INNOVATE DESIGN BUILD INC. | B= | C | 07/11/2022 | | ERAMIREZ | ERAMIREZ | | B= | C | 7440763 |
INNOVATE DESIGN BUILD INC. | B= | P | 06/21/2022 | Building final OK pending other finals /. Additional Inspections Required (computer generated): LIGHTS ON ELECTRIC INC. Electrical Final Inspection is not Completed yet, BULLSEYE PLUMBING HEATING & AIR Mechanical Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7419852 |
INNOVATE DESIGN BUILD INC. | BFR | C | 04/21/2021 | Items corrected | TIMOTHYS | TIMOTHYS | | BFR | C | 6942144 |
INNOVATE DESIGN BUILD INC. | BFR | R | 01/04/2021 | Need mechanical permit attached or N/A, need all floating wall blocks removed and draftstops completed, egress window at south east bedroom must meet minimum egress size, Reviewed Smoke and CO requirements / | NATHAN | NATHAN | | BFR | R | 6824463 |
LIGHTS ON ELECTRIC INC. | E= | C | 06/23/2022 | | JOHNN | JOHNN | | E= | C | 7422274 |
LIGHTS ON ELECTRIC INC. | E= | P | 06/08/2022 | Need to secure service mast with 1/4" lags. --- Need bonding jumper across water meter and PRV. --- Basement bedroom smoke detector not showing power. --- Need permit for kitchen remodel. --- Baseboard heat not installed. --- | LOGANP | LOGANP | | E= | P | 7403560 |
LIGHTS ON ELECTRIC INC. | ES | C | 06/08/2022 | Residential Overhead: 150-amp 3-wire service upgrade, no action required by utility. / | LOGANP | LOGANP | | ES | C | 7403551 |
LIGHTS ON ELECTRIC INC. | ESP | P | 03/09/2022 | ----------------------Attention inspector, on final need to verify wiring in the kitchen ceiling has been blanked off and see if any wiring came up into an island that has been removed. -------------------------------------- | DEAN | DEAN | | ESP | P | 7295813 |
LIGHTS ON ELECTRIC INC. | ES | L | 01/25/2021 | Need access to service panel for ES inspection for final / 2/0 AL line and load at Meter Socket ok / | LOGANP | LOGANP | | ES | L | 6847204 |
LIGHTS ON ELECTRIC INC. | ER | C | 01/25/2021 | 8/3 CU -- 10/3 -- 4/3 AL to 80a sub-panel --- | LOGANP | LOGANP | | ER | C | 6847197 |
LIGHTS ON ELECTRIC INC. | ER | P | 01/25/2021 | affidavit uploaded / | LOGANP | LOGANP | | ER | P | 6846927 |
LIGHTS ON ELECTRIC INC. | ES | L | 01/22/2021 | | JOHNN | JOHNN | | ES | L | 6845439 |
LIGHTS ON ELECTRIC INC. | ER | L | 01/22/2021 | EC had to reschedule. | JOHNN | JOHNN | | ER | L | 6845420 |
LIGHTS ON ELECTRIC INC. | ES | P | 01/06/2021 | Residential Underground: Pre release ok / | LOGANP | LOGANP | | ES | P | 6826628 |
LIGHTS ON ELECTRIC INC. | ER | P | 12/21/2020 | Need affidavit for 240v receptacle in kitchenette for final / Kitchenette wired as kitchen - Ok / leave sheet rock off at top of stairs and bed room with elec-panel / | BRETC | BRETC | | ER | P | 6815082 |
BULLSEYE PLUMBING HEATING & AIR | H= | C | 06/23/2022 | Scope updated / PLAN SPLICE ADDED | MICHAELM | MICHAELM | | H= | C | 7421809 |
BULLSEYE PLUMBING HEATING & AIR | H= | P | 06/09/2022 | **** DOOR ADDED AT TOP OF STAIRS FOR ACCESS TO BASEMENT (Will need plan splice showing the change in framing and a building inspection) **** / CONTRACTOR TO ADD EXHAUST FAN TO SCOPE OF WORK FOR BATH FAN INSTALLED IN BASEMENT BATHROOM / NOTE: LOUVER DOOR TO MECHANICAL ROOM / PRE-EXISTING OUTSIDE AIR TO FURNACE RETURN | MICHAELM | MICHAELM | | H= | P | 7405364 |
BULLSEYE PLUMBING HEATING & AIR | H= | R | 03/07/2022 | Appears this is not a basement finish but a remodel to a duplex without proper plans. Only access is from outdoors. Has return air cut in above range hood (missing grill). If this is 2 dwelling units, cannot share air between units. Cabinets are set up for a cook top under hood. How is combustion air being provided to mechanical room (outside air duct is tied into return)? Need doors installed to check for return air. May be more notes to follow. | MARKB | MARKB | | H= | R | 7292906 |
BULLSEYE PLUMBING HEATING & AIR | H= | P | 09/23/2021 | CALL AHEAD SENT AT 8:51 / KNOCKED AND RANG BELL / NO ANSWER / LEFT DOOR TAG AT 9:37 | MICHAELM | MICHAELM | | H= | P | 7117283 |
BULLSEYE PLUMBING HEATING & AIR | HRR | C | 04/13/2021 | | MATTM | MATTM | | HRR | C | 6931973 |
BULLSEYE PLUMBING HEATING & AIR | H= | P | 04/02/2021 | NO ANSWER AT DOOR / LEFT DOOR TAG | MICHAELM | MICHAELM | | H= | P | 6920899 |
BULLSEYE PLUMBING HEATING & AIR | HRR | P | 02/02/2021 | Update WH: Per discussion with contractor home-flex line was existing and bathroom exhaust termination existing- due to movement of home-flex into ceiling soffit inspector to verify nail protection plates are placed and leak test existing connection to main / Dryer termination re-located, will need minimum 26 gauge dryer duct installed / New supply in south east bedroom to be mechanically fastened and sealed / | WHITNEYH | WHITNEYH | | HRR | P | 6855811 |
BULLSEYE PLUMBING HEATING & AIR | HRR | R | 01/22/2021 | NEW DRYER DUCT MUST BE MINIMUM 26 GAUGE, MISSING TERMINATION HOOD AT EXTERIOR / NEW SUPPLY INSTALLED TO SOUTH EAST BEDROOM TO BE MECHANICALLY FASTENED AT ALL JOINT CONNECTIONS / QUESTIONING NEW HOME-FLEX CSST LINE INSTALLED TO UPPER LEVEL, NO ACCESS TO UPPER LEVEL; MISSING ELECTRICAL BONDING, STRIKER PLATES FOR PROTECTION AND HI INSPECTION INCLUDING PRESSURE TEST/ BATHROOM EXHAUST TERMINATING WITHIN 3' OF OPERABLE OPENING, WITHIN 10' OF OUTSIDE AIR TO FURNACE RETURN / NOTE / PRE-EXISTING OUTSIDE AIR TO FURNACE RETURN / A/C ROUGH LINE-SET ONLY | WHITNEYH | WHITNEYH | | HRR | R | 6845936 |
BULLSEYE PLUMBING HEATING & AIR | HSP | P | 01/07/2021 | WILL NEED FULL MECHANICAL INSPECTION OF BASEMENT REMODEL / NEED BULLSEYE TO CALL IN HRR INSPECTION AND UPDATE SCOPE OF WORK OR MECHANICAL CONTRACTOR RESPONSIBLE FOR REMODEL TO ATTACH TO PERMIT AND CALL IN ANY RELEVANT INSPECTION / ****DO NOT COVER PRIOR TO MECHANICAL INSPECTION**** | MATTM | MATTM | | HSP | P | 6828003 |
BULLSEYE PLUMBING HEATING & AIR | H= | P | 11/17/2020 | UNABLE TO ACCESS MAIN LEVEL / OK TO ATTACH PICTURE OF CO DETECTOR TO NEXT INSPECTION REQUEST / NOTE / UNFINISHED BASEMENT / 4 INCH PRE-EXISTING OUTSIDE AIR TO FURNACE RETURN / | MATTM | MATTM | | H= | P | 6827679 |
DMB PLUMBING SERVICES INC. | PSP | P | 06/09/2022 | NEW WASHER BOX INSTALLED UPSTAIRS TO BE CLAIMED AND INSPECTED | MICHAELM | MICHAELM | | PSP | P | 7405380 |
DMB PLUMBING SERVICES INC. | P= | C | 06/06/2022 | Ok. | DANR | DANR | | P= | C | 7400066 |
DMB PLUMBING SERVICES INC. | P= | L | 06/03/2022 | Field cancel / not ready. | DANR | DANR | | P= | L | 7398712 |
DMB PLUMBING SERVICES INC. | PE | P | 01/06/2022 | | SIERRAC | SIERRAC | | PE | P | 7231062 |
DMB PLUMBING SERVICES INC. | PTO | C | 12/21/2020 | AAV at mechanical room x2. | SAMH | SAMH | | PTO | C | 6814780 |
INNOVATE DESIGN BUILD INC. | XBS | T | 06/20/2022 | PAID (REC#1876266): PLAN SPLICE FEE: $50 by: CGIECK for Construction: Please review plan. | CGIECK | CGIECK | | XBS | T | 7416892 |