KIRELLA HOMES, INC | B= | C | 02/10/2022 | All other required Final inspections are complete. (This is a computer generated result) | TRENTP | TRENTP | | B= | C | 7266243 |
KIRELLA HOMES, INC | B= | P | 02/04/2022 | Items corrected. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | TRENTP | TRENTP | | B= | P | 7260499 |
KIRELLA HOMES, INC | BIN | C | 02/04/2022 | Changed to BIN / Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 on file / | TRENTP | TRENTP | | BIN | C | 7259632 |
KIRELLA HOMES, INC | BIN | P | 02/03/2022 | ES Reports for foam insulation on file / still need air leakage report | DANE | DANE | | BIN | P | 7258624 |
KIRELLA HOMES, INC | BIN | P | 02/03/2022 | Still need to provide air leakage test results / Need to provide evaluation report for spray foam insulation used per installers certificate provided / Installers certificate for spray foam insulation on file | TRENTP | TRENTP | | BIN | P | 7258158 |
KIRELLA HOMES, INC | B= | P | 01/28/2022 | still need to provide insulation certs and provide Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 to complete BIN / missing gutters and down spouts / rest of final OK / slab - no decks - A/C in -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | LONNYS | LONNYS | | B= | P | 7253710 |
KIRELLA HOMES, INC | BLA | C | 11/23/2021 | | TRENTP | TRENTP | | BLA | C | 7187399 |
KIRELLA HOMES, INC | BIN | P | 11/09/2021 | Need installers certificate of applied insulation and installation thickness uploaded / Insulation ok / | ERIKK | ERIKK | | BIN | P | 7170555 |
KIRELLA HOMES, INC | BFR | C | 11/02/2021 | Items corrected | TRENTP | TRENTP | | BFR | C | 7163048 |
KIRELLA HOMES, INC | BFR | P | 11/02/2021 | Engineer letter for balloon framed wall on file / Pending field inspection of corrections | TRENTP | TRENTP | | BFR | P | 7162081 |
KIRELLA HOMES, INC | BFR | R | 10/18/2021 | Need to provide clarification from licensed design professional for balloon wall built over 10ft per R602.3(5) / Missing all windows and doors for dry in / Need to complete fireblocking/draftstopping throughout / Slab on grade, no deck | TRENTP | TRENTP | | BFR | R | 7145378 |
KIRELLA HOMES, INC | BSP | P | 10/18/2021 | Changed to BSP / Updated porch framing hardware detail on file | TRENTP | TRENTP | | BSP | P | 7144181 |
KIRELLA HOMES, INC | BFN | C | 09/16/2021 | All paperwork on file | TRENTP | TRENTP | | BFN | C | 7108809 |
KIRELLA HOMES, INC | BFI | C | 09/16/2021 | R10 installed | TRENTP | TRENTP | | BFI | C | 7108805 |
KIRELLA HOMES, INC | BFT | C | 09/16/2021 | Engineer observation letter for exterior piers on file | TRENTP | TRENTP | | BFT | C | 7108800 |
KIRELLA HOMES, INC | BFT | P | 08/26/2021 | No site visit needed per contractor / Need to provide observation of exterior piers | TRENTP | TRENTP | | BFT | P | 7086133 |
KIRELLA HOMES, INC | BFN | P | 08/26/2021 | Open hole on file 2600 psf, rest of paperwork on file / Need to complete BFT | TRENTP | TRENTP | | BFN | P | 7085904 |
KIRELLA HOMES, INC | BFI | P | 07/26/2021 | Image upload only / Pending field inspection | TRENTP | TRENTP | | BFI | P | 7048222 |
KIRELLA HOMES, INC | BFN | P | 07/26/2021 | Need to provide open hole to confirm bearing capacity of foundation design / Footing/foundation observation states exterior piers were not inspected, will need to provide observation or request inspection / Foundation design (2400) and foundation observation on file | TRENTP | TRENTP | | BFN | P | 7048213 |
KIRELLA HOMES, INC | BFT | P | 07/26/2021 | Need to provide open hole / Footing observation and soils report on file | TRENTP | TRENTP | | BFT | P | 7048209 |
KIRELLA HOMES, INC | BFT | P | 07/16/2021 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFT | P | 7038771 |
KIRELLA HOMES, INC | BFN | P | 07/16/2021 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFN | P | 7038770 |
ROMERO ELECTRIC, INC. | E= | C | 01/27/2022 | | BRET | BRET | | E= | C | 7252000 |
ROMERO ELECTRIC, INC. | E= | R | 01/26/2022 | gfci protect both receptacles by water heater, install box extension for fireplace switch, install intersystem bond terminal 25 amp a/c installed | BRET | BRET | | E= | R | 7250968 |
ROMERO ELECTRIC, INC. | E= | R | 01/26/2022 | gfci protect both receptacles by water heater, install box extension for fireplace switch, install intersystem bond terminal 25 amp a/c installed | BRET | BRET | | E= | R | 7250969 |
ROMERO ELECTRIC, INC. | ES | C | 09/27/2021 | Residential Underground: 100-amp 3 wire service upgrade, no action required by utlity. / | TOMC | TOMC | | ES | C | 7120365 |
ROMERO ELECTRIC, INC. | ER | C | 09/27/2021 | 1 - # 4 AL , 2 - # 10 , irreversible ufer , slab on grade | TOMC | TOMC | | ER | C | 7120364 |
ROMERO ELECTRIC, INC. | EUG | C | 09/03/2021 | #2al from ped to house in back | MATTHEW | MATTHEW | | EUG | C | 7097481 |
THE FURNACE GUY HEATING & COOLING | H= | C | 01/26/2022 | Whole house ventilation being achieved through exhaust fan located in bathroom / Whole house ventilation switch located in bathroom / | JHORSMAN | JHORSMAN | | H= | C | 7250474 |
THE FURNACE GUY HEATING & COOLING | H= | P | 01/20/2022 | PROPERLY TERMINATE WATER HEATER VENTING/ NO POWER TO WHOLE HOUSE FAN AT TIME OF INSPECTION/ LABEL WHOLE HOUSE VENTILATION SWITCH, UNABLE TO LOCATE AND DETERMINE WHICH SWITCH OPERATES FAN/ Whole house ventilation being achieved through exhaust fan located in powder room / Unable to locate whole house ventilation switch / NOTE / NO OUTSIDE AIR TO FURNACE RETURN / DIRECT VENT FURNACE / DIRECT VENT TANKLESS WATER HEATER / A/C COMPLETE / | JHORSMAN | JHORSMAN | | H= | P | 7244868 |
ROCKY MOUNTAIN MECHANICAL, LLC | HC | C | 10/11/2021 | PER HO COMMENTS ON SEPTEMBER 3, 2021, UNDERGROUND LINE WAS GOOD FOR 409K BTUS/ TOTAL ADDED BTUS TO EXISTING LOAD IS 267K BTUS | JHORSMAN | JHORSMAN | | HC | C | 7137229 |
ROCKY MOUNTAIN MECHANICAL, LLC | HI | C | 10/11/2021 | 10 LB TEST OK/ 1 1/4 INCH MAIN / 1 FURNACE / 1 TANKLESS WATER HEATER / 1 FIREPLACE / | JHORSMAN | JHORSMAN | | HI | C | 7137219 |
WESTERN FIREPLACE SUPPLY, INC. | HV | C | 09/29/2021 | MAIN LEVEL FIREPLACE CLEARANCE TO COMBUSTIBLES AND VENT TERMINATION OK / | JHORSMAN | JHORSMAN | | HV | C | 7124277 |
THE FURNACE GUY HEATING & COOLING | HSP | P | 09/13/2021 | DUCT LEAKAGE REPORT RECEIVED, SEE IMAGES | JHORSMAN | JHORSMAN | | HSP | P | 7104069 |
THE FURNACE GUY HEATING & COOLING | HRR | C | 09/10/2021 | PER CONTRACTOR ATTIC WILL BE SPRAY FOAM, NO DUCT LEAKAGE REPORT REQUIRED/ PER CONTRACTOR FIREPLACE WILL BE INSTALLED AT A LATER TIME AFTER A FRAMING CHANGE, DO NOT CLEAR HI INSPECTION UNTIL HV INSPECTION IS CALLED/ IN PROCESS OF GETTING A 2 LB SYSTEM UPGRADE FOR GAS SYSTEM FROM BLACK HILLS/ AT FINAL WILL NEED 2 LB APPROVAL LETTER, MEDIUM PRESSURE STENCILING IN PLACE, AND REGULATORS INSTALLED/Whole house ventilation being achieved through exhaust fan located in powder room / Verify whole house ventilation switch location at final / NOTE/ NO OUTSIDE AIR TO FURNACE RETURN/ DIRECT VENT FURNACE / DIRECT VENT TANKLESS WATER HEATER / A/C ROUGH, COIL AND LINESET / | JHORSMAN | JHORSMAN | | HRR | C | 7102844 |
JR WHITNEY PLUMBING COMPANY | HC | C | 09/03/2021 | ADDED UP TO 409K BTUS TO EXISTING LOAD | JHORSMAN | JHORSMAN | | HC | C | 7097196 |
JR WHITNEY PLUMBING COMPANY | HO | C | 09/03/2021 | 10 LB TEST OK/ ADDED 75 FEET OF 1 1/4 INCH PE WITH TRACER WIRE FROM METER TO NEW GUEST HOUSE GOOD FOR UP TO 409K BTUS/ OK TO COVER | JHORSMAN | JHORSMAN | | HO | C | 7097192 |
DISTINGUISHED RADIANT HEATING AND PLUMBING LLC | PBP | C | 01/26/2022 | | JOSEPHD | JOSEPHD | | PBP | C | 7250889 |
MD SERVICE PLUMBING, INC. | P= | C | 01/26/2022 | | JOSEPHD | JOSEPHD | | P= | C | 7250878 |
MD SERVICE PLUMBING, INC. | PTO | C | 09/24/2021 | WATER HEATER VENT TEST OK note: contractor stated that insulation will be above water lines on trusses check at final, | JOSEPHD | JOSEPHD | | PTO | C | 7119369 |
MD SERVICE PLUMBING, INC. | PB | C | 09/21/2021 | double cleanout outside | JOSEPHD | JOSEPHD | | PB | C | 7114555 |
MD SERVICE PLUMBING, INC. | PTO | P | 09/21/2021 | need to test water heater vent, how is water piping in attic being freeze protected?, missing water supply to master toilet, rest ok note: double cleanout outside, vtr 3 | JOSEPHD | JOSEPHD | | PTO | P | 7114554 |
DISTINGUISHED RADIANT HEATING AND PLUMBING LLC | PWO | C | 09/02/2021 | note: pipe run from existing house by final check connection in house, pre-existing well | JOSEPHD | JOSEPHD | | PWO | C | 7095255 |
MD SERVICE PLUMBING, INC. | PB | P | 07/30/2021 | need cleanout for junction at sewer and building drain (P3005.2.3), no water stubbed in at this time, rest ok | JOSEPHD | JOSEPHD | | PB | P | 7055665 |
KIRELLA HOMES, INC | XBS | T | 10/18/2021 | PAID (REC#1815832): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised fasteners at porches | SHELLEY | SHELLEY | | XBS | T | 7144573 |