HENSEL PHELPS CONSTRUCTION CO | B= | C | 02/15/2022 | verification of fire stop and termination of smoke partition on file | LONNYS | LONNYS | | B= | C | 7270401 |
HENSEL PHELPS CONSTRUCTION CO | B= | P | 02/11/2022 | smoke partition continuity incomplete to underside of upper floor over A2114 door - complete continuity or provide specs for grid ceiling to verify it is approved to limit the transfer of smoke / fire stop incomplete at penetration above storage room door / gyp fastening corrections OK per UL V489 / rest of building final OK -- Schedule a new Building Final when above items are complete. | LONNYS | LONNYS | | B= | P | 7268080 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 11/30/2021 | GYP ATTACHMENT AT FIRE BARRIER IN CLEAN SUPPLY ROOM // gyp fastening incomplete per UL V489 in surgery supervisors office above duct, around existing concrete beam, and above duct in clean supply room // provide fire stop details for all through penetrating items / reviewed continuity requirements for smoke barrier over A2114 door / HARD LID FRAMING INSPECTION -- hard lids OK / UPDATE: by Lonny S -- Upon Further Review, / wall above A2114 is a smoke partition | LONNYS | LONNYS | | BFR | P | 7191951 |
HENSEL PHELPS CONSTRUCTION CO | BSP | R | 11/23/2021 | GYP ATTACHMENT AT FIRE BARRIER IN CLEAN SUPPLY ROOM // gyp fastening incomplete per UL V489 // provide fire stop details for all through penetrating items / reviewed continuity requirements for smoke barrier over A2114 door / training with Jason B / UPDATE: by Lonny S -- Upon Further Review, / wall above A2114 is a smoke partition | LONNYS | LONNYS | | BSP | R | 7186733 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 11/08/2021 | pending other required inspections // need too attach mech and plumbing permits and complete roughs / smoke partition continuity to upper floor system incomplete over A2114 door - provide tile ceiling assembly for code compliant smoke partition termination / scope of interior light gauge steel framing OK // reviewed rated assemblies and accessible elements with site rep UPDATE: 11-23-21 by Lonny S -- Upon Further Review, / smoke partition noted above is a smoke barrier | LONNYS | LONNYS | | BFR | P | 7168609 |
ENCORE ELECTRIC, INC. | E= | C | 01/25/2022 | | RANDY | RANDY | | E= | C | 7249116 |
ENCORE ELECTRIC, INC. | E= | R | 01/21/2022 | All receptacles within 6' of sink need to be GFCI protected. | AARONR | AARONR | | E= | R | 7246504 |
ENCORE ELECTRIC, INC. | ER | P | 12/29/2021 | drop ceilings ok | RANDY | RANDY | | ER | P | 7223715 |
ENCORE ELECTRIC, INC. | ER | P | 12/03/2021 | all hard lids ok | RANDY | RANDY | | ER | P | 7197539 |
ENCORE ELECTRIC, INC. | ER | P | 11/17/2021 | walls marked on plans | RANDY | RANDY | | ER | P | 7179891 |
MECHONE, INC. | H= | C | 02/03/2022 | TEST AND BALANCE REPORT RECEIVED SEE IMAGES. MECHANICAL FINAL COMPLETE. | TREVORH | TREVORH | | H= | C | 7258042 |
MECHONE, INC. | H= | P | 02/01/2022 | FINAL PENDING-------------TEST AND BALANCE | TREVORH | TREVORH | | H= | P | 7257435 |
MECHONE, INC. | HD | P | 01/10/2022 | FINAL PENDING--------------TEST AND BALANCE REPORT. | TREVORH | TREVORH | | HD | P | 7233477 |
MECHONE, INC. | HD | P | 12/01/2021 | DUCT ROUGH ABOVE HARD LID SOFFIT AT RADIUS WALL : 8 SUPPLY DUCTS, 8 RETURN DUCTS AND REGISTER CANS OK / | LIDO | LIDO | | HD | P | 7194359 |
MECHONE, INC. | HD | P | 11/15/2021 | (DUCT ROUGH) PLAN SHEET M120 BDA PLAN SPLICE PAGE 57 RETURN AIR TO GRILLE LOCATIONS SHOWN OK, EXHAUST DUCTING RAN PER PLAN OK WRAP SUPPLY | TREVORH | TREVORH | | HD | P | 7177025 |
MECHONE, INC. | HD | P | 11/11/2021 | (DUCT ROUGH) PLAN SHEET M120 BDA PLAN SPLICE PAGE 57 -- NEW SUPPLY AIR LATERAL DOWN STREAM OF VAV'S INSTALL PER PLAN OK, OK TO WRAP. AT NEXT INSPECTION REQUEST WILL VERIFY RETURN AIR INSTALL, AND EXHAUST DUCTING. NO FLEX OR REGISTERS AT THIS TIME. | TREVORH | TREVORH | | HD | P | 7173656 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 01/25/2022 | | JOSEPHD | JOSEPHD | | P= | C | 7249539 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 11/30/2021 | clinical sink area ok, note: check overhead water pipe insulation at final | JOSEPHD | JOSEPHD | | PTO | C | 7191482 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 11/29/2021 | over head ok, still need to see water pipe insulation, and vent connections, still need to see under floor by clinical sink, other under floor areas ok | JOSEPHD | JOSEPHD | | PTO | P | 7190246 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 11/18/2021 | in wall ok, still need over head and under floor inspected | JOSEPHD | JOSEPHD | | PTO | P | 7181664 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 12/13/2021 | PAID (REC#1829308): PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Revised wall types | LBENNETT | LBENNETT | | XBS | T | 7206493 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 10/26/2021 | PAID (REC#1817825): PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Revised 1-hour fire barrier assembly | LBENNETT | LBENNETT | | XBS | T | 7154454 |
HENSEL PHELPS CONSTRUCTION CO | XES | P | 08/11/2021 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: As builts | SHELBY | SHELBY | | XES | P | 7069221 |
HENSEL PHELPS CONSTRUCTION CO | XMS | P | 08/11/2021 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Layout and schedule revisions | JUSTINC | JUSTINC | | XMS | P | 7069180 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 08/11/2021 | PAID (REC#1798052): PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Numerous minor revisions | LBENNETT | LBENNETT | | XBS | T | 7068863 |