ECHO CONSTRUCTION AND REMODELING INC. | B= | C | 04/12/2022 | Items corrected | TRENTP | TRENTP | | B= | C | 7335177 |
ECHO CONSTRUCTION AND REMODELING INC. | B= | R | 03/18/2022 | Missing CO detector outside of main level bedrooms, to be hardwired / Missing safety glazing in multiple windows less than 60 inches from waters edge of hot tub and 60 inches in height from walking surface in hot tub room / Need to complete final grade on west side of house / Slab on grade, no deck, no AC. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | TRENTP | TRENTP | | B= | R | 7307212 |
ECHO CONSTRUCTION AND REMODELING INC. | BSP | P | 03/18/2022 | Changed to BSP/ Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 on file / | TRENTP | TRENTP | | BSP | P | 7306279 |
ECHO CONSTRUCTION AND REMODELING INC. | BLA | C | 03/01/2022 | | TRENTP | TRENTP | | BLA | C | 7285656 |
ECHO CONSTRUCTION AND REMODELING INC. | BLA | P | 02/07/2022 | Lath still incomplete at northern and southern most windows for western balloon wall, still need to observe lath once windows are installed / Rest of lath okay | TRENTP | TRENTP | | BLA | P | 7261831 |
ECHO CONSTRUCTION AND REMODELING INC. | BIN | C | 12/10/2021 | Installers certificate and evaluation report for spray foam insulation received on site / Will need to inspect blown in insulation section of attic at final, need air leakage test result by final | TRENTP | TRENTP | | BIN | C | 7205581 |
ECHO CONSTRUCTION AND REMODELING INC. | BFR | C | 12/06/2021 | Letters for frame items and hardware fasteners on file | TRENTP | TRENTP | | BFR | C | 7197766 |
ECHO CONSTRUCTION AND REMODELING INC. | BLA | P | 12/03/2021 | Lath incomplete around windows on all elevations at throughout west elevation / Rest of areas for lath okay | TRENTP | TRENTP | | BLA | P | 7197424 |
ECHO CONSTRUCTION AND REMODELING INC. | BFR | P | 12/02/2021 | Need to upload engineer letter viewed onsite for additional frame changes electronically / Incorrect fasteners used in HUS/HGUS hangers on upper floor / Slab grade, no deck | TRENTP | TRENTP | | BFR | P | 7195535 |
ECHO CONSTRUCTION AND REMODELING INC. | BSP | P | 12/02/2021 | Changed to BSP / Engineer letters for straps at beams and base plates on file | TRENTP | TRENTP | | BSP | P | 7194518 |
ECHO CONSTRUCTION AND REMODELING INC. | BSP | R | 11/24/2021 | Inspection stopped and changed to BSP after too many items, need full re inspection / Contractor to review all hardware requirements and notes in plans, need to review fastener requirements for simpson strong tie hardware / Update by TP, after further review, Note: Future dry runs may result in trip fee | TRENTP | TRENTP | | BSP | R | 7188508 |
ECHO CONSTRUCTION AND REMODELING INC. | BFN | C | 06/24/2021 | Engineer letter for foundation design bearing capacity on file | TRENTP | TRENTP | | BFN | C | 7013894 |
ECHO CONSTRUCTION AND REMODELING INC. | BFN | P | 06/22/2021 | Foundation design bearing capacity provided (5000 PSF) does not match the bearing capacity of the open hole on file (3000 PSF) / Engineer letter for foundation on file -- Eufer noted / | TRENTP | TRENTP | | BFN | P | 7010288 |
ECHO CONSTRUCTION AND REMODELING INC. | BFT | C | 06/22/2021 | soils and open hole on file -- 3000 PSF -- no drain -- 10% / footing and foundation observation on file - ufer noted / Note: Foundation design bearing capacity does not match open hole bearing | TRENTP | TRENTP | | BFT | C | 7010282 |
ECHO CONSTRUCTION AND REMODELING INC. | BFN | P | 06/21/2021 | Complete BFT / Provide foundation design / Foundation observation on file -- Pier observation on file -- Ufer noted | CHAD | CHAD | | BFN | P | 7008806 |
ECHO CONSTRUCTION AND REMODELING INC. | BFT | P | 06/21/2021 | Provide open hole and soils report / Footer observation on file | CHAD | CHAD | | BFT | P | 7008799 |
ECHO CONSTRUCTION AND REMODELING INC. | BFI | C | 06/18/2021 | R10 installed at entire perimeter / Note: Need to complete BFT and BFN | TRENTP | TRENTP | | BFI | C | 7008008 |
ECHO CONSTRUCTION AND REMODELING INC. | BFT | P | 04/19/2021 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFT | P | 6938309 |
ECHO CONSTRUCTION AND REMODELING INC. | BFN | P | 04/19/2021 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFN | P | 6938308 |
719 ELECTRIC INC | E= | C | 03/14/2022 | 50 amp hot-tub | TOMC | TOMC | | E= | C | 7300007 |
719 ELECTRIC INC | E= | P | 03/07/2022 | if separate permit is pulled for hot-tub house can be finaled | TOMC | TOMC | | E= | P | 7292056 |
719 ELECTRIC INC | ES | C | 03/07/2022 | Residential Underground: 200-amp 3 Wire New Residence ok to set meter. / | TOMC | TOMC | | ES | C | 7292052 |
719 ELECTRIC INC | ER | C | 11/09/2021 | no mcc, no vac, ufer and dryer booster must be accessible at final #6 al hot tub, required south wall receptacles will be surface mounted at final | BRET | BRET | | ER | C | 7170435 |
719 ELECTRIC INC | EUG | C | 11/05/2021 | conductors 15 short of make it to utility pole | BRET | BRET | | EUG | C | 7167307 |
719 ELECTRIC INC | ER | R | 11/05/2021 | land all cables and make up grounds in panel, ground metal box under panel, missing outlet for dryer booster fan, add outlet to both main floor bedrooms at closet switch walls, add receptacle to wall space at great room sliders within 6' of each side of slider, s.w room not wired , add receptacle loft east handrail receptacle on wall over 6' from start of wall, make masterbath outlet, rough in exterior receptacle per NEC, complete re-inspect | BRET | BRET | | ER | R | 7167303 |
ADVANTAGE HEATING AND COOLING | H= | C | 03/10/2022 | Whole house ventilation being achieved through exhaust fan located in bathroom / Whole house ventilation switch located in bathroom / NOTE / DIRECT VENT BOILER / NO A/C / | JHORSMAN | JHORSMAN | | H= | C | 7297606 |
ADVANTAGE HEATING AND COOLING | HRR | C | 11/24/2021 | AFTER FURTHER REVIEW OF INSTALLATION INSTRUCTIONS FOR BOILER VENTING, MATERIAL USED IN VENTING PRACTICES ONLY REQUIRES 1/4 INCH SLOPE BACK TO APPLIANCE, VENTING INSTALLED IS OK. | JHORSMAN | JHORSMAN | | HRR | C | 7188035 |
ADVANTAGE HEATING AND COOLING | HRR | P | 11/23/2021 | BOILER VENTING STILL LACKS PROPER SLOPE, FOR THE CURRENT LENGTH IN THE GARAGE 12 1/2 INCHES OF SLOPE IS REQUIRED FOR THE 20 FOOT LENGTH OF HORIZONTAL VENT IN THE GARAGE SOFFIT/ | JHORSMAN | JHORSMAN | | HRR | P | 7187528 |
ADVANTAGE HEATING AND COOLING | HWP | C | 11/22/2021 | 50 LB TEST ON ONE UPPER LEVEL ZONE OK | JHORSMAN | JHORSMAN | | HWP | C | 7184924 |
ADVANTAGE HEATING AND COOLING | HRR | P | 11/22/2021 | PER PAGE 10 OF THE VENT MANUAL 5/8 INCH SLOPE BACK TO APPLIANCE PER FOOT OF HORIZONTAL RUN/ MANUAL DOES NOT SHOW CONCENTRIC TERMINATION, SEE PAGES 18 AND 19/ | JHORSMAN | JHORSMAN | | HRR | P | 7184913 |
ADVANTAGE HEATING AND COOLING | HSP | P | 11/22/2021 | VENT SUPPLEMENT MANUAL RECEIVED, SEE IMAGES | JHORSMAN | JHORSMAN | | HSP | P | 7184625 |
ADVANTAGE HEATING AND COOLING | HRR | P | 11/18/2021 | AT FINAL PROVIDE ACCESS TO DRYER BOOSTER FAN, AND LABEL DRYER EXHAUST DUCT PER IRC M1502.4.6/ PROVIDE VENT SUPPLEMENT MANUAL TO VERIFY VENTING PRACTICES/ SEAL JOINT BETWEEN DRYER EXHAUST DUCT AND BOOSTER FAN IN SOFFIT | JHORSMAN | JHORSMAN | | HRR | P | 7181817 |
ADVANTAGE HEATING AND COOLING | HRR | P | 11/18/2021 | BOILER AND DRYER BOOSTER FAN INSTALLATION INSTRUCTIONS RECEIVED, SEE IMAGES | JHORSMAN | JHORSMAN | | HRR | P | 7181276 |
ADVANTAGE HEATING AND COOLING | HRR | P | 11/16/2021 | PROVIDE BOILER INSTALLATION INSTRUCTIONS TO VERIFY VENTING PRACTICES/ PROVIDE INSTALLATION INSTRUCTIONS FOR DRYER EXHAUST DUCT BOOSTER FAN | JHORSMAN | JHORSMAN | | HRR | P | 7178485 |
R AND D PLUMBING | HO | C | 11/10/2021 | 10 LB TEST OK/ ADDED 40 FEET OF 1/2 INCH PE WITH TRACER WIRE FROM PROPANE TANK TO BACK OF HOUSE/ OK TO COVER | JHORSMAN | JHORSMAN | | HO | C | 7171663 |
ADVANTAGE HEATING AND COOLING | HRR | P | 11/08/2021 | INSTALL FRAMING AROUND DRYER EXHAUST DUCT/ INSTALL FRAMING AROUND BOILER VENTING/ PROVIDE INSTALLATION INSTRUCTIONS FOR BOILER/ PROVIDE INSTALLATION INSTRUCTION FOR DRYER EXHAUST BOOSTER FAN/ Whole house ventilation being achieved through exhaust fan located in bathroom. / Verify whole house ventilation switch location at final / NOTE / DIRECT VENT BOILER / NO A/C / | JHORSMAN | JHORSMAN | | HRR | P | 7168470 |
R AND D PLUMBING | HI | C | 10/26/2021 | 10 LB TEST OK / 1 INCH MAIN / 1 BOILER / 1 RANGE / | JHORSMAN | JHORSMAN | | HI | C | 7154447 |
ADVANTAGE HEATING AND COOLING | HWP | C | 07/28/2021 | 50 LB TEST OK / R-10 INSULATION BOARD IN PLACE / OK TO COVER PER MECHANICAL ONLY / THIS INSPECTION FOR THE GROUND LEVEL OF HOME ONLY / **INSPECTION STATUS AT PARTIAL DUE TO ANOTHER HWP INSPECTION IS NEEDED FOR THE UPPER FLOOR OF THE HOME** | BILLS | BILLS | | HWP | C | 7053128 |
ECHO CONSTRUCTION AND REMODELING INC. | HWP | T | 07/28/2021 | PAID (REC#1794056) AFTER-HOURS INSPECTION: $200 From: JANE Per Jon. B | JANE | JANE | | HWP | T | 7052628 |
R AND D PLUMBING | P= | C | 03/17/2022 | POTABLE WATER CERT IN IMAGES | LEE | LEE | | P= | C | 7304857 |
R AND D PLUMBING | P= | P | 03/16/2022 | NEED POTABLE WATER CERT. ATTACHED TO PERMIT REQUEST -- REST OK | LEE | LEE | | P= | P | 7303234 |
R AND D PLUMBING | P= | P | 03/14/2022 | MISSING HAMMER ARRESTOR AT DISH WASHER -- REMOVE CAP ON VTR -- TERMINATE T&P DRAINS ON THE VERTICAL WITH CODE REQUIRED AIR GAPS -- NEED POTABLE WATER CERT. -- REST OK | LEE | LEE | | P= | P | 7299684 |
HOMEOWNER | PWO | C | 02/08/2022 | need certificate of potable water by final. | TAYLOR | TAYLOR | | PWO | C | 7263300 |
R AND D PLUMBING | PTO | C | 10/26/2021 | still need PWO inspection, rest ok note: no irrigation, vtr 1, cap on vent thru roof, aav @ laundry room, 1st floor lav, check water heater at final | JOSEPHD | JOSEPHD | | PTO | C | 7154656 |
R AND D PLUMBING | PB | C | 07/15/2021 | will need pwo inspection | JOSEPHD | JOSEPHD | | PB | C | 7037074 |