lid near stairway door/ | JOHNN | JOHNN | | ER | P | 6691079 |
AIRTECH MECHANICAL, INC. | H= | C | 04/14/2021 | BALANCE REPORT IS OK AND SET AT 20% PER AIR BALANCE CONTRACTOR. RETURN AIR IS OPEN TO ENTIRE SPACE ABOVE CEILING. | JON | JON | | H= | C | 6933035 |
AIRTECH MECHANICAL, INC. | H= | P | 04/14/2021 | Test and balance report received does not have outside air reading on it. Still need to see sound boot installed | MARKB | MARKB | | H= | P | 6932741 |
AIRTECH MECHANICAL, INC. | H= | P | 04/05/2021 | NEED TAB REPORT.. NOTE RETURN AIR SOUND BOOT NOT INSTALLED WALL OPEN TO DECK. | JON | JON | | H= | P | 6921691 |
AIRTECH MECHANICAL, INC. | HSP | P | 03/11/2021 | ALERTED BY ELECTRICAL INSPECTOR THAT DUCT SMOKE DETECTOR ON 3RD FLOOR BY ELEVATOR WAS CONCEALED IN DRYWALL WITH INADEQUATE ACCESS. CALLED AND LEFT MESSAGE WITH CONTRACTOR. | JON | JON | | HSP | P | 6896741 |
AIRTECH MECHANICAL, INC. | HD | R | 03/05/2021 | NO INSPECTION PLANS DO NOT MATCH AND CEILINGS ARE INSTALLED DUCTS CONCEALED WITHOUT INSPECTION. DUCTS NOT SEALED. | JON | JON | | HD | R | 6890813 |
TRI-STAR MECHANICAL | PE | L | 11/26/2023 | Renewed online for Full Fee at Nov 26 2023 5:55PM (RECEIPT #: 2010699) | WEBSITE | WEBSITE | | PE | L | 7927063 |
TRI-STAR MECHANICAL | PE | L | 05/25/2023 | Renewed online for Full Fee at May 25 2023 8:46PM (RECEIPT #: 1957238) | WEBSITE | WEBSITE | | PE | L | 7755385 |
TRI-STAR MECHANICAL | PE | L | 11/14/2022 | Renewed for $50.00 at 11/14/2022 3:27:37 PM (Receipt#1914581) | ASHLEYL | ASHLEYL | | PE | L | 7582846 |
TRI-STAR MECHANICAL | P= | P | 05/12/2022 | No Answer From Call Ahead Number / No One @ Front Desk / | TRAVISR | TRAVISR | | P= | P | 7373318 |
TRI-STAR MECHANICAL | PTO | C | 05/12/2022 | See plans splice. | DANR | DANR | | PTO | C | 7372784 |
TRI-STAR MECHANICAL | PE | L | 12/17/2021 | Renewed online for Full Fee at Dec 17 2021 6:12AM (RECEIPT #: 1830375) | WEBSITE | WEBSITE | | PE | L | 7212399 |
TRI-STAR MECHANICAL | PE | L | 06/18/2021 | Renewed for No Fee at 6/18/2021 10:39:24 AM | VERONIKAP | VERONIKAP | | PE | L | 7007429 |
TRI-STAR MECHANICAL | PTO | P | 11/25/2020 | Domestic water not per plan / DWV ok. Note: AAV sink. | DANR | DANR | | PTO | P | 6789376 |
TRI-STAR MECHANICAL | XPS | T | 05/06/2022 | PAID (REC#1865172): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Clouded revisions only: Adjusted sheet P1.0. | SHANEN | SHANEN | | XPS | T | 7366604 |