CQL-2000 CONSTRUCTORS, LLC. | B= | C | 01/19/2022 | All other required Final inspections are complete. (This is a computer generated result) | ADAML | ADAML | | B= | C | 7243959 |
CQL-2000 CONSTRUCTORS, LLC. | B= | P | 01/19/2022 | Final items OK pending all other finals. Additional Inspections Required (computer generated): REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 7243315 |
CQL-2000 CONSTRUCTORS, LLC. | B16 | P | 12/13/2021 | Changed to B16 / Provided final item courtesy walk through / Flush valve in Restroom 116 needs to be on open side / Need accessible hardware in dry sauna room / Complete all roughs and MEP finals | ADAML | ADAML | | B16 | P | 7206729 |
CQL-2000 CONSTRUCTORS, LLC. | BFR | P | 11/29/2021 | Frame items OK pending all other required inspections | ADAML | ADAML | | BFR | P | 7190106 |
CQL-2000 CONSTRUCTORS, LLC. | BSP | P | 10/07/2021 | Drywall screw inspection not required for non rated walls / This is a 2B building with no ratings | ADAML | ADAML | | BSP | P | 7133072 |
CQL-2000 CONSTRUCTORS, LLC. | BFR | P | 09/15/2021 | Missing kicker bracing above Office 107 and above entry to hallway at Reception / May upload photos to a new inspection request / Reviewed accessible elements / Discussed removing closer at entrance door to Shower Room 115 due to lack of 12" on push side | ADAML | ADAML | | BFR | P | 7107948 |
CQL-2000 CONSTRUCTORS, LLC. | BFT | P | 08/12/2021 | Attach mechanical, electrical, and plumbing / Rebar reinforcement OK for pad for Nitrogen tank 113 | ADAML | ADAML | | BFT | P | 7070520 |
R&R ELECTRIC | E= | C | 01/19/2022 | plans spliced and received pictures of the panel labeled aic rating via email OK | CRAIGS | CRAIGS | | E= | C | 7243033 |
R&R ELECTRIC | E= | P | 01/18/2022 | splice plans with the corrected aic rating and upload picture of panel aic rating labeling | CRAIGS | CRAIGS | | E= | P | 7242111 |
WESTERN STATES FIRE PROTECTION COMPANY | E= | C | 11/16/2021 | FIRE ALARM INSPECTION: F/A above ceiling OK | CRAIGS | CRAIGS | | E= | C | 7178315 |
R&R ELECTRIC | E= | P | 11/12/2021 | GFCI protect Dryer receptacles / Label AIC on panel & schedule / AIC rating on drawings for panel B shows 45k AIC and 10k AIC brkrs installed / Install shower trim for light / Roof - Ok / Splice required, please submit splice for changes in scope. If unfamiliar in submitting electronic splice, please click the following link: https://youtu.be/dG3kHpgDP0w / | BRETC | BRETC | | E= | P | 7175015 |
R&R ELECTRIC | ER | C | 11/11/2021 | above ceiling OK | CRAIGS | CRAIGS | | ER | C | 7173535 |
R&R ELECTRIC | ER | P | 09/17/2021 | Attach Fire Alarm to permit for next inspection / All FA devices will be in ceilings per FA contractor | BRETC | BRETC | | ER | P | 7110467 |
R&R ELECTRIC | ESL | C | 09/15/2021 | 1- front 3/4" to reception | BRETC | BRETC | | ESL | C | 7108150 |
R&R ELECTRIC | ER | R | 09/15/2021 | All walls & hard lids (3) only - Ok / Attach Fire Alarm to permit / Discussed accessibility requirements with contractor / Electrical Rough ok, FA not complete ---------------do not sheetrock--------------- / | BRETC | BRETC | | ER | R | 7108149 |
REEVES SPECIALTY SERVICES, INC. | H= | C | 01/19/2022 | PLAN SPLICE DATED 1/13/22 - ENGINEER ADDRESS HOW SAUNA MEETS CODE CRITERIA. A VENT WAS ADDED INTO THE TOP OF THE SAUNA. OTHER ITEMS HAVE BEEN ADDRESSED. | MARKB | MARKB | | H= | C | 7243958 |
REEVES SPECIALTY SERVICES, INC. | H= | R | 12/29/2021 | NOTE ADDED 12/30/21 Air vent is above radio and can be closed off when radio is pushed up into place, appears vent is for radio only and not to meet code. FOR FINAL - How does sauna comply with 2015 IMC section 914? Bolt down mini-split condenser on roof. Tag gas piping at meter with correct suite number. Remove gas regulator from water heater piping as gas is a low pressure system. | MARKB | MARKB | | H= | R | 7224314 |
REEVES SPECIALTY SERVICES, INC. | HC | C | 12/29/2021 | ADDING WATER HEATER TO METER NUMBER 268895 PER PLAN | MARKB | MARKB | | HC | C | 7224309 |
REEVES SPECIALTY SERVICES, INC. | HI | C | 12/29/2021 | Gas piping installed per plan splice. | MARKB | MARKB | | HI | C | 7224306 |
REEVES SPECIALTY SERVICES, INC. | HSP | P | 12/29/2021 | TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | HSP | P | 7223063 |
REEVES SPECIALTY SERVICES, INC. | HV | C | 12/13/2021 | WATER HEATER VENT COMPLETE. | MARKB | MARKB | | HV | C | 7206488 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/13/2021 | --SPOKE WITH GENERAL CONTRACTOR ON SITE: Need approved plan splices for installed gas line, existing RTU schedule and ventilation table. Still need to inspect Sauna to see that it complies with code, roof and provide test and balance report. ABOVE CEILING DUCT - NEW EXHAUST FANS/DUCTS INSTALLED PER PLAN SPLICE. MINI-SPLIT CONDENSATE AND THERMOSTATS COMPLETE. Still need condenser and exhaust on roof. | MARKB | MARKB | | HD | P | 7206485 |
REEVES SPECIALTY SERVICES, INC. | HI | P | 12/01/2021 | 10 LB TEST OK / Still need gas pipe shown on approved plans / | MATTM | MATTM | | HI | P | 7194371 |
REEVES SPECIALTY SERVICES, INC. | HV | P | 12/01/2021 | INSPECTION FOR WATER HEATER VENT ONLY: Water heater intake cannot be longer than the vent per page 21 / WATER HEATER VENT ROOFTOP TERMINATION LOCATION OK / | MATTM | MATTM | | HV | P | 7194368 |
REEVES SPECIALTY SERVICES, INC. | HSP | R | 11/24/2021 | Plan splices need to be approved through RBD plan review, inspector cannot take un approved plans. If unfamiliar with electronic submittal please click the following link: https://youtu.be/-R4mAh8LBCM / | MARKB | MARKB | | HSP | R | 7188143 |
REEVES SPECIALTY SERVICES, INC. | HSP | P | 11/18/2021 | HAD PHONE CONVERSATION WITH DEBRA (REEVES) - She is working with the engineer to address ventilation for changing rooms and a gas plan. Gave her Becky Allens number for questions to deal with splice. Will need mechanical contractors attached to permit to claim water heater vent and sauna - current vent in permit scope is for dryer. Sauna is shown on plans but need to be inspected to meet code criteria. Once plan splice is complete, need to complete all rough inspections. | MARKB | MARKB | | HSP | P | 7181663 |
REEVES SPECIALTY SERVICES, INC. | HD | R | 11/17/2021 | left message for call ahead at 3:42. No contractors on site at 4:13. No plan splices on file, still need to address all previous inspection comments. STOPPED INSPECTION. Will need contractor on site for next inspection to address issues. | MARKB | MARKB | | HD | R | 7181145 |
REEVES SPECIALTY SERVICES, INC. | HD | R | 11/12/2021 | --INSPECTION NOTES FROM PREVIOUS INSPECTION STILL HAVE NOT BEEN ADDRESSED. --CONTRACTOR TO CORRECT PERMIT SCOPE - THIS IS NOT A MANUFACTURED HOME, JUST NEEDS TO BE 1 GAS PIPING OUTLET BUT STILL CANNOT FIND GAS PIPING ON PLANS. MECHANICAL CONTRACTOR CANNOT PERMIT WATER HEATER. STILL NEED GAS PIPING AND WATER HEATER VENT INSPECTIONS ONCE GAS PIPING IS SHOWN ON PLANS. --MECHANICAL OR GENERAL CONTRACTORS NOT ON SITE. ABOVE CEILING DUCT - FLEX AND DIFFUSERS ARE COMPLETE IN ROOMS 101, 102, 104, 105 & 106. | MARKB | MARKB | | HD | R | 7174972 |
REEVES SPECIALTY SERVICES, INC. | HD | T | 09/24/2021 | PAID (REC#1822238): SITE LOCKED - NO ACCESS | MARKB | MARKB | | HD | T | 7120028 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 09/16/2021 | ----FURTHER RESEARCH REQUIRED FOR NITROGEN STORAGE TANK, OXYGEN GENERATOR, SAUNA, STEAM ROOM NOT SHOWN ON PLANS. CANNOT FIND GAS PLAN FOR NEW GAS WATER HEATER, AND CHANGING ROOMS DO NOT SHOW ANY VENTILATION AIR OR EXHAUST. MORE NOTES TO FOLLOW.---- ABOVE CEILING DUCT - EXHAUST DUCT/FANS AND SUPPLY AIR DUCTS ABOVE HARD LIDS OK TO COVER. SUPPLY BRANCHES FOR RTU'S 1 & 2 OK TO INSULATE. Returns, transfers, dryer duct or EF-5 not complete at this time. | MARKB | MARKB | | HD | P | 7109326 |
REEVES SPECIALTY SERVICES, INC. | HD | L | 09/15/2021 | SITE LOCKED AT 4:20 | MARKB | MARKB | | HD | L | 7108674 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | P= | C | 01/18/2022 | | LEE | LEE | | P= | C | 7241290 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | P= | P | 01/05/2022 | NEED PLANS TO REFLECT LOCATION OF FOUR AAV'S AS NOTED ON OTHER INSPECTIONS -- REST OK | LEE | LEE | | P= | P | 7230076 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | P= | P | 12/29/2021 | NEED AAV APPROVAL, NEED STEAM SHOWER DELETED FROM PLANS AND EJECTOR TIE IN ISSUES RESOLVED -- REST OK | LEE | LEE | | P= | P | 7224216 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | P= | P | 12/14/2021 | NEED PTO INSPECTION -- THE EJECTOR IS STILL PIPED ON THE 2" RESTROOM LAV STACK ( WET VENT FOR WATER CLOSET ) PLANS SHOW IT PIPED TO A 3" STACK IN OTHER WALL -- EJECTOR MISSING GATE VALVE -- STILL NEED ENGINEER APPROVAL FOR AAV'S -- TOILET TANK MISSING -- EXPANSION TANK PIPED ON HOT SIDE OF W/H -- NEED STEAM SHOWER DELETED ON PLANS | LEE | LEE | | P= | P | 7208813 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | PTO | P | 09/21/2021 | STILL NEED EJECTOR / TIE-IN POINT APPROVAL -- NEED ENGINEER TO APPROVE AAV X-4 AND STEAM SHOWER DELETED -- REST OK -- CHECK W/H PIPING AND CYRO VENT TIE-IN AT CONNECTION TO UNIT AT FINAL | LEE | LEE | | PTO | P | 7114938 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | PTO | P | 09/15/2021 | NEED APPROVAL FOR EJECTOR AT SINK ROOM # 102 -- NEED VENT FOR SAME SINK -- IF APPROVED NEED PLANS TO REFLECT TIE-IN AT RESTROOM LAV WET VENT -- NAIL / SCREW PROTECTION INCOMPLETE THRU-OUT -- NEED CLOSET FLANGES ANCHORED -- NEED COPPER CYRO VENT INSTALLED ( SEE NOTE 7 ) -- DOMESTIC HOT / RE-CIRC NOT INSULATED -- NEED AAV APPROVAL X-4 ( RESTROOMS, LAUNDRY AND BREAK SINK ) -- NEED PLANS REVISED TO SHOW STEAM SHOWER DELETED -- NOTE: SHOWER NOT FRAMED CORRECTLY -- # 117 RESTROOM WALL OK | LEE | LEE | | PTO | P | 7107879 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | PB | P | 08/17/2021 | PENDING APPROVAL FOR SINK EJECTOR ROOM # 102 | LEE | LEE | | PB | P | 7074556 |
WESTERN STATES FIRE PROTECTION COMPANY | XES | T | 01/19/2022 | PAID (REC#1861337): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revised panel AIC rating | SHELBY | SHELBY | | XES | T | 7244269 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | XPS | P | 01/13/2022 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: See engineer's letter in permit images. | SHANEN | SHANEN | | XPS | P | 7238199 |
REEVES SPECIALTY SERVICES, INC. | XMS | P | 01/13/2022 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Added clarification notes for sauna | JUSTINC | JUSTINC | | XMS | P | 7237936 |
WESTERN STATES FIRE PROTECTION COMPANY | XES | T | 01/11/2022 | PAID (REC#1836017): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revised one line///Panel B is not being replaced | SHELBY | SHELBY | | XES | T | 7236000 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | XPS | T | 01/05/2022 | PAID (REC#1836903) PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta G revisions: Adjusted sheet P201. | SHANEN | SHANEN | | XPS | T | 7228805 |
REEVES SPECIALTY SERVICES, INC. | XMS | P | 12/20/2021 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Dressing room exhaust, ventilation schedule, gas | JUSTINC | JUSTINC | | XMS | P | 7215372 |
REEVES SPECIALTY SERVICES, INC. | XMS | T | 12/20/2021 | PAID (REC#1831261): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Added Gas | JUSTINC | JUSTINC | | XMS | T | 7214750 |
REEVES SPECIALTY SERVICES, INC. | XMS | T | 11/30/2021 | PAID (REC#1826127): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Added exhaust to dressing rooms, modified schedules | JUSTINC | JUSTINC | | XMS | T | 7191294 |
BEFORT PLUMBING AND HEATING COMPANY, INC. | XPS | T | 10/06/2021 | PAID (REC#1825370): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta E revisions: adjusted sheet P201 and P701. | SHANEN | SHANEN | | XPS | T | 7131651 |