GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 01/21/2022 | | NATHAN | NATHAN | | B= | C | 7246036 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 12/15/2021 | With completed required inspections B= okay. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, GUARANTEE ELECTRICAL CONTRACTING, LLC Electrical Final Inspection is not Completed yet, HEATING & PLUMBING ENGINEERS, INC Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7209719 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/09/2021 | Light gauge steel framing ok pending all other MEP required inspections | TIMOTHYS | TIMOTHYS | | BFR | P | 7171140 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 12/15/2021 | Corrections made / High winds - was able to complete using Facetime with contractor. | BRETC | BRETC | | E= | C | 7210374 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 12/14/2021 | Need fine stranded lugs or reducing pins for 125 amp shunt and 80 amp CB disconnect, label 80 amp CB disconnect / Install EPO switch | BRETC | BRETC | | E= | P | 7209151 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 11/16/2021 | WALL IN ROOMS 3621, 3619 A. 3619 NORTH WALL OK ABOVE CEILING IN ROOMS 3619, 3621 OK 6 - 3/4" EMT FROM ELECTRICAL ROOM TO ROOM 3619 OK | CRAIG | CRAIG | | ER | P | 7178872 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 01/20/2022 | PLAN SPLICE CORRECTED THROUGH PLAN REVIEW - DISCUSSED WITH PLAN REVIEWER. | MARKB | MARKB | | H= | C | 7245444 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 01/13/2022 | NO BALANCE REPORT ATTACHED TO INSPECTION REQUEST | MARKB | MARKB | | H= | P | 7238524 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 01/10/2022 | FINAL PENDING - Provide test and balance report PLAN SPLICE ON FILE | MARKB | MARKB | | H= | P | 7233263 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 12/20/2021 | FINAL PENDING - Need approved plan splice for added return. Provide test and balance report. PIPE INSULATION COMPLETE. | MARKB | MARKB | | H= | P | 7214225 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 12/17/2021 | FINAL PENDING - Insulate hydronic piping, need pan splice for second return and provide test and balance report. DUCT AND GRILLS COMPLETE. HYDRONIC PIPING UNDER OPERATING PRESSURE. | MARKB | MARKB | | H= | P | 7213036 |
HEATING & PLUMBING ENGINEERS, INC | H= | L | 12/16/2021 | COULD NOT GET A HOLD OF CALL AHEAD PROVIDED. | MARKB | MARKB | | H= | L | 7211826 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 11/17/2021 | ----ENGINEER TO ADDRESS: Diffuser and transfer sizes differ from approved plan---- ABOVE CEILING DUCT - SUPPLY DUCT AND COIL INSTALLED PER PLAN OK TO WRAP. | MARKB | MARKB | | HD | P | 7180922 |
HEATING & PLUMBING ENGINEERS, INC | XMS | P | 01/10/2022 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Mechanical | TCRIPPEN | TCRIPPEN | | XMS | P | 7233260 |
HEATING & PLUMBING ENGINEERS, INC | XMS | T | 01/06/2022 | PAID (REC#1834499) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: revised ducts in Cath room. | TCRIPPEN | TCRIPPEN | | XMS | T | 7230310 |
HEATING & PLUMBING ENGINEERS, INC | XMS | T | 11/29/2021 | PAID (REC#1828273): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout and schedule revised | JUSTINC | JUSTINC | | XMS | T | 7190248 |
HEATING & PLUMBING ENGINEERS, INC | XMS | T | 11/09/2021 | PAID (REC#1823301): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouds | DALEH | DALEH | | XMS | T | 7170867 |