CRADDOCK DEVELOPMENT COMPANY, INC. | B= | C | 06/11/2021 | | BOBF | BOBF | | B= | C | 7000313 |
CRADDOCK DEVELOPMENT COMPANY, INC. | B= | L | 06/10/2021 | Call ahead completed at 1:14, door was locked at 1:55, no access | BOBF | BOBF | | B= | L | 6998235 |
CRADDOCK DEVELOPMENT COMPANY, INC. | B= | P | 05/19/2021 | need pipe protection under break room sink / need to complete plumb and mech finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): HOMELAND MECHANICAL LLC Mechanical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 6973562 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | P | 04/12/2021 | pending completion of other required inspections - need to splice plans with revisions of location of electric and It room, rest of framing at entry and infill areas okay / need to attach mech to permit / reviewed accessible elements including max height at break room sink | BOBF | BOBF | | BFR | P | 6929874 |
LIVE WIRE ELECTRICAL, LLC | E= | C | 05/12/2021 | | CRAIG | CRAIG | | E= | C | 6965665 |
LIVE WIRE ELECTRICAL, LLC | ER | P | 04/07/2021 | Walls. Ok. Need approved set of plans on site | CRAIG | CRAIG | | ER | P | 6925445 |
HOMELAND MECHANICAL LLC | H= | C | 06/04/2021 | TAB REPORT AND ENGINEER APPROVAL LETTER RECEIVED - PLAN REVISION IS COMPLETE | JERRYF | JERRYF | | H= | C | 6990759 |
HOMELAND MECHANICAL LLC | H= | P | 05/12/2021 | PLANS SHOW FIRE DAMPERS FOR SUPPLY AND RETURN AIR DUCTS AT WALL INTO OPEN OFFICE 104, NO FIRE DAMPERS INSTALLED. PER LIFE SAFETY PLAN AND CONVERSATION WITH CONTRACTOR, THIS DOES NOT APPEAR TO BE A FIRE RATED WALL. WILL NEED REVISED/APPROVED PLANS IF DAMPERS WILL NOT BE INSTALLED. NEED TO INSTALL RELOCATED THERMOSTAT IN CRAFT 103. PROVIDE TEST AND BALANCE REPORT FOR FINAL. ALL OTHER SUPPLY/RETURN AIR DUCTS, FLEX AND DIFFUSERS INSTALLED. TRANSFER FAN INSTALLED. | DUSTINS | DUSTINS | | H= | P | 6966672 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 05/24/2021 | see images of contractor provided photos of corrections | JOHNS | JOHNS | | P= | C | 6977815 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 05/19/2021 | need to seal sink to top of cab, need tempering @ sink, need trap guard insulation @ sink trap, UPLOADED images to complete, rest ok | JOHNS | JOHNS | | P= | P | 6973598 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 04/14/2021 | bldg tracking permit attachments | JOHNS | JOHNS | | PTO | C | 6933435 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 04/06/2021 | GC to attach mech / elec permits
need plastic x plastic mission band @ vent tie in above mens bath, uploaded image and permit attachments to complete, rest ok for added sink and disposal only. NOTE: vtr (existing) | JOHNS | JOHNS | | PTO | P | 6923164 |
LIVE WIRE ELECTRICAL, LLC | XES | P | 05/21/2021 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: Revised one-line | DANIELG | DANIELG | | XES | P | 6976426 |
HOMELAND MECHANICAL LLC | XMS | P | 05/18/2021 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised CFM | JUSTINC | JUSTINC | | XMS | P | 6971873 |
CRADDOCK DEVELOPMENT COMPANY, INC. | XBS | T | 05/17/2021 | PAID (REC#1773839): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add electrical room and closet. | MICHAELA | MICHAELA | | XBS | T | 6970821 |