THE COPESTONE COMPANY | B= | C | 04/21/2022 | | LONNYS | LONNYS | | B= | C | 7346278 |
THE COPESTONE COMPANY | B= | P | 04/15/2022 | Temp CO: Pending F=, P=, B= ( Expires: 5/15/2022 12:00:00 AM) | BRITNEY | BRITNEY | | B= | P | 7340449 |
THE COPESTONE COMPANY | B= | P | 04/14/2022 | building final OK pending other required inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), PEAK HEATING & AIR CONDITIONING, INC. Mechanical Final Inspection is not Completed yet, SOCO PLUMBING Plumbing Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7338267 |
THE COPESTONE COMPANY | BSP | R | 02/07/2022 | inspection cancelled per call from GC - changed inspection from building final (not ready) to bsp inspection | BRIANB | BRIANB | | BSP | R | 7261783 |
THE COPESTONE COMPANY | BFR | P | 01/24/2022 | pending other required inspections / interior light gauge steel framing OK / reviewed accessible elements with site rep | LONNYS | LONNYS | | BFR | P | 7247587 |
ELECTRIC TECH INC. | E= | C | 04/13/2022 | Corrections made / Video sent to phone | BRETC | BRETC | | E= | C | 7336299 |
ELECTRIC TECH INC. | E= | P | 04/12/2022 | Label water where disconnect is located / Need to GFCI receptacle in far room 6' from water / Need to install 1-pole 30amp brkr for water heater - 20 amp installed | BRETC | BRETC | | E= | P | 7334873 |
ELECTRIC TECH INC. | EP | C | 04/12/2022 | Transformer and panel R3B - Ok | BRETC | BRETC | | EP | C | 7334870 |
ELECTRIC TECH INC. | ER | C | 04/12/2022 | Fire Alarm was permit N95311 Unit 302 not 202 | BRETC | BRETC | | ER | C | 7334869 |
ELECTRIC TECH INC. | ER | R | 02/17/2022 | Fire Alarm will need to be attach to this permit / Ceiling rough ok, FA not complete ---------do not close ceiling-------------- / | BRETC | BRETC | | ER | R | 7275047 |
ELECTRIC TECH INC. | ER | P | 01/24/2022 | All wall rough OK. | AARONR | AARONR | | ER | P | 7247672 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 04/15/2022 | REVISED TEST AND BALANCE REPORT RECEIVED. / | LIDO | LIDO | | H= | C | 7339996 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 04/14/2022 | FINAL PENDING: NEED REVISED TEST AND BALANCE REPORT / | LIDO | LIDO | | H= | P | 7338552 |
PEAK HEATING & AIR CONDITIONING, INC. | HSP | P | 04/14/2022 | TEST AND BALANCE REPORT REVIEW : MISSING SUITE ADDRESS (#302) / | LIDO | LIDO | | HSP | P | 7338199 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 02/24/2022 | FINAL PENDING : NEED DOCUMENTATION FOR INSULATION USED TO WRAP PVC IN PLENUM ABOVE PLENUM RETURN TO VERIFY IF MATERIAL IS PLENUM RATED / THERMOSTAT CONTROLS IN ROOM #110 ARE MORE THAN 48" ABOVE THE FLOOR. LOWER THERMOSTAT OR OK TO INSTALL LOCK BOX / MISSING THERMOSTAT IN ROOM # 114 AND 116 / NEED TEST AND BALANCE REPORT / SCREEN INSTALL ON EXHAUST ROOF TERMINATION /
| LIDO | LIDO | | H= | P | 7281755 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | C | 02/18/2022 | PVC LOCATED ABOVE CEILING PLENUM RETURN IS NOT PLENUM RATED. OK TO WRAP WITH PLENUM RATED MATERIAL (material to have a flame spread no greater than 25 and smoke development no greater than 50) / MISSING THERMOSTAT IN ROOM 110, 114 AND 116 / EXHAUST TERMINATION ON ROOF IS MISSING THE SCREEN / NEED TEST AND BALANCE REPORT / ALL SUPPLY, RETURN FLEX DUCT, GRILLS AND REGISTERS OK / | LIDO | LIDO | | HD | C | 7276753 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 01/14/2022 | DUCT ROUGH : MISSING SUPPLY BRANCH FOR ROOM #108 (install by final) / STILL NEED ROOF INSPECTION FOR DRYER AND EF-1 EXHAUST TERMINATIONS / REST OF SUPPLY, EXHAUST AND DRYER EXHAUST DUCT ROUGH OK / | LIDO | LIDO | | HD | P | 7239972 |
SOCO PLUMBING | P= | C | 04/18/2022 | | LEE | LEE | | P= | C | 7342133 |
SOCO PLUMBING | P= | P | 04/13/2022 | MISSING PLASTER TRAP AND TRAP GUARD AT W/H PAN FLOOR DRAIN -- REST OK | LEE | LEE | | P= | P | 7336862 |
SOCO PLUMBING | PTO | C | 04/13/2022 | | LEE | LEE | | PTO | C | 7336858 |
SOCO PLUMBING | PTO | P | 01/27/2022 | need plans to reflect under floor dwv and water piping, need plans to show point of connection for water and dwv, need to run 3" to washer box, need vacuum discharge on plans, in wall pipe protection and nail protection ok, water and dwv was on test, looked at dwv and water under floor in unit 250, will need to see rest of under floor and correction at washer box, | JOSEPHD | JOSEPHD | | PTO | P | 7252073 |
SOCO PLUMBING | PTO | P | 01/24/2022 | In wall DWV and domestic water only: Need pipe protection all plastic and pex piping in stud walls ( State Regulations IPC 305.1) / need 100 pound test on 200 pound test gauge for water / where is vacuum pump discharging? / need insulation domestic water per plan and code / missing nail protection through out./ | DANR | DANR | | PTO | P | 7248324 |