HILL COMMERCIAL CONSTRUCTION, LLC | B= | C | 03/11/2022 | All other required Final inspections are complete. (This is a computer generated result) | LONNYS | LONNYS | | B= | C | 7298346 |
HILL COMMERCIAL CONSTRUCTION, LLC | B= | P | 03/04/2022 | verification of knee and toe protection on file. Additional Inspections Required (computer generated): MAGNUM EDGE,INC. Mechanical Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7290228 |
HILL COMMERCIAL CONSTRUCTION, LLC | B= | P | 02/18/2022 | missing knee and toe protection in staff lounge / pending other required inspections building final OK / OK to submit photo verification of corrected items / -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): PINE VALLEY ELECTRIC, INC. Electrical Final Inspection is not Completed yet, MAGNUM EDGE,INC. Mechanical Final Inspection is not Completed yet, BULLETPROOF PLUMBING AND HEATING Plumbing Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7275693 |
HILL COMMERCIAL CONSTRUCTION, LLC | B= | P | 02/17/2022 | pending other required inspections / still need to inspect staff lounge sink when installed / rest of final OK -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), PINE VALLEY ELECTRIC, INC. Electrical Final Inspection is not Completed yet, MAGNUM EDGE,INC. Mechanical Final Inspection is not Completed yet, BULLETPROOF PLUMBING AND HEATING Plumbing Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7273913 |
HILL COMMERCIAL CONSTRUCTION, LLC | BFR | P | 12/28/2021 | GYP ATTACHMENT AT 1 HOUR FIRE PARTITION IN STAFF LOUNGE // gyp attachment OK per UL U465 | LONNYS | LONNYS | | BFR | P | 7221992 |
HILL COMMERCIAL CONSTRUCTION, LLC | BFR | P | 12/17/2021 | pending other required inspections / all interior light gauge steel framing walls and hard lids OK / reviewed accessible elements with site rep | LONNYS | LONNYS | | BFR | P | 7212823 |
PINE VALLEY ELECTRIC, INC. | E= | C | 03/01/2022 | Corrections made. | AARONR | AARONR | | E= | C | 7285209 |
PINE VALLEY ELECTRIC, INC. | E= | P | 02/18/2022 | Cant phase #8 white wire in air compressor --- Need Arc flash stickers --- Label Air compressor disconnect....................Rest OK. | AARONR | AARONR | | E= | P | 7276210 |
PINE VALLEY ELECTRIC, INC. | ER | C | 01/24/2022 | All above ceilings rough completed. | AARONR | AARONR | | ER | C | 7247550 |
PINE VALLEY ELECTRIC, INC. | ER | P | 01/20/2022 | Exam rooms 1 & 2 drop ceilings OK. --- Hall and office drip ceilings OK. | AARONR | AARONR | | ER | P | 7245097 |
PINE VALLEY ELECTRIC, INC. | ER | P | 12/17/2021 | Corrections made / All walls and hard lids only - Ok | BRETC | BRETC | | ER | P | 7213497 |
PINE VALLEY ELECTRIC, INC. | ER | R | 12/14/2021 | Need documentation on all connectors if they are HCF rated / Green HCF cable will need to be installed per manufacture specs / Discussed ADA requirements / Discussed listed raceway above 7'-6" in patient care areas / Complete Re-Inspect | BRETC | BRETC | | ER | R | 7208405 |
PINE VALLEY ELECTRIC, INC. | ESL | C | 11/05/2021 | Rm's 104 & 105 also 118 - PVC coated GRC - Ok | BRETC | BRETC | | ESL | C | 7167560 |
PINE VALLEY ELECTRIC, INC. | ESL | P | 11/02/2021 | 7 out 9 floor boxes under dental chairs OK. --- All ran in GRC rubber coated pipe. --- Still needing rooms 104, and 105 to be inspected. | AARONR | AARONR | | ESL | P | 7162256 |
MAGNUM EDGE,INC. | H= | C | 03/11/2022 | MECHANICAL FINAL COMPLETE | TREVORH | TREVORH | | H= | C | 7298344 |
MAGNUM EDGE,INC. | H= | P | 02/10/2022 | MECHANICAL FINAL PENDING------------FORTHCOMING PLAN SPLICE FOR REMOVING NOTE # 8 AND EF-2 SHOWN AS EXISTING. | TREVORH | TREVORH | | H= | P | 7266270 |
MAGNUM EDGE,INC. | H= | P | 02/10/2022 | TEST AND BALANCE REPORT RECEIVED SEE IMAGES. MECHANICAL FINAL PENDING--------------ON SITE INSPECTION | TREVORH | TREVORH | | H= | P | 7265796 |
MAGNUM EDGE,INC. | HD | P | 12/01/2021 | NEW/RELOCATED SUPPLY AIR DUCTS OK, OK TO WRAP. FLEX INSTALLED, NO DIFFUSERS. NEW EXHAUST DUCT OK, FAN NOT INSTALLED YET. | DUSTINS | DUSTINS | | HD | P | 7193222 |
BULLETPROOF PLUMBING AND HEATING INC. | P= | C | 02/24/2022 | | TAYLOR | TAYLOR | | P= | C | 7281335 |
BULLETPROOF PLUMBING AND HEATING INC. | PTO | C | 02/24/2022 | revised plans ok. | TAYLOR | TAYLOR | | PTO | C | 7281319 |
BULLETPROOF PLUMBING AND HEATING INC. | P= | L | 02/18/2022 | field cancelled. | TAYLOR | TAYLOR | | P= | L | 7275647 |
BULLETPROOF PLUMBING AND HEATING INC. | PTO | P | 12/08/2021 | still need revised plans as previously noted, test ok. | TAYLOR | TAYLOR | | PTO | P | 7202102 |
BULLETPROOF PLUMBING AND HEATING INC. | PTO | P | 12/06/2021 | test DWV, revise plans for ( new sizing and layout for H2O, aav at break room sink, waste connection of vacuum pump ), need to insulate all DHW piping. | TAYLOR | TAYLOR | | PTO | P | 7199025 |
BULLETPROOF PLUMBING AND HEATING INC. | PB | C | 11/05/2021 | | TAYLOR | TAYLOR | | PB | C | 7167036 |
MAGNUM EDGE,INC. | XMS | T | 02/11/2022 | PAID (REC#1849474): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised exhaust | JUSTINC | JUSTINC | | XMS | T | 7268360 |
BULLETPROOF PLUMBING AND HEATING INC. | XPS | T | 12/13/2021 | PAID (REC#1829302): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 2 revisions: Adjusted sheet P001, P111 and P111A. | SHANEN | SHANEN | | XPS | T | 7206263 |
PINE VALLEY ELECTRIC, INC. | XES | P | 11/16/2021 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised circuit numbers, revised panel schedule, updated background. | BERTHA | BERTHA | | XES | P | 7179084 |
BULLETPROOF PLUMBING AND HEATING INC. | XPS | T | 11/16/2021 | PAID (REC#1827178): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 1 revisions: Adjusted sheet P111 and P111A. | SHANEN | SHANEN | | XPS | T | 7178023 |
HILL COMMERCIAL CONSTRUCTION, LLC | XBS | P | 11/15/2021 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Add dishwasher. | MICHAELA | MICHAELA | | XBS | P | 7177192 |