GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 04/20/2022 | All other required Final inspections are complete. (This is a computer generated result) | BRIANB | BRIANB | | B= | C | 7346143 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 03/11/2022 | still pending other final inspections. Additional Inspections Required (computer generated): FIRE ALARM: ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 7297967 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 10/11/2021 | still pending other final inspections. Additional Inspections Required (computer generated): FIRE ALARM: ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 7136254 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 04/29/2021 | Building final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet, ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, U.S.ENGINEERING CONSTRUCTION, LLC Mechanical Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | P | 6951680 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/23/2021 | No new interior framing -- Walls demo'd per plan | DAKOTAB | DAKOTAB | | BFR | P | 6877958 |
ENCORE ELECTRIC, INC. | E= | C | 04/20/2022 | FIRE ALARM INSPECTION: | RANDY | RANDY | | E= | C | 7346142 |
ENCORE ELECTRIC, INC. | E= | R | 10/04/2021 | consultation only | RANDY | RANDY | | E= | R | 7128181 |
ENCORE ELECTRIC, INC. | E= | C | 05/10/2021 | | RANDY | RANDY | | E= | C | 6963585 |
ENCORE ELECTRIC, INC. | E= | P | 04/28/2021 | drop ceiling ok ------sandwich shop and gfcis dead fronts behind equipment ok | RANDY | RANDY | | E= | P | 6951045 |
ENCORE ELECTRIC, INC. | E= | P | 04/26/2021 | in sandwich shop need gfci breaker on outlet behind equipment and lights working-------need gfci breaker or dead front gfci protection on outlets behind equipment------ | RANDY | RANDY | | E= | P | 6947424 |
ENCORE ELECTRIC, INC. | ER | P | 04/20/2021 | no new work in ceiling for sandwich station | RANDY | RANDY | | ER | P | 6940951 |
ENCORE ELECTRIC, INC. | EP | P | 04/14/2021 | kitchen panels on equipment ok | RANDY | RANDY | | EP | P | 6934186 |
ENCORE ELECTRIC, INC. | ER | P | 01/21/2021 | walls marked on plans | RANDY | RANDY | | ER | P | 6844814 |
ENCORE ELECTRIC, INC. | ER | P | 01/14/2021 | servery rm walls | RANDY | RANDY | | ER | P | 6837015 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | C | 09/17/2021 | TEST AND BALANCE REPORT RECEIVED. SEE IMAGES. | LIDO | LIDO | | H= | C | 7110439 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 09/14/2021 | TEST AND BALANCE REPORT IS BEING REVIEWED . | LIDO | LIDO | | H= | P | 7106162 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 04/27/2021 | Captive air type -1 hood sensor located. See images / FINAL PENDING: NEED TEST AND BALANCE REPORT.
| LIDO | LIDO | | H= | P | 6947721 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 04/26/2021 | FINAL PENDING : NOT ABLE TO LOCATE ROOM TEMP SENSORS FOR CAPTIVE AIR HOODS / ALL REMOTE SMOKE INDICATORS IN PLACE / NEED TEST AND BALANCE REPORT / | LIDO | LIDO | | H= | P | 6947220 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 04/26/2021 | Gas contractor compete / FINAL GAS CONNECTIONS TO COOK-LINE OK / RESTRAINTS IN PLACE / | LIDO | LIDO | | H= | C | 6947197 |
OLSON PLUMBING & HEATING COMPANY | HI | C | 04/26/2021 | FINAL GAS CONNECTIONS TO COOK-LINE OK / RESTRAINTS IN PLACE / | LIDO | LIDO | | HI | C | 6947193 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 04/20/2021 | HOOD 1, 2 AND 3 : GREASE DUCT FIRE BARRIER WRAP COMPLETE / HOOD INTERLOCK INSPECTION : HOOD 1,2 AND 3 OK AND HOOD INSTALLS ARE COMPLETE / NEED FINAL WALK INSPECTION / NEED TEST AND BALANCE REPORT /
| LIDO | LIDO | | H= | P | 6941075 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 03/05/2021 | HOOD -1 : GREASE DUCT TOP OF HOOD ONLY FIRE BARRIER WRAP INSPECTION - TWO LAYERS OF WRAP ARE NOT CONTINUOUS THROUGH THE WALL ( see 2015 IMC code section 506.3.11.2 field applied grease duct enclosure / grease duct shall be continuously covered on all sides from point of witch duct originated to the outlet terminal/ also see install instructions) HOOD -1 INSTALL OK / HOOD 2 : GREASE DUCT TOP OF HOOD ONLY FIRE BARRIER WRAP INSPECTION - TWO LAYERS OF WRAP ARE NOT CONTINUOUS THROUGH THE WALL. WHERE DUCT PENETRATES WALL THE BOTTOM IS WITHIN 18" OF THE TOP OF HOOD AND MUST BE SEALED. HOOD - 2 INSTALL OK / HOOD -3 : GREASE DUCT TOP OF HOOD ONLY WRAP INSPECTION . FIRE BARRIER WRAP OK . WHERE DUCT PENETRATES WALL THE SIDES ARE WITHIN 18" OF THE TOP OF HOOD AND MUST BE SEALED. HOOD -3 INSTALL OK / | LIDO | LIDO | | HD | P | 6890517 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 03/03/2021 | GREASE DUCT FIRE BARRIER WRAP MUST BE INSTALLED PER TH MANUFACTURER REQUIREMENTS. SEE PAGE # 4 AND 5 FOR HORIZONTAL RUNS, PAGE #12 FOR ELBOWS AND T-FITTING, PAGE # 6 FOR ACCESS DOORS. WENT OVER PAGE #12 FROM THE INSTALL INSTRUCTIONS WITH MECHANICAL CONTRACTOR. | LIDO | LIDO | | HD | P | 6887452 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 02/25/2021 | FIELD CANCELED. NOT READY. | LIDO | LIDO | | HD | P | 6881377 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 02/24/2021 | KITCHEN TYPE 1 HOOD INSPECTION : HOOD 1 - LACKING 18" OF SMOOTH, CLEANABLE NON ABSORBENT NON COMBUSTIBLE SURFACE ON THE RIGHT SIDE AT SOFFIT / HOOD 2 - LACKING 18" OF SMOOTH, CLEANABLE NON ABSORBENT NON COMBUSTIBLE SURFACE LEFT SIDE FROM FLOOR TO 18" ABOVE HOOD. LARGE OPENING AROUND DUCT WITHIN 18" OF THE TOP OF HOOD / HOOD 3 - LACKING 18" OF SMOOTH, CLEANABLE NON ABSORBENT NON COMBUSTIBLE SURFACE RIGHT SIDE AT SOFFIT . LARGE OPENING AROUND DUCT WITHIN 18" OF THE TOP OF HOOD /
| LIDO | LIDO | | HD | P | 6879832 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 02/23/2021 | GREASE DUCT LIGHT TEST : KEF-4 GREASE DUCT CONNECTION TO HOOD 2 / HOOD 3. NO HOLES.(all grease duct welded connection complete for this system inside building ). OK TO APPLY 1ST AND SECOND LAYER OF FIRE BARRIER WRAP. CONTRACTOR TO PROVIDE PICTURES OF 1ST LAYER WRAP AT 2ND LAYER WRAP INSPECTION / | LIDO | LIDO | | HD | P | 6878857 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 02/22/2021 | GREASE DUCT LIGHT TEST : KEF-5 GREASE DUCT CONNECTION TO HOOD 1. NO HOLES.(all grease duct welded connection complete for this system inside building ). OK TO APPLY 1ST AND SECOND LAYER OF FIRE BARRIER WRAP. CONTRACTOR TO PROVIDE PICTURES OF 1ST LAYER WRAP AT 2ND LAYER WRAP INSPECTION / | LIDO | LIDO | | HD | P | 6877218 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 02/01/2021 | SMOKE DAMPER INSPECTION : 1- SMOKE DAMPERS OK. ACCESS DOOR FOR 22" X 12" SMOKE DAMPER OK / | LIDO | LIDO | | HD | P | 6855263 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 01/25/2021 | SMOKE DAMPER INSPECTION : 4 SMOKE DAMPERS OK. 1- 22" X 12" DAMPER IS MISSING THE ACCESS DOOR / | LIDO | LIDO | | HD | P | 6848056 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 01/07/2021 | SMOKE DAMPER INSPECTION : 9 DAMPERS ON SERVERY SIDE. INSTALL AND LABELED ACCESS OK / | LIDO | LIDO | | HD | P | 6828875 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 04/26/2021 | OK. | DANR | DANR | | P= | C | 6946836 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 03/11/2021 | ALREADY LOOKED AT ON PREVIOUS INSPECTION | LEE | LEE | | PTO | C | 6896285 |
OLSON PLUMBING & HEATING COMPANY | PB | C | 02/25/2021 | REVISIONS MADE | LEE | LEE | | PB | C | 6881277 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 01/27/2021 | hand sink at column lines 26 & M being changed to direct connect from indirect, need to add changes to plan, 2" line was tested, floor sink was removed | JOSEPHD | JOSEPHD | | PB | P | 6850591 |
OLSON PLUMBING & HEATING COMPANY | XPS | T | 03/17/2022 | PAID (REC#1865821): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: Approved new splice adding for sink. | TCRIPPEN | TCRIPPEN | | XPS | T | 7305908 |
OLSON PLUMBING & HEATING COMPANY | XPS | T | 02/23/2021 | PAID (REC#1752610): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 42 revisions: P102 adjusted garden level - area 102 plumbing plan | SHANEN | SHANEN | | XPS | T | 6878173 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XMS | P | 12/23/2020 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Layout revisions | JUSTINC | JUSTINC | | XMS | P | 6817910 |