RYBA ELECTRIC, INC. | E= | C | 09/11/2020 | | LOGANP | LOGANP | | E= | C | 6703584 |
RYBA ELECTRIC, INC. | ER | C | 09/11/2020 | 2-new-20a dedicated circuits--- | LOGANP | LOGANP | | ER | C | 6703583 |
HVAC SOLUTIONS, INC. | H= | C | 05/26/2021 | REVISED TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | H= | C | 6981299 |
HVAC SOLUTIONS, INC. | H= | P | 05/24/2021 | No outside air shown on balance report | MARKB | MARKB | | H= | P | 6978054 |
HVAC SOLUTIONS, INC. | HE | L | 05/24/2021 | Renewed for $50.00 at 5/24/2021 8:19:20 AM (Receipt#1775133) | VERONIKAP | VERONIKAP | | HE | L | 6978006 |
HVAC SOLUTIONS, INC. | H= | P | 10/20/2020 | PARTIAL PENDING TAB REPORT | BENH | BENH | | H= | P | 6747324 |
HVAC SOLUTIONS, INC. | H= | P | 10/07/2020 | PICTURES REJECTED - FIRE STOPPING APPEARS TO NOT BE INSTALLED CORRECTLY - WILL NEED ONSITE INSPECTION WITH LADDER TO VERIFY INSTALLATION IS PER MECHANICAL PLAN PAGE 11 DETAIL 3 - WILL NEED ACCESS TO BOTH SIDES OF WALL - APPEARS MINERAL WOOL IS NOT INSTALLED FULLY AROUND EACH DUCT PER DETAIL - INSPECTOR TO VERIFY | JERRYF | JERRYF | | H= | P | 6733299 |
HVAC SOLUTIONS, INC. | H= | P | 10/07/2020 | JERRY IS NOT AT WORK TODAY. I HAVE LOOKED AT THE PICTURES AND FROM WHAT I SEE THE INSTALLATION OF THE INSULATION AROUND THE DUCT AND IN THE WALL CAVITY DOES NOT LOOK CORRECT. THE FIRE CAULK ALSO DOES NOT LOOK CORRECT, INSULATION IS SHOWING THROUGH AND IT IS NOT CONTINUOUS AROUND THE DUCTS. I WILL SAVE THE PICTURES TO THE PERMIT AND PUT ANOTHER INSPECTION REQUEST INTO JERRY'S SCREEN SO HE CAN TAKE A LOOK AT WHAT YOU SENT. JERRY MAY BE BACK TO WORK TOMORROW. | NANCY | NANCY | | H= | P | 6732587 |
HVAC SOLUTIONS, INC. | H= | P | 09/30/2020 | NEED TAB REPORT AND SEE HD NOTES TO COMPLETE FINAL | JERRYF | JERRYF | | H= | P | 6724726 |
HVAC SOLUTIONS, INC. | HD | P | 09/30/2020 | NEED FIRE STOPPING COMPLETED PER PAGE 11 DETAIL - CONTRACTOR TO ATTACH PICTURES TO NEXT INSPECTION REQUEST | JERRYF | JERRYF | | HD | P | 6724723 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 05/05/2021 | Ok. | DANR | DANR | | P= | C | 6957834 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 05/05/2021 | See plans splice. | DANR | DANR | | PTO | C | 6957828 |
LANDMARK PLUMBING AND HEATING, INC. | PE | C | 02/12/2021 | | SAVANNAHT | SAVANNAHT | | PE | C | 6869197 |
LANDMARK PLUMBING AND HEATING, INC. | P= | L | 10/27/2020 | field cancelled by contractor, need access to areas to inspect | JOHNS | JOHNS | | P= | L | 6755219 |
LANDMARK PLUMBING AND HEATING, INC. | P= | L | 09/25/2020 | STILL need GC to attach mech permit (as previously noted)
STILL need plan revision
cancelled via call from plbg contractor | JOHNS | JOHNS | | P= | L | 6719436 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 09/02/2020 | NEED TO attach mech permit
NEED TO revise plans to show deleting floor sink and eye wash counter top mounted (in lieu of stand alone eye wash (plans)
NEED TO update scope of work to show revised plbg items installed
rest ok. NOTE: vtr (existing), accessible sinks (x2), revisions | JOHNS | JOHNS | | PTO | P | 6694268 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 09/02/2020 | | JOHNS | JOHNS | | PB | C | 6694259 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 09/01/2020 | see pb notes | JOHNS | JOHNS | | PTO | P | 6692510 |
LANDMARK PLUMBING AND HEATING, INC. | PB | P | 09/01/2020 | dwv not per plan, missing some items, contractor to verify all specs and reqs, re inspect all | JOHNS | JOHNS | | PB | P | 6692507 |
LANDMARK PLUMBING AND HEATING, INC. | XPS | T | 10/23/2020 | PAID (REC#1724697): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: 2 sheets provided, Delta 4 revisions: P0.3 adjusted plumbing schedules and details, P2.1 adjusted level 3 plumbing plan | SHANEN | SHANEN | | XPS | T | 6753604 |