GATEWAY PROPERTY SOLUTIONS LTD | B= | P | 05/11/2022 | pending completion of all other required inspections, building okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), VASQUEZ ELECTRIC LLC Electrical Final Inspection is not Completed yet, NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 7371658 |
GATEWAY PROPERTY SOLUTIONS LTD | B= | P | 03/02/2022 | Need to complete mech, elec and plumb finals, provide ANSI compliant signage at locker rooms / maximum height to top of sink in Cafe is 34", need to complete sink hook up in cafe -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), SYSTEMS ELECTRIC, INC. Electrical Final Inspection is not Completed yet, VASQUEZ ELECTRIC LLC Electrical Final Inspection is not Completed yet, NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet, SM PLUMBING & MECHANICAL, LLC Plumbing Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 7287114 |
GATEWAY PROPERTY SOLUTIONS LTD | BSP | P | 01/28/2022 | reviewed requirements for threshold at roll in shower and acceptable materials for protecting walls in bathroom stalls | BOBF | BOBF | | BSP | P | 7253420 |
GATEWAY PROPERTY SOLUTIONS LTD | BFR | P | 12/28/2021 | Wall framing at cafe OK | JEREMYA | JEREMYA | | BFR | P | 7222398 |
GATEWAY PROPERTY SOLUTIONS LTD | BFR | P | 08/20/2021 | pending completion of other required inspections, wall framing for showers, locker room and and restrooms okay | BOBF | BOBF | | BFR | P | 7079542 |
GATEWAY PROPERTY SOLUTIONS LTD | BFR | P | 08/04/2021 | pending other required inspections, framing for gym area only okay / Please note plans indicate trnsfer showers in locker room but are actually sized similar to rollin showers, rollin showers must be a minimum of 60" wide at finish , currently 60" wide with one side drywall and no tile installed, by finish will be less than 59" , size of must be 36" x 36" and no larger / training with Christine K, reviewed elements of rollin and transfer showers | BOBF | BOBF | | BFR | P | 7060230 |
GATEWAY PROPERTY SOLUTIONS LTD | BSP | P | 08/04/2021 | Training with Bob F / Reviewed elements of accessible transfer vs roll in showers | CHRISTINEH | CHRISTINEH | | BSP | P | 7060224 |
VASQUEZ ELECTRIC LLC | E= | P | 05/03/2022 | cafe ok / | BRIAN | BRIAN | | E= | P | 7361443 |
VASQUEZ ELECTRIC LLC | ESP | P | 04/27/2022 | contractor provided specs for the 'vending machines' and they do not meet the NEC definition so would only require GFCI protection if within 6' of a sink / pop up receps in table are not required to be listed for countertops unless in a countertop | MATTHEW | MATTHEW | | ESP | P | 7355018 |
VASQUEZ ELECTRIC LLC | E= | R | 04/25/2022 | need kitchen rated pop ups in the counter top the ones installed are for a conference table / need breaker locks in the breaker for the fireplace / need gfci protection on the vending area or have the machines on site to verify it is built in / check panel on hallway inspection / this was for the cafeteria / | BRIAN | BRIAN | | E= | R | 7350480 |
VASQUEZ ELECTRIC LLC | E= | L | 04/22/2022 | No access. Cancelled by contractor via phone after inspector arrived. | CHIPO | CHIPO | | E= | L | 7348571 |
SYSTEMS ELECTRIC, INC. | E= | C | 03/08/2022 | Phase 1 complete for Systems Electric only | CHIPO | CHIPO | | E= | C | 7293508 |
VASQUEZ ELECTRIC LLC | ER | C | 01/25/2022 | rough in okay | CHIPO | CHIPO | | ER | C | 7249849 |
VASQUEZ ELECTRIC LLC | ER | R | 01/24/2022 | called contractor when on site , went to voice mail left message to call me back for access and location of inspection. after 10 min i left and rejected inspection / | BRIAN | BRIAN | | ER | R | 7248126 |
VASQUEZ ELECTRIC LLC | ER | P | 01/12/2022 | rough in for walls okay | CHIPO | CHIPO | | ER | P | 7236592 |
VASQUEZ ELECTRIC LLC | ER | R | 01/11/2022 | no poc on site / door locked no access / | BRIAN | BRIAN | | ER | R | 7234851 |
SYSTEMS ELECTRIC, INC. | E= | P | 12/02/2021 | gym / surrounding corridors / bathrooms for phase 1 only see plans E 3.1 and E 4.1 | CRAIG | CRAIG | | E= | P | 7195428 |
SYSTEMS ELECTRIC, INC. | ER | C | 08/24/2021 | Above ceilings in two restrooms next to gym and can lights in ceiling outside of restrooms okay - rough in complete | CHIPO | CHIPO | | ER | C | 7083371 |
SYSTEMS ELECTRIC, INC. | ESL | C | 07/02/2021 | | BRIAN | BRIAN | | ESL | C | 7024448 |
SYSTEMS ELECTRIC, INC. | ER | P | 06/11/2021 | partial walls still need to see the under ground connection to finish walls /rest ok / see plans marked in orange / | BRIAN | BRIAN | | ER | P | 6999535 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | C | 05/11/2023 | DUCT MATCHES SPLICE. | MARKB | MARKB | | H= | C | 7741889 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | P | 05/10/2023 | FINAL PENDING - Need on site final inspection. SPLICE ON FILE. TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | P | 7740346 |
NIELSEN MECHANICAL CONTRACTORS, LLC | HE | L | 05/09/2023 | Renewed for No Fee at 5/9/2023 9:12:04 AM | ASHLEYL | ASHLEYL | | HE | L | 7739098 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/31/2022 | PHASE 2 (GRAB N GO CAFETERIA): ABOVE CEILING DUCT - Duct installed per un approved plan (delta 4) - Will need approved plan splice or install per plan. PHASE 1: ACCESS FOR EF-1 FAN IN WOMENS BATHROOM COMPLETE. | MARKB | MARKB | | HD | P | 7255046 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 01/13/2022 | NO PICTURE ATTACHED TO INSPECTION REQUEST | MARKB | MARKB | | H= | P | 7238527 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 01/06/2022 | FINAL PARTIAL FOR MEN'S 102, WOMEN'S 107 & GYM 101 ONLY PENDING - Provided 24"x24" access for EF-1 above women's hard lid per code and plan. provide test and balance report. TRANSFERS, GRILLS AND CONTROLS COMPLETE. Still need all inspections on cafe.
| MARKB | MARKB | | H= | P | 7231060 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 07/23/2021 | ABOVE CEILING DUCT - ALL ROUGH DUCT COMPLETE. VAV'S INSTALLED. ALL HANGERS COMPLETE. Will Need proper service access and removal openings installed in hard lids. All volume dampers that lack required access will need to be permanently fastened open if using OBD'S. | MARKB | MARKB | | HD | P | 7046950 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | L | 07/21/2021 | Cancelled at call ahead by contractor | MARKB | MARKB | | HD | L | 7044544 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 06/30/2021 | FITNESS CENTER PLAN SHEET M-1.2: ABOVE CEILING DUCT - MEDIUM/LOW PRESSURE/EXHAUST, MAINS/BRANCHES DUCT FROM CORRIDOR INTO FITNESS AND LOCKER ROOMS OK TO WRAP FOR 2 FAN POWERED BOXES, 1 VAV AND EF-1. 28X16 TRANSFERS IN FITNESS ROOM COMPLETE. Will need permanent access provided above hard lid for VAV, EF-1 and volume dampers. FPB'S, VAV, flex, diffusers not installed at this time. | MARKB | MARKB | | HD | P | 7020662 |
SM PLUMBING & MECHANICAL, LLC | P= | C | 04/25/2022 | | CODYP | CODYP | | P= | C | 7350279 |
SM PLUMBING & MECHANICAL, LLC | P= | P | 02/01/2022 | ok for women's accessible stall corrections only
--STILL NEED P= @ CAFE AREA | JOHNS | JOHNS | | P= | P | 7257190 |
SM PLUMBING & MECHANICAL, LLC | PTO | C | 02/01/2022 | see 1/27/22 PTO notes for @ final requirements | JOHNS | JOHNS | | PTO | C | 7257189 |
SM PLUMBING & MECHANICAL, LLC | PTO | P | 01/28/2022 | dwv not on test, still need to insulate water per plan / IECC TO INCLUDE water htr piping with first 8' of cold off water htr insulated (per IECC), sink configuration not per plan? (where's the water htr drain pan going to terminate), rest ok | JOHNS | JOHNS | | PTO | P | 7253751 |
SM PLUMBING & MECHANICAL, LLC | PTO | P | 01/27/2022 | --NEED engineers letter allowing aav @ sink in lieu of vtr (per plans)
lost test @ dwv, water test to be 50 or 100# (currently 70#), insulate all waters per plan / IECC, missing vacuum relief valve @ water htr (per plans), sink configuration not per plan (where is the water htr drain pan going to terminate), rest ok.
NOTE: --BY FINAL all exposed waters to include water htr piping to be insulated, --BY FINAL sink drain configuration to be per plan, aav- sink, verify all bfp noted on plan page p1.1
--STILL NEED PREVIOUS P= CORRECTION | JOHNS | JOHNS | | PTO | P | 7252215 |
SM PLUMBING & MECHANICAL, LLC | PB | C | 01/21/2022 | ok for remainder of PB (cafe 100)
--STILL NEED PREVIOUS P = CORRECTIONS | JOHNS | JOHNS | | PB | C | 7246019 |
SM PLUMBING & MECHANICAL, LLC | P= | P | 01/07/2022 | after new partition was added stall width is 59 1/4" (60" minimum required) on site inspection required once corrections are made --STILL NEED REMAINDER OF AREAS PB / PTO / AND P= | JOHNS | JOHNS | | P= | P | 7232270 |
SM PLUMBING & MECHANICAL, LLC | PTO | P | 12/10/2021 | ok for PTO corrections @ mens and womens locker room / baths only
--STILL NEED REMAINDER OF AREAS PB / PTO / AND P= | JOHNS | JOHNS | | PTO | P | 7204770 |
SM PLUMBING & MECHANICAL, LLC | P= | P | 12/10/2021 | womens accessible water closet more than 18" of side partition, rest ok for mens and womens locker room / bath ONLY
--STILL NEED REMAINDER OF AREAS PB / PTO / AND P= | JOHNS | JOHNS | | P= | P | 7204767 |
SM PLUMBING & MECHANICAL, LLC | PTO | P | 08/09/2021 | ok for engineers letter deleting re circ and allowing current water tie in locations only, all other corrections / areas still apply | JOHNS | JOHNS | | PTO | P | 7064541 |
SM PLUMBING & MECHANICAL, LLC | PTO | P | 07/30/2021 | ok for lower level mens / womens locker and baths only today. lavs are pre existing and only changing out fixtures
need to insulate waters per plan / IECC reqs, still need remainder of --PB and PTO--, rest ok for this area only. NOTE: vtr (existing)
| JOHNS | JOHNS | | PTO | P | 7055166 |
SM PLUMBING & MECHANICAL, LLC | PB | P | 06/07/2021 | ok for Engineers letter for material used and hammer arrestor inquiry only, see images
STILL NEED remainder
ins note only: refer to e letter for hammerr arrestor inquiry , etc. | JOHNS | JOHNS | | PB | P | 6992879 |
SM PLUMBING & MECHANICAL, LLC | PB | P | 06/03/2021 | NEED engineers approval letter for abs (cast on plans) and to allow trap guards in lieu of trap primers (listed on plans)
ok for mens / womens locker shwrs only today
STILL NEED remainder | JOHNS | JOHNS | | PB | P | 6989356 |
NIELSEN MECHANICAL CONTRACTORS, LLC | XMS | T | 05/09/2023 | PAID (REC#1953220): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout revised | JUSTINC | JUSTINC | | XMS | T | 7739426 |
GATEWAY PROPERTY SOLUTIONS LTD | XBS | T | 09/03/2021 | PAID (REC#1812238): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Reduced scope of work | MICHAELA | MICHAELA | | XBS | T | 7096006 |
GATEWAY PROPERTY SOLUTIONS LTD | XBS | P | 08/02/2021 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Reduce scope of work | MICHAELA | MICHAELA | | XBS | P | 7057074 |