CTY OF C/S - MUNICIPAL AIRPORT | H07 | C | 05/15/2024 | WITNESSED ANNUAL ESCALATOR SAFETY AND STEP INDEX TESTS W/ SCHINDLER -- MINIMUM BRAKE TORQUE 81 FT/LBS, ACTUAL 115 FT/LBS -- / LOWER PIT GFCI NOT WORKING. COMBPLATE WITH BROKEN TOOTH AT TOP NEEDS REPLACED | DUSTINS | DUSTINS | | H07 | C | 8085425 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 05/14/2024 | WITNESSED INSPECTION W/DUSTIN AND SCHINDLER. | MATTM | MATTM | | HE16 | C | 8085631 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 04/02/2024 | ACCIDENT REPORT RECORDED - SEE IMAGES | DUSTINS | DUSTINS | | HE16 | C | 8039374 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 03/19/2024 | PERFORMED EXTERNAL VISUAL INSPECTION -- / NO VISIBLE ISSUES (Receipt #2043760) | DUSTINS | DUSTINS | | H02 | C | 8025625 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 03/12/2024 | ACCIDENT REPORT RECORDED - SEE IMAGES | DUSTINS | DUSTINS | | HE16 | C | 8021878 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 02/01/2024 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7991206 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 01/26/2024 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7991201 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 09/25/2023 | PERFORMED EXTERNAL VISUAL INSPECTION -- / ESCALATOR NOT RUNNING AT TIME OF INSPECTION / BOTTOM EMERGENCY STOP BUZZER SWITCH IS MISSING / 60 DAYS TO ADDRESS (Receipt #1991541) | DUSTINS | DUSTINS | | H01 | C | 7866508 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 08/25/2023 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7837584 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 07/25/2023 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7807844 |
CTY OF C/S - MUNICIPAL AIRPORT | H07 | C | 05/30/2023 | WITNESSED ANNUAL ESCALATOR SAFETY AND STEP INDEX TESTS W/ SCHINDLER -- MINIMUM BRAKE TORQUE 81 FT/LBS, ACTUAL 105 FT/LBS -- / BOTTOM EMERGENCY STOP BUZZER SWITCH IS MISSING | DUSTINS | DUSTINS | | H07 | C | 7756844 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 05/02/2023 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7754377 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 03/30/2023 | H02 -- PERFORMED EXTERNAL VISUAL INSPECTION (NO VISIBLE CODE ISSUES) | ROBERTV | ROBERTV | | H02 | C | 7703054 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 03/20/2023 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7693316 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 01/31/2023 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7655832 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 01/10/2023 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7634916 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 12/28/2022 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7621106 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 10/09/2022 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7544962 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 10/08/2022 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7544951 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 09/27/2022 | TKE ESCALATOR WITH SCHINDLER SERVICE -- MCP LOCATED IN ELEVATOR MACHINE ROOM 3 --/ MISSING BOTTOM EMERGENCY STOP BUZZER SWITCH --/ SCHINDLER TO PROVIDE PPRBD WITH A TIME LINE FOR PARTS BEING DELIVERED AND FOR THE REPAIRS TO BE COMPLETED (Receipt #1902558) | MIKEM | MIKEM | | H01 | C | 7531317 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 09/08/2022 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7509964 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 08/18/2022 | ACCIDENT REPORT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7490200 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 06/22/2022 | ACCIDENT RECORDED - SEE IMAGES | ROBERTV | ROBERTV | | HE16 | C | 7437963 |
CTY OF C/S - MUNICIPAL AIRPORT | H07 | C | 06/13/2022 | WITNESSED ANNUAL ESCALATOR SAFETY AND STEP INDEX TESTS-- MCP LOCATED IN ELEVATOR MACHINE ROOM 3--/ MINIMUM BRAKE TORQUE 81 FT/LBS ACTUAL 95 FT/LBS--/ MISSING BOTTOM EMERGENCY STOP BUZZER SWITCH (SECOND NOTICE)--/ NOTE: COULD NOT IDENTIFY THE ELECTRO MECHANICAL BRAKING DEVICE AND A FOLLOW UP HAS BEEN SCHEDULED | MIKEM | MIKEM | | H07 | C | 7408980 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 05/31/2022 | ACCIDENT REPORT RECORDED - (SEE IMAGES) | ROBERTV | ROBERTV | | HE16 | C | 7394203 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 05/11/2022 | ACCIDENT REPORT RECORDED - (SEE IMAGES) | ROBERTV | ROBERTV | | HE16 | C | 7371578 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 04/15/2022 | ACCIDENT REPORT RECORDED (SEE IMAGES) | ROBERTV | ROBERTV | | HE16 | C | 7340335 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 03/14/2022 | ACCIDENT RECORDED (SEE IMAGES) | ROBERTV | ROBERTV | | HE16 | C | 7300210 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 03/03/2022 | TKE ESCALATOR - WITNESSED ANNUAL TESTING SCHEDULED FOR 5/2022 (CHECK PREVIOUS LISTED ITEMS) | ROBERTV | ROBERTV | | H02 | C | 7289644 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 09/21/2021 | TKE ESCALTOR - BOTTOM EMERGENCY STOP BUTTON COVER BUZZER SWITCH IS STILL NOT WORKING / MISSING. OIL IN PIT NEEDS TO BE CLEANED UP AND SOURCE IDENTIFIED........... 60 DAYS TO ADDRESS.
ESCALATOR MAINTENANCE CONTROL PROGRAM DOCUMENTS ARE SCATTERED AMONGST MULTIPLE ROOMS. THESE DOCUMENTS NEED TO BE GATHERED, SORTED, COMPILED AND IDENTIFIED FOR EACH ESCALATOR AND MADE AVAILABLE IN ONE LOCATION FOR INSPECTORS. BRAKE DATA TAG INFORMATION NEEDS TO BE RE-SCRIBED INTO PLATE....... 60 DAYS TO ADDRESS (Receipt #1808713) | ROBERTV | ROBERTV | | H01 | C | 7115289 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 06/25/2021 | ACCIDENT RECORDED | ROBERTV | ROBERTV | | HE16 | C | 7017108 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 06/02/2021 | ACCIDENT RECORDED | ROBERTV | ROBERTV | | HE16 | C | 7017107 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 05/25/2021 | WITNESSED ANNUAL ESCALATOR SAFETY AND STEP INDEX TESTS--/ MINIMUM BRAKE TORQUE 65 FT/LBS ACTUAL 80 FT/LBS--/ ELECTRICAL AT CONTROLLER IS COMING OUT AT CONNECTIONS--/ COMB AT TOP DECK IS MISSING A TOOTH--/ BOTTOM EMERGENCY STOP COVER BUZZER IS NON FUNCTIONAL--/ MONITOR LEFT HANDRAIL FOR WEAR | MIKEM | MIKEM | | HE16 | C | 6981006 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 05/24/2021 | ACCIDENT RECORDED | ROBERTV | ROBERTV | | HE16 | C | 7017105 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 03/08/2021 | H02 -- ANNUAL SAFETY AND STEP INDEX TESTING DUE 4/2021 | ROBERTV | ROBERTV | | H02 | C | 6892025 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 04/15/2020 | ACCEPTANCE AND ANNUAL | ROBERTV | ROBERTV | | HE16 | C | 6732767 |