CUSITECH LLC | B= | C | 02/22/2022 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 7278499 |
CUSITECH LLC | B= | P | 11/04/2021 | . Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), RIAL HEATING & AIR COND, INC Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 7165745 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 10/21/2021 | stenciling rated walls above grid okay | BOBF | BOBF | | BSP | P | 7149766 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 10/06/2021 | above ceiling penetration protection and head wall okay, talked to contractor about stenciling rated walls above grid ceiling | BOBF | BOBF | | BSP | P | 7131929 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 09/28/2021 | pending completion of splice revising listed wall to UL U 425, drywall install at rated walls okay | BOBF | BOBF | | BSP | P | 7122242 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 09/22/2021 | pending completion of all other required inspections, interior wall framing okay / please note, rated walls are still U419, propriatary to USG drywall, american is installed, will need to splice revised listed system and inspect all rated walls prior to finishing | BOBF | BOBF | | BFR | P | 7116765 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 07/27/2021 | framing at common wall between 104 and 100 okay and wall between 121 and 100 okay | BOBF | BOBF | | BFR | P | 7050215 |
PEAK PROFESSIONAL CONTRS INC | BFR | R | 07/21/2021 | demo was not completed for office 114 where new rated walls are to be installed, need continuous studs to deck / listed wall assembly is a u 419 that is propriatary to USG drywall, american has been installed on 1 side of rated walls for rooms 101, 105, 106 and 114, wall framing for 101, 105, 106, 114 and 102 okay, need to complete other required inspections | BOBF | BOBF | | BFR | R | 7043783 |
STILSON ELECTRIC SYSTEMS, INC. | E= | C | 02/09/2022 | FIRE ALARM INSPECTION: | CRAIG | CRAIG | | E= | C | 7264520 |
STILSON ELECTRIC SYSTEMS, INC. | ER | C | 02/09/2022 | FIRE ALARM INSPECTION: | CRAIG | CRAIG | | ER | C | 7264502 |
STILSON ELECTRIC SYSTEMS, INC. | E= | C | 02/09/2022 | FIRE ALARM INSPECTION: | CRAIG | CRAIG | | E= | C | 7264503 |
SYSTEMS ELECTRIC, INC. | E= | C | 10/22/2021 | | CRAIG | CRAIG | | E= | C | 7151815 |
SYSTEMS ELECTRIC, INC. | ER | C | 10/22/2021 | ABOVE CEILING OK | CRAIG | CRAIG | | ER | C | 7151804 |
SYSTEMS ELECTRIC, INC. | ER | P | 09/22/2021 | WALL IN ROOM 121 OK | CRAIG | CRAIG | | ER | P | 7116329 |
SYSTEMS ELECTRIC, INC. | ER | P | 07/21/2021 | rough in for new walls as per plans okay | CHIPO | CHIPO | | ER | P | 7044112 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 11/05/2021 | ALL CORRECTIONS MADE NOTES: NO TAB REPORT REQUIRED | JERRYF | JERRYF | | H= | C | 7167009 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 10/22/2021 | LABEL ALL FIRE DAMPER ACCESS DOORS / MISSING 1 SUPPLY AND 3 RETURN GRILLES IN ROOM 119 | JERRYF | JERRYF | | HD | P | 7151946 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 10/13/2021 | NEED TO REMOVE SCREWS AT RETAINING ANGLES IN WALLS - WILL VERIFY AT FINAL (LEAVE TILES OUT AT ALL DAMPER LOCATIONS NOTES: RETAINING ANGLES OK PENDING VERIFICATION OF REMOVAL OF SCREWS - ALL BREAKAWAY CONNECTIONS AND ACCESS DOORS ARE COMPLETE | JERRYF | JERRYF | | HD | P | 7140412 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 10/07/2021 | STILL NEED 32 X 18 DAMPER INSTALLED AND ALL DUCT SEALANT BEFORE INSULATION - WILL VERIFY SECOND ANGLES AT FUTURE INSPECTION NOTES: ALL OTHER DAMPER GAP AND 1ST SET OF ANGLES OK OK 1 SIDE | JERRYF | JERRYF | | HD | P | 7134052 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 10/01/2021 | NOTE / 32 X 18 FIRE DAMPER FRAMING OK / | JERRYF | JERRYF | | HD | P | 7127637 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 09/23/2021 | STILL NEED 32 X 18 FIRE DAMPER FRAMING INSPECTED WHEN READY NOTES: ALL OTHER FIRE DAMPER OPENINGS ARE COMPLETE | JERRYF | JERRYF | | HD | P | 7118113 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 09/22/2021 | NEED OPEN HOLES COVERED WITH TRACK AT FIRE DAMPERS | JERRYF | JERRYF | | HD | P | 7115757 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | L | 07/01/2021 | WRONG PERMIT CALLED FOR INSPECTION INSPECTION WAS FOR UNIT 225 | JERRYF | JERRYF | | HD | L | 7022539 |
PEAK PROFESSIONAL CONTRS INC | XBS | T | 09/28/2021 | PAID (REC#1810642): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised corridor assembly | SHELLEY | SHELLEY | | XBS | T | 7122587 |
RIAL HEATING AND AIR CONDITIONING, INC. | XMS | T | 09/10/2021 | PAID (REC#1805985): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Added dampers, revised layout | JUSTINC | JUSTINC | | XMS | T | 7103593 |