GERALD H PHIPPS INC | B= | C | 04/15/2021 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 6934509 |
GERALD H PHIPPS INC | B= | P | 04/13/2021 | With completed required inspections B= okay. Additional Inspections Required (computer generated): MECH ONE, INC. Mechanical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 6931537 |
GERALD H PHIPPS INC | BFR | P | 03/05/2021 | pending completion of other required inspections, framing in MRI room okay | BOBF | BOBF | | BFR | P | 6889733 |
STURGEON ELECTRIC CO INC | E= | C | 04/05/2021 | | LOGANP | LOGANP | | E= | C | 6921540 |
STURGEON ELECTRIC CO INC | ER | C | 04/05/2021 | Ceiling ok / Corections made / | LOGANP | LOGANP | | ER | C | 6921537 |
STURGEON ELECTRIC CO INC | ER | P | 04/02/2021 | Need pictures of grid wires and grounding of cable tray inside MRI room | BRIAN | BRIAN | | ER | P | 6919854 |
STURGEON ELECTRIC CO INC | ER | P | 03/10/2021 | walls in MRI / | BRIAN | BRIAN | | ER | P | 6895493 |
STURGEON ELECTRIC CO INC | ER | P | 03/09/2021 | walls outside of MRI room --ok / | BRIAN | BRIAN | | ER | P | 6893144 |
STURGEON ELECTRIC CO INC | ER | R | 03/05/2021 | patient care areas need to comply with 517.13 | MATTHEW | MATTHEW | | ER | R | 6890520 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 04/15/2021 | LABELS COMPLETE | MARKB | MARKB | | H= | C | 6934508 |
MECHONE, INC. | H= | C | 04/15/2021 | ENGINEER LETTER RECEIVED FOR PRESSURE EQUALIZATION | MARKB | MARKB | | H= | C | 6934430 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 04/08/2021 | FINAL PENDING - Label chiller piping. SPLICE ON FILE REMOVING CHILLER FROM ROOF. CHILLER PIPING ON MRI SIDE OF HEAT EXCHANGER UNDER OPERATING PRESSURE. INSULATION COMPLETE. CONDENSATE DRAIN FOR HUMIDIFIER TIED INTO CONDENSATE TANK IN BASEMENT. | MARKB | MARKB | | H= | P | 6926978 |
MECHONE, INC. | HSP | P | 04/08/2021 | TEST AND BALANCE REPORT RECEIVED, ACCESS DOORS INSTALLED. Pressure equalization needs to be addressed by engineer of record. | MARKB | MARKB | | HSP | P | 6926411 |
OLSON PLUMBING & HEATING COMPANY | HRR | P | 03/26/2021 | PER DEMOLITION PAGE FOR ROOF THERE IS A NOTE ABOUT A NEW CHILLER, NEED TO ASK CONTRACTOR NEXT TRIP. STEAM PIPING, HOT WATER AND DRAIN PIPING ABOVE CEILING AT STEAM DISTRIBUTION TUBE AT DUCT WORK WITH PIPING AND PUMP PIPING COMPLETE AT MRI EQUIPMENT ROOM #1. PARTIAL OK TO INSULATE PIPING UP STREAM OF HEAT EXCHANGER. MRI SIDE OF HEAT EXCHANGER IS NOT CHARGED YET. NEED TO SEE DRAIN TERMINATION IN BASEMENT. SEE PAGE 35 ON BLUE BEAM READER FOR THIS INSPECTION FOR PIPING. | JON | JON | | HRR | P | 6913057 |
MECHONE, INC. | HD | P | 03/25/2021 | FOR FINAL - Install access doors for TB1-1 per detail 2 on sheet P2-M4.3. Need pressure equalization opening per note M13 (sheet P2-M 1.1), Oxygen monitoring per note M30 (sheet P2-M 1.1) Provide test and balance report. ABOVE CEILING DUCT - FCU-1 SUPPLY/RETURN/GRILLS COMPLETE, TB-1-1 SUPPLY/RETURN/HUMIDIFIER AND CONNECTIONS TO ROOM COMPLETE & ER-1 DUCT COMPLETE. ROOF - QUENCH VENT COMPLETE PER SHEET P2-M4.2 AND EF2-1 COMPLETE WITH BACK-DRAFT DAMPER. | MARKB | MARKB | | HD | P | 6910389 |
MECHONE, INC. | HD | P | 03/05/2021 | SUPPLY AND RETURN DUCTS AND DUCT WRAP OK IN 2 SOFFITS ONLY IN NEW MRI ROOM PLAN PAGE P2-M 1.1. WILL NEED TO SEE ALL THE REST OF THE DUCT SYSTEMS INCLUDING EXHAUST DUCT FOR THIS MRI ROOM WHEN READY. STILL NEED QUENCH VENT INSPECTION WHEN READY. NO EQUIPMENT YET | JON | JON | | HD | P | 6890169 |
GERALD H PHIPPS INC | XPS | T | 04/14/2021 | PAID (REC#1764624): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 2 revisions: P2-P3.1 adjusted plumbing plan phase 2 | SHANEN | SHANEN | | XPS | T | 6933021 |
OLSON PLUMBING & HEATING COMPANY | XMS | P | 04/07/2021 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised sheet note for removed chiller curb | JUSTINC | JUSTINC | | XMS | P | 6924954 |
GERALD H PHIPPS INC | XES | T | 02/17/2021 | PAID (REC#1754267): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Add FC-1 | SHELBY | SHELBY | | XES | T | 6872574 |
GERALD H PHIPPS INC | XMS | T | 01/20/2021 | PAID (REC#1746495): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised piping | JUSTINC | JUSTINC | | XMS | T | 6842424 |